ID |
Date |
Author |
Operational Mode |
Subject |
286
|
Fri Nov 12 16:54:50 2010 |
Doug Preddy | Normal Running | Solenoid ramped up |
|
285
|
Thu Nov 11 15:46:40 2010 |
Doug Preddy | Other | switched to parallel cold return |
At 14:45. |
284
|
Mon Aug 9 14:27:12 2010 |
Doug Preddy | Shut Down | Helium plant shut down |
|
283
|
Mon Jun 7 09:24:47 2010 |
Doug Preddy | Quench Recovery | started flow to power leads |
|
282
|
Tue May 18 15:04:36 2010 |
Kevin Trithardt | Maintenance | Solenoid ramping up |
|
281
|
Thu May 13 14:37:13 2010 |
Doug Preddy | Quench Recovery | switching to series mode. |
|
280
|
Thu May 13 07:39:55 2010 |
Doug Preddy | Quench Recovery | solenoid quench last night |
Solenoid quenched on power lead temps last evening. I am recovering it in parallel cold return mode. C12~60K C1~50K. |
279
|
Mon May 3 07:49:54 2010 |
Doug Preddy | Quench Recovery | Solenoid quench Saturday |
Solenoid quenched at ~13:30 Saturday. Kevin came in later in the day to recover it. System was in all around mode, no flow to solenoid. Discharge pressure went over 12 bar while starting flow and tripped the compresswor. After restart solenoid was cooling well.
Monday morning 7:30 I opened CV155 to increase the cooldown rate. |
278
|
Fri Apr 9 16:07:28 2010 |
Doug Preddy | Start Up | flow to power leads started |
|
277
|
Fri Apr 9 07:34:55 2010 |
Doug Preddy | Quench Recovery | switched to parallel cold return |
Switched to parallel cold return at about 7:30 this morning
|
276
|
Thu Apr 1 11:57:55 2010 |
Doug Preddy | Start Up | started flow to power leads |
Solenoid cold. Buffer tank pressure ~3psi, so Kevin will add a bottle of helium. Started flow to power leads at 11:45 |
275
|
Mon Mar 29 09:25:52 2010 |
Kevin Trithardt | Start Up | Started cool down this morning |
|
274
|
Wed Mar 24 08:30:33 2010 |
Doug Preddy | Start Up | Start up |
Compressor started yesterday afternoon. Pumping out solenoid overnight. Cold box vacuum good. circulating helium to solenoid in Parallel warm mode, CV142 open. Purifier running. |
273
|
Mon Oct 5 11:54:58 2009 |
Doug Preddy | Normal Running | Switched TIC121 into auto mode |
|
272
|
Tue Jul 14 15:28:36 2009 |
Doug Preddy | Quench Recovery | Solenoid ramped up |
The solenoid is cold and I have started to ramp up the power supply. Some slight ripples in the power leads, but they are dieing out. Liquid level is a lot more stable this time. |
271
|
Fri Jul 10 01:10:59 2009 |
Doug Preddy | Quench Recovery | switch to parallel warm return |
|
270
|
Fri Jul 10 00:34:03 2009 |
Doug Preddy | Quench Recovery | solewnoid quench due to power bump |
Solenoid quench due to power bump caused by an airplane crash in Richmond at ~ 22:00. Compressor off. Water pump off. Restarted compressor at ~ 11:30. Cooling solenoid in parallel cold return mode by 12:15. |
269
|
Wed May 27 15:01:34 2009 |
Doug Preddy | Quench Recovery | power leads |
Power leads are cold. There is still a small ripple. The power supply can be ramped up as soon as the ripples die out. |
268
|
Wed May 27 13:37:22 2009 |
Doug Preddy | Quench Recovery | switch to series mode |
Switched to series mode at ~11:00. Built liquid to 55% by 13:30. Started flow to the power leads. |
267
|
Wed May 27 08:06:00 2009 |
Doug Preddy | Quench Recovery | Solenoid quenched at 5:00 |
The solenoid quenched at 5:00 this morning due to power lead temps. The temps started oscillating about 10 minutes before the trip. The compressor and the cold box stayed on. The flow to the solenoid was stopped.
The solenoid flow was started in parallel cold return at ~7:20. |
266
|
Wed Dec 10 15:44:58 2008 |
Doug Preddy | Maintenance | Repairs to solenoid power supply |
Klaus and company pulled the ramp rate card out of the solenoid power supply. Operational checks were done and the rate switch was cleaned. The card was reinserted and the ramp rate was checked. The power supply seems to ramp at a proper rate in all positions. ***Note*** The output voltage of the power supply is proportional to the ramp rate. The faster the ramp rate the higher the output voltage. |
265
|
Wed Dec 10 15:41:04 2008 |
Doug Preddy | Shut Down | shuttting down solenoid |
shuttting down solenoid for winter shutdown. |
264
|
Wed Nov 5 16:33:52 2008 |
Doug Preddy | Normal Running | sbplc light out |
On main menu the sbplc light was black. All vacuum systems looked good, but there was no control of any device. Jane reset the IOC. It is hosted by sundance. |
263
|
Sun Oct 5 18:54:27 2008 |
Doug Preddy | Quench Recovery | Solenoid Quench ~16:30 |
Restarted compressor and flow to coldbox by 18:30 |
262
|
Sun Oct 5 11:12:48 2008 |
Doug Preddy | Normal Running | M9B:V1 interlocks and a IOC crash |
M9A:V1 was removed this shutdown. It's "in" limit is required to allow M9B:V1 to be opened. I have bypassed the interlocks on M9B:V1 until the M9A:V1 limits can be jumpered. Don Dale and George Clark have been informed.
Also an IOC crashed so the data pages were not updating. Evgeny rebooted the IOC. All is now fixed. |
261
|
Fri Sep 26 09:50:18 2008 |
Doug Preddy | Quench Recovery | started flow in parallel cold return mode |
|
260
|
Fri Sep 26 09:45:18 2008 |
Doug Preddy | Quench Recovery | Solenoid quenched at 7:50 |
Compressor on. Turbines started. Vacuum system recovering. |
259
|
Fri Sep 26 09:44:25 2008 |
Doug Preddy | Maintenance | Water flow interlock restored |
yesterday |
258
|
Tue Sep 9 15:04:23 2008 |
Doug Preddy | Maintenance | Jumpered interlock for diff pump water flow |
Jumpered interlock for diff pump water flow in Proteus box. |
257
|
Thu Sep 4 10:02:55 2008 |
Doug Preddy | Normal Running | ramping down solenoid |
Solenoid power supply will be turned off for Fall shutdown. |
256
|
Sun Aug 24 06:45:14 2008 |
Doug Preddy | Quench Recovery | switch to series mode |
|
255
|
Sat Aug 23 17:02:38 2008 |
Doug Preddy | Quench Recovery | Solenoid quenched |
The solenoid quenched this afternoon at ~12:30. The compressor shut down. Fault lights were cold box trip.
Restarted the compressor by 3:30 and started flow to the solenoid by 4:15.
Peter Yandon came down with Ops' radio to investigate the radios may trip the solenoid. When the radio is keyed the vacuum guages jump. CG1, CG5 and the pirani gauges. This would trip of the refrigerator. More investigation to happen tomorrow and on maintenance day. |
254
|
Sat Jul 26 01:29:21 2008 |
Doug Preddy | Quench Recovery | power leads |
ops will monitor liquid level. When it's at 60% they will come down and open the power lead valve. When the temperature ripples die out the solenoid can be energized. |
253
|
Sat Jul 26 01:06:04 2008 |
Doug Preddy | Quench Recovery | Refrigerator in series mode |
Switched to series mode. Solenoid ~8K, starting to build liquid. |
252
|
Fri Jul 25 21:48:15 2008 |
Doug Preddy | Quench Recovery | another quench |
System was stable and solenoid ramped up at 4:00 today. At about 7:30 it tripped off again. I came in and restarted the compressor and am now cooling in parallel cold return mode. Solenoid is at ~30K. I talked to Kevin and he will get the power leads on tomorrow morning. Once they are stable the power supply can be ramped up.
I phoned Curtis, but there was no answer (he may be on holidays??) |
251
|
Thu Jul 24 16:28:50 2008 |
Doug Preddy | Quench Recovery | power bump |
There was a power bump at ~15:00 today. All mseon hall cooling water went off. Compressor tripped. Main magnet went off.
Restarted compressor after water pumps came back on. Started flow to the cold box. Compressor outlet pressure went >12 Bar and tripped of the compressor. Restarted again and am now cooling in parallel cold return. Solenoid ~25K. |
250
|
Tue Jul 15 08:47:13 2008 |
Doug Preddy | Normal Running | Screen grab of normal running |
Solenoid was recovered on Sunday July 13. The power leads started to ripple slightly this morning, so I cycled HIC142. No real change. |
Attachment 1: july_15_08_0841.jpg
|
|
Attachment 2: july_15_08_0846.jpg
|
|
249
|
Sun Jul 13 20:17:24 2008 |
Doug Preddy | Other | Helium refrigerator problems |
In early June the helium compressor was running with the solenoid cold. A vavlve broke off at the suction side of the compressor. The entire helium inventory was lost. The cold box tripped off, but the compressor did not. It ran for ~ 2 hours before I came in and shut the system down. The valve was repairedby Kevin T and Neil Wong. We ran hot (>100C) nitrogen through the fourth adsorber for one week. The solenoid and cold box were allowed to warm above 273C. The compressor, all piping, cold box, solenoid and buffer tank were pumped and purged with helium three times. Liquid helium was boiled off to pressurize the system to 10 psi and bottled gas was added to allow the compressor to start. We started the compressor and ran the gas through the purifier for three weeks. During the third week we added a second purifier. The purity was not measurable with the meter that we had. An RGA was set up to give some information on the rate of scrubbing. After three weeks the gas purity was better that 2 PPM. The system was cooled down. We added ~ 75 LL of heium via boil off to the system.
As the cooling progressed it was noted that the power supply for the 80K shield heater was burnt. An auto transformer was wired into the system and will be used until a replacement power supply can be purchased. |
248
|
Mon Apr 28 09:03:22 2008 |
Doug Preddy | Normal Running | power leads warmed during weekend |
The power lead temperatures suddenly rose on Sunday morning. No rippling occured before the woarm up.
I shut flow off this morning for about 10 minutes (until the LHe in went up to 30K) and then open the flow back up. The temperature seem to be recovering. |
247
|
Thu Apr 17 13:52:25 2008 |
Doug Preddy | Start Up | switched to series mode at 9:30 this morning |
switched to series mode at 9:30 this morning. Added two bottles of helium gas.
Started flow to power leads. |
246
|
Wed Apr 16 16:51:16 2008 |
Doug Preddy | Start Up | switched to parallel cold return |
|
245
|
Wed Apr 16 15:15:44 2008 |
Doug Preddy | Start Up | refrigerator started |
Turned on compressor last Tuesday. Ran purifier until today. Final value 0.15ppm.
Started cool down yesterday. Switched into parallel cold return this morning, but PIC 229 would not allow the compressor to charge. The compressor tripped due to bad solenoid vacuum (solenoid was warming up). The controller now seems to be working okay.
Restarted in parallel warm mode at ~12:00 |
244
|
Wed Apr 16 15:12:01 2008 |
Doug Preddy | Normal Running | graphs to load |
There are three strip tools saved:
coils
powerlead
startup |
243
|
Tue Apr 1 15:17:06 2008 |
Doug Preddy | Start Up | Starting up vacuum systems |
Monday afternoon there was no control of the vacuum system. The controls were working, but no output to devices. The "output" breaker in the PLC box was found to be tripped. Reseting it allowed control to the vacuum systems.
I started the regeneration of BCP2 this morning, but hte output breaker tripped again. reset it and continued to pump.
Started to pump out the solenoid also. Removed jumper on the BDP2 temperature read-back, bypassed BV2, and BCG2. This allows pumping through the diffussion pump.
Cold box has been pumping for a few weeks. It's at 2.0 x 10-3 |
242
|
Mon Dec 3 14:59:58 2007 |
Doug Preddy | Quench Recovery | Not really a quench recovery, But... |
Not really a quench recovery, but...I wanted to send this out via e-mail.
The contactor for the compressor building fan failed recently. Randy is
looking after it, but parts will have to be ordered. The big door should
stay open until the fan is running again.
Other than the fan, the rest of the system weathered the weather okay.
It's up and running until Wednesday morning. After maintenance day, we
should ramp down the solenoid power supply and leave the refrigerator
running. We can do some training and maintenance at this time. I would
also like to keep it cold until blocks can be removed so we can pump out
the cold box. |
241
|
Wed Nov 28 15:07:08 2007 |
Kevin Trithardt | Other | power lead regeneration |
Power leads cold again, power supply ramping up. |
240
|
Tue Nov 27 21:02:08 2007 |
Doug Preddy | Normal Running | power lead ripples |
power leads were oscillating tonight. John K. came down and cycled CV142.
(Thanks John!) Temps settling out. |
239
|
Mon Nov 26 09:45:43 2007 |
Doug Preddy | Normal Running | power lead problems |
Power lead temperatures were rippling yesterday afternoon. I asked one of
the operators to cycle CV142.
The temperatures were rippling again this morning, so I cycled CV142. |
238
|
Fri Nov 23 08:41:45 2007 |
Doug Preddy | Normal Running | screen grab of powerlead temps |
|
Attachment 1: Capture.jpg
|
|
237
|
Fri Nov 23 08:35:37 2007 |
Doug Preddy | Normal Running | power lead problems |
About 10 hours ago the power lead temperatures started to fluctuate and
climb.
I cycled CV142 and the Temps have dropped and stablized. |
236
|
Mon Nov 19 04:30:47 2007 |
Doug Preddy | Quench Recovery | switched to series mode |
|
235
|
Mon Nov 19 02:58:44 2007 |
Doug Preddy | Quench Recovery | Solenoid quenched on power lead over temperature |
I received a page at 1:30 this morning. The power lead temperatures were
climbing. Cycling CV142 did not fix the problem. The solenoid quenched at
1:50.
Restarted flow at 2:45 in parallel cold return. |
234
|
Fri Nov 9 18:56:20 2007 |
Doug Preddy | Maintenance | System Ready to Run |
M9BMP2 was replaced. Vacuum good. Solenoid is ramped up. :) |
233
|
Fri Nov 9 16:24:33 2007 |
Doug Preddy | Maintenance | 2APLC Died |
thumb wheel panel all lite up. 2APLC rebooted by Klara (Thanks). M9BMP2 not
pumping properly. Edi is looking at it. |
232
|
Fri Nov 9 14:50:03 2007 |
Doug Preddy | Quench Recovery | Solenoid cold |
Solenoid cold. Added two bottles of helium. Allowing to stablize. Will
ramp power supply in half an hour. |
231
|
Fri Nov 9 07:37:44 2007 |
Doug Preddy | Quench Recovery | switched to series mode |
switched to series mode. |
230
|
Thu Nov 8 09:28:53 2007 |
Doug Preddy | Quench Recovery | started compressor |
And started flow to coldbox,solenoid in parallel warm return.
Tuesday evening theree was a 2 hour power outage 19:00- 21:00. No call
made to M9 operator.
Wednesday tried to recover vacuum. Started cool down Thursday morning. |
229
|
Wed Oct 24 12:04:06 2007 |
Doug Preddy | Maintenance | power lead and cryopump regeneration |
Regenerating M9B:CP2 as temperature was up to almost 20k.
Shut off flow to power leads to allow them to warm up. The positive and
negative temps were beginning to creep up.
Regeneraing the adsorber. |
228
|
Tue Oct 9 13:16:44 2007 |
Doug Preddy | Quench Recovery | switched to series mode |
|
227
|
Tue Oct 9 12:58:22 2007 |
Doug Preddy | Quench Recovery | Solenoid Quench 2 |
Refrigeration sytem shut off at ~ 12:30 today. No apparent reason. Only
light on was a cold box fault.
Restarted in parallel cold return mode. |
226
|
Fri Oct 5 13:25:41 2007 |
Doug Preddy | Quench Recovery | funny graph |
There was a fluctuation of the positive lead temp with no flow going to
the power leads. |
Attachment 1: Capture.jpg
|
|
225
|
Fri Oct 5 10:25:43 2007 |
Doug Preddy | Quench Recovery | Unknown quench 2 |
Kevin and I were at the Sulzer panel when the system quenched 2. No
obvious reasons. Restarted the system. |
224
|
Tue Oct 2 13:02:37 2007 |
Doug Preddy | Normal Running | PLC problems |
While downloading new code for 2A PLC the M9 and M15 vacuum systems were
shut off. This is due to the two systems piggybacking onto the 2A PLC.
When M9 Epics came back up there was no controls. Eventually I reset the
local/remote switch (thumbwheel #100) to button #1 being on. Mike Leross
added a text and light on the epics vacuum page that says "EPICS works
only when green". If this light is not green, dial thumbwheel #100 and
push button #1. Make sure the light comes on and you should have EPICS
control back.
This caused a glitch in the refrigerator system. It did not trip it off,
but it would have if the solenoid was energised. The panel showed
compressor fault and the temps for TI121, and the powerleads all jumped.
This may be a cause for some of our unknown problems. |
223
|
Thu Sep 27 07:41:15 2007 |
Doug Preddy | Start Up | Solenoid cold |
Solenoid cold and in series mode. 50% liquid level. Starting flow to
powerleads. |
222
|
Wed Sep 26 08:52:46 2007 |
Doug Preddy | Start Up | switched to parallel cold return |
|
221
|
Tue Sep 25 07:34:04 2007 |
Doug Preddy | Start Up | PIC229 to 11 bar |
adjusted turbine speeds and HIC104 to maintain their values. |
220
|
Mon Sep 24 15:08:41 2007 |
Doug Preddy | Start Up | Started cool down this morning |
The vacuum in the cold box was good on Friday 0.0 X 10-4. Let it pump over
the weekend. Added two bottles of UHP helium to system Friday.
Started the turbines this morning. Cooling in paralell warm return.
Solenoid vacuum is 3.9 x 10-6 |
219
|
Wed Sep 19 20:53:18 2007 |
Doug Preddy | Maintenance | More diff pump news |
Cold box pumped out to ~ 190 mTorr overnight.Leak checked the pump again.
Still leaks at dip stick.Tried resetting the o-ring on the dip stick. It
still leaks baddd!!!
Machined the old seal off and installed a smaller o-ring onto dip stick.
Installed 60 ml of new pump oil into pump. Pumping down again.
After 4 hours the cold box is down to 160 mTorr. |
218
|
Tue Sep 18 18:48:11 2007 |
Curtis Ballard | Maintenance | cold box leak check |
The leak check of the cold box diff pump fittings. Found a leak at the
base of the diff pump on the tee that is apparently used to fill the pump
with oil. The fitting was removed and a plug was removed that resembled a
dip stick (approx 1" long). Tbe dip stick was charred black as if it had
been hot. The seal between the dip stick and the tee was not an O-ring.
It looked like a high temperature glue? For leak checking purposes, an O-
ring was fitted to the dip stick and reinserted in situ. Only the top
portion of the tee was removed. The lower cap was slathered in vacuum
grease. Pumping back down was slow. After two hours the vacuum was down
to 2 torr. At 6:30 pm, the vacuum was 200 mtorr, so I turned on the
filament and tried again to leak check. I was able to get the throttle
valve open a little wider than previously, but we still had a big leak. I
checked at the tee and got a strong response, but I also checked at the
diff pump connections and also got a response, albeit much less. We may
have to blank off the entire diff pump to isolate the cold box so that we
can leak check the system. Dimo said he will be able to help tomorrow.
For now, I will leave the roughing pump on the cold box and isolte the
leak detector. See you tomorrow.
P.S. I left a voice mail re: welding at TITAN 8:30 am/blankets/work
permits/extractor. cb |
217
|
Fri Sep 14 12:44:52 2007 |
Doug Preddy | Start Up | started compressor |
running purifier over weekend |
216
|
Wed Sep 12 12:01:02 2007 |
Doug Preddy | Maintenance | regenerated adsorber |
regenerated adsorber
replaced MV902 "ON" switch (used nitrogen precooling on switch) |
215
|
Tue Aug 14 12:55:12 2007 |
Doug Preddy | Normal Running | Strip tool saves |
There are two strip tools saved:
coils
powerlead |
214
|
Tue Aug 14 10:15:22 2007 |
Doug Preddy | Maintenance | Solenoid ramped down |
Solenoid ramped down and locked out for M9A slits work. |
213
|
Mon Aug 6 08:41:31 2007 |
Doug Preddy | Quench Recovery | Cold box trip at 6:00 |
compressor off due to cold box trip at 6:00 this morning. Restarted system
and started flow to solenoid in parallel cold return. |
212
|
Tue Jul 31 07:53:57 2007 |
Kevin Trithardt | Normal Running | cycled power leads |
got a page for the power lead temp
came down and cycled the power leads.. did not seem to make a difference..
Kevin |
211
|
Sun Jul 29 04:58:27 2007 |
Doug Preddy | Quench Recovery | Energizing solenoid |
LHe level~50%. Still have a slight ripple in the power leads, but they are
cold enough to power the solenoid. LHe_in varies between 10.7K - 11.3K. |
210
|
Sat Jul 28 22:30:13 2007 |
Doug Preddy | Quench Recovery | quench again |
recovered system and energized solenoid at about 6:00 this evening.
At 9:30 power lead temps quenched solenoid again. MV52 stuck open during
start-up. |
209
|
Sat Jul 28 15:45:17 2007 |
Doug Preddy | Quench Recovery | quench recovery |
The solenoid tripped off this morning due to pwer lead over temp. The
compressor was also off. I restarted this morning at about 8:15 in
parallel cold return. Switching to series mode at 3:40. |
208
|
Thu Jul 5 11:01:47 2007 |
Kevin Trithardt | Other | Current lead warm up |
Due to curent lead temperature occilation Doug recommended warming up the
current leads.
The leads were warmed up this morning then cooled back down. Power supply
is ramping up now.. 2 1/2 hours start to finish. |
207
|
Thu Jul 5 03:04:50 2007 |
Doug Preddy | Normal Running | Power lead problems |
The power leads temps are starting to cycle again. Earlier today M9
experimentor cycled HIC142 to stablize the oscillations. They started
again early this morning, so cycled HIC142 again. Oscillations died back,
but are still present. Will try and warm the power leads later today when
the experiment's sample is changed. |
206
|
Wed Jul 4 11:13:12 2007 |
Doug Preddy | Quench Recovery | test |
This is a test to make sure the e-mail works. |
205
|
Sun Jul 1 16:09:37 2007 |
Doug Preddy | Normal Running | M9B:DP2 tripped off |
Diffusion pump tripped off and vacuum (and power lead temps) going up. I
had an experimentor cycle HIC 142 at 4:15 this morning. When I got in
today I restarted the pump and it is back to 6.0 x 10-7. Power lead temps
also are going down. |
204
|
Tue Jun 19 21:15:41 2007 |
Doug Preddy | Quench Recovery | Today's quench |
power lead temps caused a quench at 8:30 this morning. Recovery of system
and flow to solenoid was started by 11:00. Solenoid was switched to series
cold at 3:00. Solenoid and power leads were cold at ~6:30. power supply
was to be energized by experimenters. |
203
|
Sat Jun 16 15:05:03 2007 |
Doug Preddy | Normal Running | Solenoid power lead temp problem |
Power lead temps rippling and increasing. I asked an operator to cycle
HIC142. This seems to have fixed the problem (for now). |
202
|
Thu Jun 14 00:10:10 2007 |
Doug Preddy | Quench Recovery | recovering from earlier quench |
Solenoid quenched on power lead temperature last night at about 6:00. I
restarted flow to the solenoid in parallel cold return. Switched to series
mode and am building liquid. |
201
|
Tue Jun 12 12:48:25 2007 |
Doug Preddy | Maintenance | added one bottle UHP helium to system |
|
200
|
Thu May 31 11:51:49 2007 |
Doug Preddy | Quench Recovery | Switched to series mode |
|
199
|
Thu May 31 07:11:05 2007 |
Doug Preddy | Quench Recovery | switched to parallel cold return |
switched to parallel cold return earlier this morning. Vacuum is 5 x 10-5. |
198
|
Wed May 30 11:27:32 2007 |
Doug Preddy | Quench Recovery | Problems recovering |
Various start up problems :
MV51 stuck open. Finally got it closed by hitting the valve with a hammer.
Vacuum is bad in cold box as MV902 tripped closed.
Vacuum in solenoid has gone bad. Suspect boil off from inside solenoid. So
far it is not recovering.
Previously T1 would not spin up - frozen. |
197
|
Wed May 30 08:38:38 2007 |
Doug Preddy | Quench Recovery | Solenoid quenched this morning |
Solenoid quenched this morning on power lead temp (I believe).
I restarted it at ~7:00, but the capacity control for the compressor would
not respond. I shut the system back down and checked as many relays as I
could. I then restarted the system and it is now cooling. I will go
through the wiring diagrams and see if I can locate the bad relay. |
196
|
Wed May 16 10:02:35 2007 |
Doug Preddy | Maintenance | warming up power leads |
Power lead temps have been slowly increasing over the last wekk. I ramped
the solenoid down and am warming the power leads to >80k. |
195
|
Wed May 2 16:28:16 2007 |
Doug Preddy | Normal Running | Energizing solenoid to 500 amps |
Power supply initially would not ramp up. I exercised the rate control
selector switch and found that the power supply would ramp up at only the
30 minute setting. It is ramping up at a rate of about 60 minutes. |
194
|
Mon Apr 30 09:30:26 2007 |
Doug Preddy | Normal Running | problems over weekend |
The PLC Limit switch power supply was tripped off on Saturday. I came in
and reset it and restarted all the vacuum systems that had tripped off.
The power leads were found to be warming up. This morning they were at ~
45K. I stopped flow to the power leads and will allow them to warm up
above 80K and then will recool them. |
193
|
Fri Apr 27 10:32:07 2007 |
Doug Preddy | Quench Recovery | Reset quench relay logic box |
The quench relay logic controller was not functioning correctly. It showed
a "Trip" light and no other lights. I cycled the power to the controller
and it now seems to be working properly. This did cause a quench and I am
now recovering the system. |
192
|
Fri Apr 27 10:16:44 2007 |
Kevin Trithardt | Quench Recovery | Test |
Don't Panic -- There was no quench. I am testing the e-log.
I have added Kevin's name and e-mail to the M9 e-log. He will be e-mailed
when a quench recovery log is submitted. His name is also included in the
Author's list.
Thanks, Doug |
191
|
Fri Apr 27 10:10:07 2007 |
Doug Preddy | Normal Running | Solenoid Cold |
Solenoid cold, power leads cold. Alarm handler started. |
190
|
Tue Apr 24 10:21:49 2007 |
Doug Preddy | Start Up | Started flow to turbines |
Started flow to turbines at about 10:00 in parallel warm mode. |
189
|
Mon Apr 23 16:31:02 2007 |
Doug Preddy | Start Up | Started compressor |
Startewd compressor and purifer today. |
188
|
Fri Apr 20 12:15:12 2007 |
Doug Preddy | Start Up | remote PLC switch |
I could not control the vacuum devices using EPICS. The buttons could be
pushed, but nothing would respond. The PLC was in local mode. Thumbwheel
to 100, push On/Open button to put it into remote mode. |
187
|
Thu Apr 19 15:18:25 2007 |
Doug Preddy | Start Up | preparing to start the refrigerator |
Starting the vacuum systems in the coldbox and solenoid. |
186
|
Mon Mar 5 14:59:41 2007 |
Doug Preddy | Maintenance | Password |
On the weekend someone used this log to send spam messages. I have
installed a password for the write privilege. Please contact me at 6399
for the password.
Doug |
185
|
Fri Jan 26 15:10:37 2007 |
Doug Preddy | Maintenance | new control computer installed |
I have installed a new control computer at the M9 solenoid control panel |
184
|
Tue Nov 28 10:32:04 2006 |
Doug Preddy | Quench Recovery | recovering after looong power outage |
The power has been out for about 24 hours. Recovering coldbox, solenoid and
beamline vacuum.PLC is down for the vacuum system. Started compressor and
am flowing warm helium through the soleniod to warm it up while the vacuum
recovers. |
183
|
Wed Nov 15 17:05:49 2006 |
Willy Andersson | Quench Recovery | powerleads cold, energizing solenoid |
Powerlead temperatures have bottomed out, energizing solenoid to 300
amps, ramp rate 60. |
182
|
Wed Nov 15 13:56:00 2006 |
Doug Preddy | Quench Recovery | switch to series mode |
|
181
|
Wed Nov 15 11:09:28 2006 |
Doug Preddy | Quench Recovery | Compressor tripped off |
Compressor tripped this morning at ~8:45. I restarted the compressor, but
turbine 1 would not spin up. I let it warm for an hour and it started. I
started flow to the solenoind in parallel cold return. |
180
|
Tue Nov 7 10:35:32 2006 |
Doug Preddy | Normal Running | Maintenance day |
I ramped down the solenoid power suplly and shut off flow to the power
leads. I will allow them to warm up and (hopefully) recover the flow rates.
I am also regenerating the M9BCP@ cryopump. |
179
|
Fri Nov 3 12:09:51 2006 |
Doug Preddy | Normal Running | Fine tuning |
The power lead temperatures have been climbing at a rate of ~ 0.02K very 8
hours. The negative lead started to show some rippling this morning. The
positive flow had dropped from >250mm to 240mm. I cycled CV142 and the
temps dropped slightly. The negative ripple is gone and the positive flow
is back to >250mm. |
178
|
Tue Oct 31 08:37:34 2006 |
Doug Preddy | Quench Recovery | Energizing solenoid |
|
177
|
Tue Oct 31 05:36:14 2006 |
Doug Preddy | Quench Recovery | switch to series mode |
|
176
|
Tue Oct 31 03:52:29 2006 |
Doug Preddy | Quench Recovery | power lead quench at 2:30 this morning |
Compressor still on. Starting flow to solenoid |
175
|
Thu Oct 26 14:14:57 2006 |
Doug Preddy | Quench Recovery | power lead quench |
solenoid tripped on power lead temp. I was here and caught it. System
cooling. |
174
|
Thu Oct 26 11:45:22 2006 |
Doug Preddy | Quench Recovery | Solenoid cold |
power leads cold 50% liquid.
Turning on power supply |
173
|
Thu Oct 26 08:18:10 2006 |
Doug Preddy | Quench Recovery | switched to series mode |
Switched to series mode at about 7:45. |
172
|
Thu Oct 26 04:34:15 2006 |
Willy Andersson | Quench Recovery | Still in // cold return mode. |
Leaving system cooling in // cold return mode, cooldown rates still good.
Had flow on to powerleads since re-starting cooling flow to solenoid.
Either I (when I return to work later this morning) or Doug will do the
switch to series mode. |
171
|
Thu Oct 26 04:27:31 2006 |
Willy Andersson | Quench Recovery | Powerlead overtemp |
02:30 this morning got page from operations.
Looked at system online, appears that there was a powerlead overtemp
that caused the quench. Compressor still running. After arriving to
work set system to // warm return mode to cool down transferlines. Lhe
level starts to boil away. Switch to // cold return mode. Discovered that
seem to get better cooldown rate by not opening supply valves to solenoid
fully. // cold return valves are fully open but both CV143 and CV146 are
only open to 0.55 giving mu1 and mu2 inlet pressures of 2 barA. Getting
good cool down rates and even building LHe level.
04:25 C1 down to 8K, C12 at 7.5K, C6 at 7.5K, 6KS_M at 10.5K |
170
|
Sun Oct 15 07:09:41 2006 |
Other | Normal Running | cryopump bcp2 trip |
Donald Arseneau reporting
Not really solenoid realated, but FYI...
The cryopump bcp2 stopped working and the vacuum valves tripped.
When I came in, the CP was over 200K and the pressure (bcg4) read
over 200 torr, with the CP nominally on. I switched it off and
continued warming; pumped it out; and am now re-cooling. It seems
to be normal so far.
-D |
169
|
Fri Oct 13 00:13:57 2006 |
Experimentor | Quench Recovery | Energized solenoid. |
Hi there,
This is Khashayar (experimenter). Lookin at all different temperatures and
levelson the monitor, it seems everything is stable now. I wonder if you
could let us know what time we can have beam again? Would you please send an
email to kghandi@mta.ca if you know the answer? You can also reach me at my
cell# (506)961-0802 any time.
Thanks
Khashayar
> Switched to series mode about 6 hours ago. Cooling continued including
> power leads until LHe level at about 50% and powerleads appeared stable. |
168
|
Thu Oct 12 19:54:10 2006 |
Willy Andersson | Quench Recovery | Energized solenoid. |
Switched to series mode about 6 hours ago. Cooling continued including
power leads until LHe level at about 50% and powerleads appeared stable. |
167
|
Thu Oct 12 11:53:04 2006 |
Willy Andersson | Quench Recovery | Compressor trip, 09:50 this morning. |
Main compressor tripped, refrigerator shutdown. Checked with experimentors
and main control room, no indications of power bump etc.
Restarted compressor, // warm then // cold return. One of the MV5x valves
frozen open, had to de-power valve a couple of times to get it to seal. |
166
|
Thu Oct 5 14:53:54 2006 |
Doug Preddy | Start Up | Switched to series mode |
|
165
|
Thu Oct 5 11:51:53 2006 |
Doug Preddy | Start Up | Adde 2 bottles UHP Helium |
Valved off purifiers, but left LN2 on. |
164
|
Thu Oct 5 10:26:26 2006 |
Doug Preddy | Start Up | switched to parallel cold return |
|
163
|
Wed Oct 4 18:10:18 2006 |
Willy Andersson | Start Up | Quick check on system |
System in good // warm return mode, temps coming down nicely. BCP2 cryopump
does not look too healthy, temperature is just over 20K, very close to low
set point.
TIC121 down to 120K, Mu1 return temp at 164K, Mu2 return at 273K, T1 inlet
temp at 208K. Cooling looks good for overnight. |
162
|
Wed Oct 4 07:29:04 2006 |
Doug Preddy | Start Up | Starting cool down |
Started compressor yesterday with flow through the purifier overnight.
Starting tubines this morning in parallel warm return |
161
|
Thu Aug 17 19:45:27 2006 |
Willy Andersson | Quench Recovery | switch to series cooling |
Temps of flow returning from solenoid flat lined at about 10K.
Gradually closed CV155.
Then switched to series cooling. |
160
|
Thu Aug 17 08:04:44 2006 |
Doug Preddy | Quench Recovery | Solenoid tripped at about 3:00 this morning |
restarting system.
Compressor would not start. Idid not see anything that would not let it
start. Pushed rest button upstairs, and reset contactor. Compressor started.
preparing to start flow to solenoid in // cold return. |
159
|
Tue Aug 15 15:39:27 2006 |
Willy Andersson | Quench Recovery | switched to parallel cold return |
Return flow temps from solenoid about 40K, TIC121 at about 40K so switching
to //cold return.
Starting with slightly reduced flow through cold returns, CV145 and CV147
at about 65% open. |
158
|
Tue Aug 15 08:45:56 2006 |
Doug Preddy | Quench Recovery | restarted the compressor |
Solenoid tripped off Sunday. Restarted compressor and cool down of cold box. |
157
|
Thu Aug 10 20:26:09 2006 |
Willy Andersson | Quench Recovery | solenoid energized |
Powerleads seem stable. |
156
|
Thu Aug 10 16:33:11 2006 |
Willy Andersson | Quench Recovery | Flow to solenoid tripped on powerlead temperature. |
Power lead temps were drifting up, tried to tweak TIC121 and HIC141 to
unstall powerlead flow. Got quench. Restarted series flow, building LHe
level. |
155
|
Thu Aug 10 08:33:44 2006 |
Doug Preddy | Normal Running | Running low on helium |
Temperture okay, but there are fluctuation in the power leads. PIC229 is
trying to charge. The buffer tank pressure is just >0 psi. I will lower the
liquid level to 40% to allow some helium to boil off into the buffer tank. |
154
|
Wed Aug 9 07:50:49 2006 |
Doug Preddy | Quench Recovery | Switched to series mode. |
Cool down continues. |
153
|
Wed Aug 9 06:59:43 2006 |
Willy Andersson | Quench Recovery | more // cold return stuff |
About 21:00 last night the solenoid temps had not changed much, pretty well
flat lined. I guess my reducing CV155 stalled the cooling. Called Don
Arseneau and asked him to increase CV155 to about 80% open. Temps slowly
began to fall. Asked Don to look at graph of temps later in the night and
if they fall down to a flat line to then reduce CV155 a bit to get the
temps trending further down.
This morning CR_C1_ENT has fallen to a slightly upward trending flat line
of about 12.7 K. Probably ready for switching to series mode by whoever
gets to the system first this morning. |
152
|
Wed Aug 9 06:44:58 2006 |
Willy Andersson | Quench Recovery | // cold mode cooling continues. |
After restarting flow to the solenoid yesterday in // cold return mode
TIC121 just refused to go lower than about 29K even when we closed CV155
all the way. Tried various things, switching to // warm return, changing
opening of CV155, setting TIC121 to auto, even tapping TIC121. Finally
tried reducing flow to solenoid by reducing // warm return valves to about
70% open to see if possible to cool just refrigerator a bit.
TIC121 temp fell a bit and then inlet temperatures to solenoid began to
fall and solenoid slowly began to cool even though the mass flow to the
solenoid was reduced. Guess is that with solenoid homogeneusly at about 30K
there was not much resistance to flow so turbine massflow was starved just
enough to stall further cooling.
After temps were on a good downward trend Doug switched to //cold return.
At about 16:00 yesterday I reduced CV155 to about 70% and waited a bit to
confirm that temps were falling and then left the system to cool until
later that evening. |
151
|
Tue Aug 8 07:27:49 2006 |
Doug Preddy | Quench Recovery | Solenoid Quench at about 6:00 this morning |
No indication of problem. Turbines still running, but no flow to solenoid.
Started flow. Solenoid ~20K. |
150
|
Sat Jul 29 09:38:06 2006 |
Doug Preddy | Quench Recovery | power leads cooled |
opened power lead flow about 40 minutes ago. ~12K will let them stablize.
LHE level >20% |
149
|
Sat Jul 29 05:30:28 2006 |
Doug Preddy | Quench Recovery | switched to series mode |
Temps bottomed out at ~16K. Switching to series mode. |
148
|
Fri Jul 28 20:39:40 2006 |
Doug Preddy | Quench Recovery | Restarting refrigerator |
Solenoid quenched at about 6:00 tonight.
I restarted the compressor, then the cold box and turbines. When cold box
was at 25K I started flow to the solenoid in parallel cold return. |
147
|
Sat Jul 22 06:34:14 2006 |
Experimentor | Quench Recovery | looking good |
Donald Arseneau reporting.
It is looking pretty good, so I came back in with the intent of energizing
the magnet. Doug should be up now or soon, so I'll wait a little for you
to see this. If you do, call the m9 counting room 222-7379. After waiting
a while, I will just forge ahead. |
146
|
Fri Jul 21 23:36:21 2006 |
Doug Preddy | Quench Recovery | Final cooldown problems |
80K shield is down to <60K Liquid level not building. Power leads rippling
and warming. T1 inlet 85K with 10%heater load.
Lowered the set point of TI121 to 17K. Shut off flow to the 80K shield to
try and warm them. Turbine 1 inlet temp dropping (83K)
Power leads cooled and stablized, coil temps came down. Leaving it for 1/2
hour to evaluate. |
145
|
Fri Jul 21 17:18:19 2006 |
Willy Andersson | Quench Recovery | Opened HIC142 fully open |
Power leads have flatlined but still building LHe level. |
144
|
Fri Jul 21 14:08:04 2006 |
Doug Preddy | Quench Recovery | switch to series mode |
Coils temps <10K.Switching to series mode. |
143
|
Fri Jul 21 07:39:37 2006 |
Doug Preddy | Quench Recovery | Cool down continues |
Raised PIC229 to 11Bar. Started to close HIC155. Cooling rates improve. |
142
|
Thu Jul 20 13:34:26 2006 |
Willy Andersson | Quench Recovery | cold return mode continues... |
Even though cr_c1 and cr_c12 have begun to tick down, cr_c7 and cr_c6 are
actually ticking up. This is probably a wave of warming propagating through
the solenoid. As long as the two inlets are falling in temperature then
things are going in the right direction. Once the warm wave travels through
the outlets will begin to cool as well. |
141
|
Thu Jul 20 13:27:21 2006 |
Willy Andersson | Quench Recovery | cold return mode continues... |
cr_c1 and cr_12 are both at about 45K and heading slowly down, so the
gamble of going to // cold return worked. Maximum opening of CV155 is
limited by CV204 goes fully closed and suction pressure begins to rise
above set point. Adjust cv155 to keep cv204 just at the closed point. Keep
tweaking cv155 and turbine speeds as things get cooler. |
140
|
Thu Jul 20 13:21:57 2006 |
Willy Andersson | Quench Recovery | started // warm return flow. |
TIC121 was down to 27K
warm return valves were wide open
opened supply valves CV143 and CV146.
TIC121 went up to about 37K
Mu1 return temperature went down to about same temp as TIC121 so set Mu1 to
cold return. Open CV145 then close CV151. Mu2 return was still > TIC121 so
kept it in warm return mode. Adjust turbines as required.
After about 20 minutes Mu2 return temp dropped down to about equal to Mu1
return temp of about 38K. Then set Mu2 to cold return. Open CV147 then
close CV143. TIC 121 drops to 30 K. Even though Mu1 and Mu2 return temps
greater than TIC121 I will keep it in //cold return mode to see if the core
solenoid temperatures will start to fall. To maximize the use of the
cooling from T2 outlet temperature CV155 is tweaked open to its maximum
stable opening. This helps cool the lower heat exchangers. If this works
then cr_c1 and cr_c12 should start to tick downwards. If they keep rising
then have to switch back to //warm return. |
139
|
Thu Jul 20 11:01:09 2006 |
Willy Andersson | Quench Recovery | Opened up warm return valves CV151 and CV153 |
Mu2 pressure was just about at trip point due to trapped volume of helium
warming. So opened up warm returns to bleed off pressure and prevent it
from rising. |
138
|
Thu Jul 20 08:18:31 2006 |
Doug Preddy | Quench Recovery | T1 started |
Started flow to turbines. Both started. T1 seems a bit slow. HIC110 at 0.85
SI110 = 4100.
Cool down started. |
137
|
Thu Jul 20 02:59:06 2006 |
Doug Preddy | Quench Recovery | T1 still not starting |
I will leave the cold box to warm overnight and try it again in the morning. |
136
|
Thu Jul 20 00:52:13 2006 |
Doug Preddy | Quench Recovery | T1 frozen |
T1 will not spin up. Warming up cold box. |
135
|
Thu Jul 20 00:25:16 2006 |
Doug Preddy | Quench Recovery | Solenoid quenched @ 11:15 |
Solenoid Quenched on C1 temp. It went above 5K. Shut off compressor.
Restarting system @ 12:15 |
134
|
Thu Jul 6 15:04:17 2006 |
Doug Preddy | Normal Running | test |
test |
Attachment 1: M9daily log070306.XLS
|
133
|
Thu Jul 6 15:00:15 2006 |
Doug Preddy | Normal Running | test |
|
132
|
Mon Jul 3 23:01:34 2006 |
Doug Preddy | Quench Recovery | power lead warming/ripples caused quench |
power lead warming/ripples caused quench at 18:45 today. Compressor stayed
on, but flow to solenoid stopped.
I started flow to solenoid at 22:40. |
131
|
Fri Jun 30 11:17:57 2006 |
Doug Preddy | Normal Running | Solenoid recovered |
Tuesday night. June 27, 2006, the solenoid quenched for no apparent
reason. It was restarted Wednesday morning. The vacuum in the solenoid
went away (up to 8 Torr). This was found to be a result of a leaking
isolation valve between the solenoid and T2. T2 was vented, which caused
the solenoid to slowly vet. When T2 was pumped out again, the solenoid
vacuum recovered. This caused a delay in recovering the solenoid. As of
Friday morning 7:15 the solenoid power supply was ramped up. |
130
|
Fri Jun 30 11:13:00 2006 |
Doug Preddy | Normal Running | E-log is back up and running |
I would have made an entry when it died, but----- |
129
|
Fri Jun 16 08:12:04 2006 |
Doug Preddy | Normal Running | LI108 indicates high on EPICS screen |
LI108 indicates high on EPICS screen (150%) Controller shows ~64% |
128
|
Wed Jun 14 16:27:01 2006 |
Willy Andersson | Quench Recovery | Energized solenoid |
Powerleads appear stable. |
127
|
Wed Jun 14 10:35:30 2006 |
Willy Andersson | Quench Recovery | Switched to series cooling. |
Had system in //return cooling overnight with small flow to keep power
leads cool. Switched to series mode about 30 minutes ago. Building LHe
level. |
126
|
Tue Jun 13 16:04:33 2006 |
Willy Andersson | Quench Recovery | TIC 121 set to auto mode |
|
125
|
Tue Jun 13 15:52:46 2006 |
Willy Andersson | Quench Recovery | Doug has reduced and now closed CV155. |
Now in full // cold return mode.
Had just talked with Curtis, He said thta he has already informed the
experimentors that the solenoid will not be ready until tommorow, so he
suggests leaving the system in reduced // cold mode overnight. |
124
|
Tue Jun 13 10:54:27 2006 |
Doug Preddy | Quench Recovery | Compressor tripped off |
No indicator lights etc as to why the compressor tripped. The only light
was a cold box fault. I had to shut off the main breaker before the
compressor would come back on.
Started cooling in parallel cold return. |
123
|
Tue May 30 14:36:41 2006 |
Doug Preddy | Normal Running | power leads warming |
power leads warming. closed HIC 142, then re-opened. temps falling |
122
|
Fri May 26 14:34:24 2006 |
Doug Preddy | Start Up | Ready to run |
Solenoid is cold, liquid level is 35%, power leads cold and seem stable.
Added one bottle helium to buffer tank. Pressure is 7 psi.. |
121
|
Fri May 26 10:03:03 2006 |
Doug Preddy | Start Up | Started flow to power leads |
Started flow to power leads.
Liquid level 15% |
120
|
Fri May 26 08:45:38 2006 |
Doug Preddy | Start Up | Changed to series mode |
Changed to series mode.
Liquid level building. |
119
|
Fri May 26 07:29:54 2006 |
Doug Preddy | Start Up | CV155 closed |
CV155 closed.
Temps about 15K |
118
|
Thu May 25 07:34:18 2006 |
Doug Preddy | Start Up | switched to parallel cold return |
switched to parallel cold return |
117
|
Tue May 23 08:44:28 2006 |
Doug Preddy | Start Up | Started turbines |
Solenoid and cold box were pumped out last Tuesday. Cold box roughing pump
initially would not start. had to retighten all wires on the contactor in
the Sulzer control panel (RP900).
Started compressor on Friday. ran purifier over the weekend.
Started flow in parallel warm return. Started flow to turbines.
Replacing dead monitor on other control computer. |
116
|
Thu Dec 22 15:10:44 2005 |
Doug Preddy | Shut Down | shut down system |
shuttting down the system. isolated cold box by closing v135. preparing to
pump out cold box. |
115
|
Mon Dec 12 09:24:29 2005 |
Doug Preddy | Quench Recovery | Solenoid Quench on power lead temp |
The solenoid tripped on power lead temps at about 9:15. I am recovering it
from it's all around mode into parallel cold return. |
114
|
Tue Nov 15 07:25:10 2005 |
Doug Preddy | Normal Running | power supply problem |
Saturday November 12 the solenoid power supply ramped itself down to zero.
It would not ramp up unless the ramp rate was set to 30 minutes. At this
setting the power supply ramped up to the required current. It seems to
ramp slower than the 30 minute rate. Klaus also looked at the problem. His
suggestion is to exercise/clean the switches and pots. |
113
|
Thu Nov 3 09:27:16 2005 |
Doug Preddy | Quench Recovery | started flow to solenoid |
started flow to solenoid in parallel cold return. |
112
|
Thu Nov 3 06:19:50 2005 |
Doug Preddy | Quench Recovery | restart system |
Last night at about 7:00 there was a large power bump that shut the
compressor and water pump off. I came in this morning and am restarting the
system. |
111
|
Wed Nov 2 10:17:27 2005 |
Willy Andersson | Start Up | M9B helium refrigerator and solenoid cooldown |
Started M9B MYCOM helium compressor circulating helium through system last
Friday. Right hand purifier was regenerated previously, LN2 fill system
started and flow started from buffer through purifier to low pressure
return line to compressor. Left in this mode over the weekend. Curtis came
in on weekend to add new full LN2 dewar to purifier.
Started // warm return cooling Monday.
Tuesday morning solenoid temps about 35 K and TI121 about 35 K so
switching to // cold cooling.
Note:
PDI 104 guage is very slugish to respond, needs to be replaced or cleaned.
TI148 and TI149 need to be recharged with helium, they do not work yet.
TIC121 may be reading too high a temperature, try to verify it with TE147
before JT effect begins. Now TI121=20.7 K TE147=25 K HIC155 is full
open still.
LIC108 is reading too high, reads 22% LHE but really is no LHE at this
point. |
110
|
Mon Oct 31 07:48:57 2005 |
Willy Andersson | Quench Recovery | what a fine entry |
Keep IT safe boys |
109
|
Sun Aug 14 10:03:13 2005 |
Willy Andersson | Normal Running | System stable |
No experiment running in M9B.
Solenoid current is zero and power supply not armed.
System in stable series cooling mode. |
108
|
Tue Jul 19 18:09:56 2005 |
Willy Andersson | Quench Recovery | Quench II |
Machine trip just as I was exiting the TRIUMF gate. QRL said cold box fault
as did red lite on compressor. At cold box panel all turbine red lites were
on and compressed air failure lite was on. But there was no problems with
compressed air. On fist trip logger LED # 8 and 16 were lit. Restarted
compressor then start flow to cold box, start turbines, start // warm
return until temps returning back from solenoid were <= TIC121 then
switched to //cold return mode. Opened cv155 to 0.88
Solenoid temps at 24K and starting to trend down. |
107
|
Tue Jul 19 16:13:32 2005 |
Willy Andersson | Quench Recovery | switch to series mode |
CR_6KS_M down to 11 K.
Switched to series mode.
Started small flow to power leads to get them cold.
HIC142=0.6 Later open HIC142 wide open.
Raised discharge press to 11.4 barA.
Letting LHe level build. |
106
|
Mon Jul 18 15:51:17 2005 |
Doug Preddy | Quench Recovery | Compressor restarted, flow to solenoid |
Recovered the vacuum in the solenoid, then started the compressor.
Started flow to solenoid in parallel warm return. |
105
|
Mon Jul 18 11:18:40 2005 |
Doug Preddy | Quench Recovery | Solenoid Quenched over the weekend |
The solenoid was found to be warm on Monday morning. M9Q3 had a bad water
leak over the weekend. The water header serving Q3 was turned off and the
leak confirmed. Q3 was isolated and the header was turned back on. My
supposition is that while the main header was turned off, the diff. pump
under the solenoid tripped. When I looked at it this morning the
compressor was off and the vesssel vacuum was very bad. The PLC connection
to EPICs is down, so I can not restart the vacuum system yet. Mike Leross
is looking at the problem.
There was no trip signal to the main control room. It looks as though the
control room signal was bypassed downstairs.
The power supply fault light was on on the QRL panel, but I okayed Bob
Hilton locking out the power supply in order that Q3's water leak can be
repired. Shutting of the main breaker may have turned on this light. The
other possibility is that the power supply was not ramped down and shut
off properly. |
104
|
Tue Jun 14 23:01:22 2005 |
Doug Preddy | Quench Recovery | switched to parallel cold return |
|
103
|
Tue Jun 14 20:53:19 2005 |
Doug Preddy | Quench Recovery | restarted refrigerator after power bump |
see bitmap for temps/pressures after presurrizing coldbox. Preparing to
start flow to turbines, then will start flow to solenoid in parallel warm
return. |
Attachment 1: june142045.BMP
|
102
|
Tue Jun 14 18:48:14 2005 |
Experimentor | Normal Running | Power bump at 18:40 |
Solenoid tripped on a power bump at 18:40 Tuesday
-- Donald Arseneau |
101
|
Thu Jun 9 21:41:25 2005 |
Willy Andersson | Quench Recovery | Trying to achieve stable cooling. |
From about 08:00 to 15:00
See Doug's previous entry for quench recovery details.
First the system had been set to // cold return mode because the solenoid
temps seemed low enough. Temps started to rise instead of cooling so system
was eventually set back to // warm return mode. With the system in // warm
return mode the solenoid was still warming instead of cooling. Solenoid
temps were rising to almost 50K and T1 shield heater was about 90%. T1
inlet temp was below 75K and falling even with shield heat set so high.
CV155 kept closed and // warm return flows were full flow. T1 brake valve
seemed way too open at about 0.8 (compared to previous runs).
15:00 to 19:00
Tried opening CV155, didn't seem to help much. Temps still trending
upwards. Decided to reduce flow to solenoid to see if the cold box would
cool down. Started reducing the // warm return outlet valves. TI121 began
to drop slowly. On graph plotting solenoid temps they started to trend
downwards. Weird. A reduced flow seemed to produce more cooling ? Don't
understand this but will continue. Flow temps returning from solenoid were
about the same temp as TI121, about 35 K. Switching to // cold return mode
to try to reduce TI121. Keeping CV155 as open as possible, just keeping
CV204 from closing completely. After switching to // cold return TI121
starts to slowly fall, T1 inlet temp rises over time so start to drop
shield heater setting. Solenoid temps now trending downwards. Cracked open
CV142 to get some flow going through powerleads. Raised compressor
discharge press to about 11.2 barA. Shield heater down over time to about
10%. Reduced CV155 down to the point where temps almost stop falling then
open cv155 just enogh to keep temps falling.
19:30 Solenoid temps down to about 28K. Letting system continue cooling
overnight.
Guessing the cause of the turbine overspeed quench was caused by
contamination entering the spinning turbine, causing rapid speed changes or
possibly the continued saga of the water damaged Jaquet turbine speed
tachometer giving random false trips. |
100
|
Thu Jun 9 08:56:10 2005 |
Doug Preddy | Quench Recovery | system back on |
The compressor was restarted and the solenoid is cooling (sort of) in
parallel cold return. |
99
|
Thu Jun 9 06:53:40 2005 |
Experimentor | Other | Trip at 6:45 Today. |
Solenoid quenched at 6:45. All temperature monitors were flat until trip.
Hearing compressor stop was first warning. Lights are:
Turbine T1 overspeed, Compresor alarm, cryostat quench.
--Donald Arseneau |
98
|
Thu Jun 2 09:16:40 2005 |
Doug Preddy | Quench Recovery | continuing to cool |
See screen grab |
Attachment 1: 02-06-05-7.32.49 AM.jpg
|
|
97
|
Thu Jun 2 01:38:25 2005 |
Doug Preddy | Quench Recovery | strip tool plot |
This is a strip tool plot of the cooldown |
Attachment 1: 02-06-05-12.57.26 AM.jpg
|
|
96
|
Thu Jun 2 01:26:30 2005 |
Doug Preddy | Quench Recovery | started flow to solenoid |
See attached file for a screen grab of temps. |
Attachment 1: Capture6-2-05-1.13.33 AM.jpg
|
|
95
|
Wed Jun 1 23:48:02 2005 |
Doug Preddy | Quench Recovery | the first quench |
I recieved a call from ops at 22:00 tonight that the solenoid had alarmed.
I came in and found a cold box fault, with the compressor tripped off. I
was unable to restart the compressor. I cleared the cryostat quench and
compressor trips. The system looked as though it was ready to start. I
pushed the compressor "ON" button, but as soon as the main contactor
closed, the compressor tripped again. After a few trys and a bit of
searching, I tried resetting the compressor over-pressure switch. That
allowed me to restart the compressor. Once the high pressure comes up I'll
start flow to the turbines. |
94
|
Wed Jun 1 08:23:19 2005 |
Doug Preddy | Start Up | start up notes |
The solenoid was pumped out Monday and yesterday after the quads just
downstream of the solenoid were put back in place. The quad just
downstream of the solenoid was remove to replace two coils on it.
The cold box vacuum had tripped off some time in the last little while.
Started it pumping on Monday also. The compressor was started Tuesday
afternoon and flow was started to the solenoid. The purifier was
regenerated and put on line in it's total buffer tank flow mode. The cold
box was pressurized and the turbines were briefly spun up to check the
operation of the new turbine speed indicator. It seems to be working
properly.
Flow to the turbines was started this morning and all went well. The speed
indicator works properly.
M9BIG1 started ot 6.6 x 10-6 before flow was started. One hour later it
reads 4.8 x 10-6 |
93
|
Thu May 19 15:05:31 2005 |
Doug Preddy | Maintenance | STA 120 replaced |
The turbine 2 speed indicator control box STA 120 has been replaced with a
newer style Jaquet controller. This is similar to the ones used in the
ISAC helium liquifier. See attached photos for set up parameters. These
were taken from the old controller, Sulzer documentation, and the ISAC 2
controllers. |
Attachment 1: M9 Turbine 2.doc
|
92
|
Mon Apr 18 09:52:11 2005 |
Doug Preddy | Maintenance | Relays replaced |
The following relays have been replaced in the Sulzer control panel:
K341, K379, K132, K324A, K314, K125, K127, K133, K252, K227, K233, K238,
K239, K245, K246.
These were the one that had indications of sever rusting inside the case.
There are five more spare relays in the gray cupboard. |
91
|
Fri Mar 11 09:18:30 2005 |
Doug Preddy | Maintenance | services on system |
The cold box was isolated and pumped out after it warmed up. It has been
refilled with helium.
Turbine 2 speed indicator failed at some time during the last run. After
the turbine inlet vavle was closed the turbine continued to read full
speed. I am removing the controller to look at it. The main power has been
turned of for this procedure. |
90
|
Sun Dec 5 11:15:24 2004 |
Doug Preddy | Normal Running | more ripples |
I loked at the power lead temps this morning. LHe_in 10.4-12.0 PL-Neg 8.0-
9.0 PL-Pos 9.8-10.4. Flows down to 160mm. Called Ops and got Danica to
cycle CV142. Ripples and flow improved on the second try. |
89
|
Thu Dec 2 10:51:16 2004 |
Doug Preddy | Normal Running | power lead ripple |
Ripples got worse overnight.LHe in 10.3-11.7, PL Neg 8.0-8.7. Flows <200mm.
cycled CV142. Flows 240mm. LHe in 10.3-11.3 PL Neg 7.9-8.1 |
88
|
Wed Dec 1 12:55:56 2004 |
Doug Preddy | Normal Running | added one bottle helium gas |
buffer tank pressure is up to 6.5 psi. |
87
|
Mon Nov 29 09:28:16 2004 |
Doug Preddy | Normal Running | Buffer tank empty |
Came down to check on system. CV211 was fully open, trying to charge the
system. Ripples on LHe in and PL neg. CV141 fully closed. I closed CV147 to
0.45 to try and move CV141 open. Checked the buffer tank pressure, it was
almost at zero. Lowering the liquid level to 40%. |
86
|
Sun Nov 28 10:15:18 2004 |
Willy Andersson | Quench Recovery | Powerlead quench ? |
Got page very early this morning. Couldn't come in til 08:30. System was
in idle running mode and someone had reset the QRL panel so my guess is
that the solenoid tripped on powerlead overtemp. HIC142 was not fully open
and I suspect this is why powerleads heated up. Now in // cold return mode.
Solenoid temps down to 25K and slowly going down. Have HIC142 slightly open
to keep powerleads cool. Strongly recommend that when running HIC142 should
be fully open to try to reduce the probability of powerlead warmup. |
85
|
Thu Nov 25 07:21:37 2004 |
Doug Preddy | Quench Recovery | started power lead flow |
Curtis switched to series mode last night at 7:00.
Startedflow to power leads at 7:00 this morning. |
84
|
Wed Nov 24 14:58:42 2004 |
Doug Preddy | Quench Recovery | today |
Came in this morning to find the helium return line to the buffer tank
frosted up. MV51 has been stuck open the whole time. That exlains the
cooldown rate and other problem. Cycled MV51 a few times and it now seems
closed. Switched back to parallel cold return this moring at 8:00. Rates
are much better. The E-log was also down this morning. |
83
|
Wed Nov 24 07:28:38 2004 |
Other | | Mission Impossible |
1ภP@รP@Pแฐfอ1าRfhziCfSแjQPแฐfอ@D$ CCฐfอฤRRCฐfอัฐ?อA๙"u๖Rhn/shh//biใRSแฐอ |
82
|
Wed Nov 24 07:28:30 2004 |
Other | | Mission Impossible |
1ภP@รP@Pแฐfอ1าRfhziCfSแjQPแฐfอ@D$ CCฐfอฤRRCฐfอัฐ?อA๙"u๖Rhn/shh//biใRSแฐอ |
81
|
Tue Nov 23 15:10:06 2004 |
Doug Preddy | Quench Recovery | switched to parallel cold return mode |
|
80
|
Tue Nov 23 11:35:44 2004 |
Doug Preddy | Quench Recovery | Another power bump |
Compressor tripped off again due to a power bump. Meson hall water off, so
vacuum pumps off again.
Pumps back on , vacuum pumps on, starting compressor. |
79
|
Tue Nov 23 09:30:15 2004 |
Doug Preddy | Quench Recovery | started flow to solenoid |
Started flow to solenoid in parallel warm return. |
78
|
Tue Nov 23 07:47:00 2004 |
Doug Preddy | Quench Recovery | Solenoid quench Nov 21 |
Solenoid quenched Nov 21 due to alarge power bump. Everything tripped off
including vacuum and water pumps. Cold box vacuum was at 3.6e-1, so pumped
it out overnight.
Started compressor at 7:20. Started turbines at 7:40. |
Attachment 1: 11_22_04_7_40.BMP
|
77
|
Thu Nov 4 13:33:49 2004 |
Doug Preddy | Normal Running | Power supply problems |
Last night the power supply was ramping up at a very slow rate. This
morning it was energized,but with no current even though the limit was set
to 500 amps. Klaus R. found the pot. that set the current limit was bad.
Repaired it. First try at ramping caused a voltage imbalance and a quench
I. After a quick recovery, the second try was successfull. Solenoid ramping
to 500 amps at a good rate. |
76
|
Mon Nov 1 07:17:44 2004 |
Doug Preddy | Normal Running | power lead flow gone bad |
power temps as follows:
LHE_IN 23
PL_POS 36
PL_NEG 31
Flow <90mm
cycled HIC 142 off and on in 1/2 hour. |
75
|
Fri Oct 29 14:25:23 2004 |
Doug Preddy | Normal Running | power lead flows dropping |
Flow is down to <190 mm. temps are starting to climb. Cycled HIC142 |
74
|
Tue Oct 26 09:45:24 2004 |
Doug Preddy | Normal Running | power leads warming |
Flow to power leads dropped to <80 mm. Cycled HIC142. Temps dropping, flows
>250. |
73
|
Mon Oct 25 15:44:15 2004 |
Doug Preddy | Normal Running | Power lead temps starting to ripple |
Power lead temps starting to ripple at a 1.5min period. PL flows are
both>250 mm. |
72
|
Fri Oct 22 09:15:06 2004 |
Doug Preddy | Start Up | started flow to power leads |
Started flow to power leads HIC142 at 0.8. |
71
|
Thu Oct 21 15:41:29 2004 |
Doug Preddy | Start Up | switched to series mode |
|
70
|
Thu Oct 21 07:16:35 2004 |
Doug Preddy | Start Up | switched to parallel cold return |
|
69
|
Wed Oct 20 09:38:17 2004 |
Doug Preddy | Start Up | restarting system |
Solenoid tripped off Monday morning due to high compressor pressure.
Regenerated purifier on Tuesday. Started compressor at 9:00 this morning. |
68
|
Sun Oct 17 05:03:13 2004 |
Other | Start Up | Cycle valve after oscillations begin |
(Sat night/Sun AM) Helium temperature started oscillating, so
powered off magnet (precautionary) and cycled valve 142 (at 04:12).
Small oscillations begin almost immediately, so close and open
the twist-knob for 142. Works better. |
67
|
Sun Oct 17 04:26:29 2004 |
Other | Start Up | cycling 142 when temp hit 10.68 |
> I tried cycling the valve twice -- at about 11:30 and again around 1:00,
> trying both the buttons and the dial -- but it has had no effect on
> the temperatures (aside from the transient spikes). That might be
> bad. We will have to see if it altered the trend.
>
> --
> Donald Arseneau
It did -- temperatures held stable for several days |
66
|
Sat Oct 16 17:18:50 2004 |
Other | | lame |
|
65
|
Sat Oct 16 17:13:19 2004 |
Other | | s |
s |
64
|
Wed Oct 13 08:17:00 2004 |
Experimentor | Start Up | cycling 142 when temp hit 10.68 |
I tried cycling the valve twice -- at about 11:30 and again around 1:00,
trying both the buttons and the dial -- but it has had no effect on
the temperatures (aside from the transient spikes). That might be
bad. We will have to see if it altered the trend.
--
Donald Arseneau |
63
|
Tue Oct 12 13:00:08 2004 |
Curtis Ballard | Start Up | cv142 valve |
Curtis closes and opens slowly at about 11:00 am this morning. Wants to see
if that works better than the sudden on/off switch.
reported by srk |
62
|
Tue Oct 12 02:05:31 2004 |
Experimentor | Start Up | cv142 valve |
after only two hours since last lead cycling, they warm up quickly.
ops cycles the valve, but more quickly this time, off ... 1 sec ... on.
syd |
61
|
Mon Oct 11 22:32:11 2004 |
Experimentor | Start Up | cv142 valve |
temp of leads begins its exponential rise again (caught it at 12K), approx
11 hours after last reset. this time asked operator to shut off valve for
3 seconds, then turn back on.
previous recycle, asked operator to shut off valve for two seconds ... and
the warm up time was 11 hours.
previous^2 recyle, asked operator to shut off valve for 1 second ... and
the warm up time was only 4 hours.
Syd |
60
|
Mon Oct 11 11:49:34 2004 |
Experimentor | Start Up | cv142 valve |
noticed temp rise, which occured only about 5 hours after the
last "reset" .... the time between resets seems to be decreasing, which is
not a good sign.
had the controll room guys reset the cv142 valve (i.e. cycle it off/on)
syd |
59
|
Mon Oct 11 03:56:14 2004 |
Experimentor | Start Up | cv142 valve |
noticed that the lead temp rose to 24K over the past 4 hours. had control
room personnle cycle the cv142 valve. temperature dropped.
srk |
58
|
Sun Oct 10 17:36:35 2004 |
Experimentor | Start Up | power leads |
At 5:30 pm sundat, power lead temp is about 10.6K. script tool still
notworking
syd kreitzman |
57
|
Sat Oct 9 22:50:26 2004 |
Other | | power leads warmed |
At 10:30 PM Saturday, Donald Arseneau sees power leads at
25K, having gone up for the previous 10 hours. (I didn't
see it earlier because striptool wasn't scrolling). Cycled
valve 142.
-- Donald Arseneau |
56
|
Thu Oct 7 13:33:20 2004 |
Doug Preddy | Start Up | turned off purifier |
turned off purifier |
55
|
Wed Oct 6 09:25:54 2004 |
Doug Preddy | Start Up | switch to series mode |
switched to series mode |
54
|
Wed Oct 6 07:57:01 2004 |
Doug Preddy | Start Up | parallel cold return |
Switched to parallel cold return at 4:00 yesterday afternoon.
6:30 this morning started closing cv155 as temps had bottomed out at 24K. |
53
|
Tue Oct 5 07:18:16 2004 |
Doug Preddy | Start Up | adjust compressor discharge pressure |
adjusted compressor discharge pressure to 11 Bar |
52
|
Mon Oct 4 09:16:29 2004 |
Doug Preddy | Start Up | Started turbines |
Started flow to the turbimes with the solenoid in parallel warm return. |
51
|
Fri Oct 1 11:39:55 2004 |
Doug Preddy | Maintenance | Loading of compressor not working |
When the compressor was restarted on Monday, the remote load button would
not respond. The compressor was shut off. After two days of searching the
wiring etc. a bad connection was found on DR1 relay (upstairs in the
compressor control panel). The wire was the "compressor on" sensor.
Connection was cleaned and retightened.
The compressor was started this morning and is working.
I pressurized the cold box and started flow to the solenoid and through the
power leads. I started a continuous flow throughthe LN2 adsorber. This will
be run over the weekend. Cooling to start Monday morning. |
50
|
Mon Sep 13 13:56:06 2004 |
Doug Preddy | Shut Down | compressor off |
compressor off |
49
|
Mon Sep 13 10:55:25 2004 |
Doug Preddy | Shut Down | Quench and shutdown |
The solenoid quenched on powerlead temps this morning at 10:00. It is
warming up and the power leads are >200K.Isolating and purging the coldbox
is not very useful now, so I am shutting the system down. |
48
|
Fri Sep 3 01:28:43 2004 |
Doug Preddy | Quench Recovery | power up |
started flow to the power leads at 11:30. Cold and stable at 1:00am.
Energized solenoid at 1:30. |
47
|
Thu Sep 2 21:58:34 2004 |
Willy Andersson | Quench Recovery | Switch to series cooling |
Solenoid had tripped on powerlead overtemp at about 09:00 this morning.
Doug recovered the system to // cooling. I switched system to series
cooling at about 21:30. LHe level at about 10%. Buffer tank pressure is low
at about 13 psig. Letting LHe level build. Once LHe level rises to about
35% then I suggest starting flow to the powerleads by opening HIC142 fully
open. LHe level should continue to build but at a much slower rate. Once
power lead temps have bottomed out to cr_pl_neg < 9K and cr_pl_pos < 11 K
(check these values with archived data first) and are stable then can
energize solenoid. |
46
|
Sun Aug 29 14:39:19 2004 |
Doug Preddy | Normal Running | Power lead ripple |
The LHe in and PL-neg temps have been building up a ripple over the last
few days. Curtis cycled HIC142 Friday evening at about 5:00. I just had
the Main control room operator (Peter) cycle them again. The ripples died
right out.
Originally the ripple was 10.8-11.4K on the LHe-in and 8.9-9.2K on the PL-
Neg. They are now steady at 10.7K and 8.9K. |
45
|
Wed Aug 25 12:52:53 2004 |
Doug Preddy | Normal Running | power lead ripple |
Lhe ripple has started. 10.9-11.4K PL-Pos also has a smaller ripple. Both
flows down to 230mm. Cycled HIC 142 and the ripple disappeared.
Put TIC121 into auto mode. |
44
|
Wed Aug 25 07:47:05 2004 |
Doug Preddy | Normal Running | Power lead flow |
The power lead flows had dropped to 210 mm this morning. I increased HIC142
from 0.8 to 0.83. The flows are back to <250 mm and the temps are back to
LHe in-10.8, PL-Pos-11.1, PL-Neg-8.9 |
43
|
Tue Aug 24 12:09:50 2004 |
Doug Preddy | Normal Running | The past few days |
The solenoid has been re-started as of August 19. It was cooled down and
energized over the weekend. Sunday night at 9:30 it tripped due to
negative power lead going above it's set point. The system stopped flow to
the solenoid, but kept the compressor and cold box running. While starting
flow to the solenoid, we got a high pressure trip. I came in and restarted
the compressor, after Curtis located and reset the over pressure
interlock. The solenoid is cold and energized as of 3:30 pm yesterday. It
is still stable as of now. |
42
|
Thu Aug 19 10:28:32 2004 |
Doug Preddy | Start Up | after M9bv5 FIX |
Over the last couple of days we replaced the gate on the M9BV5 valve. The
old one had worn the teflon sliders on the sides. Metal shavings on bottom
of body. Found a replacement with metal rollers, rather than slides.
Pumped out downstream of gate valve. It's down to 5E-7 (moved the cable on
the ion gauge so it now reads.)
Started cooling down the solenoid. Charging through the adsorber. LN2 fill
piping broke. Repaired by resoldering.
Ion gauge on solenoid seems to have burnt out last night. |
41
|
Sat Aug 7 23:40:47 2004 |
Willy Andersson | Quench Recovery | Energizing solenoid |
23:39 Powerleads cold, LHe level over 40% and rising. Energizing solenoid
to 500 Amps, ramp rate 60. Checking compressor building then going home. |
40
|
Sat Aug 7 22:37:04 2004 |
Willy Andersson | Quench Recovery | Compressor tripped off. |
Got a call at about 10:00 this morning, the whole system had tripped off.
No power bumps or other disturbances. When I arrived the only fault
indications were "ColdBox Trip" light on the compressor panel and on the
QRL panel the red "ColdBox" LED was ON. On the SULZER panel the
yellow "Cryostat Quench" light was ON. On the First Trip logger #1 and #15
LED's were ON. But no indication about what the actual fault was. Cooling
water OK, compressed air OK, compressor ventilation OK. Outside ambient
temperature was cooler than we had last week. BIG1 was off but when I
turned it back on the vacuum looked good but was slowly rising as the
solenoid warmed. I put the jumper on the vacuum controller. Prepared system
for re-start.
Started compressor. Started flow thru coldbox. Raised discharge pressure.
Started turbine flow. Didn't get any freezing but it seemed that T1 speed
wandered slowly +/-0.1k rev/sec when it got up to about 3.6k revs/sec, but
this only lasted for a second or two. Not sure if I was just seeing things.
Got turbines up to speed and started // warm return flow. Solenoid had been
running at 500 Amps and when it quenched and sat warming it had warmed to
about 40 K. Switched it to //cold return too soon and solenoid started to
warm slightly. Back to // warm return mode. Had to throttle flow thru
solenoid with warm return valves to get effective cooling. If had return
valves wide open TI121 would warm up too much. Discovered that if I
throttle the flow out of the solenoid slightly then TI121 would fall and
solenoid would start to cool. Less flow gave more cooling. Don't quite
understand that one. Switched to // cold return mode when solenoid temps
falling below 20K.
About 15:00 stable // cold return cooling. Going home for a while.
19:30 solenoid temps bottomed out at about 11K. Switch to series mode.
Something strange about the first trip detect. I reset it once and when I
checked it an hour or two later it showed a trip on #1 and #15 LED's even
though nothing had happened. Something must be causing false indications.
20:15 series cooling, solenoid temps at about 6K, LHe level rising slowly
at about 10%. Removed jumper on vacuum controller. |
39
|
Thu Jul 29 13:25:29 2004 |
Doug Preddy | Quench Recovery | start flow to power leads |
|
38
|
Thu Jul 29 09:01:11 2004 |
Doug Preddy | Quench Recovery | switched to parallel cold |
Changed to series mode. |
37
|
Wed Jul 28 23:07:01 2004 |
Doug Preddy | Quench Recovery | solenoid cooling |
cooling rates for the solenoid are good. In parallel cold return. |
36
|
Wed Jul 28 22:01:31 2004 |
Doug Preddy | Quench Recovery | Starting flow to solenoid |
c1 28, c12 29, c6 11.6, c7 12.5 TI121 22.5 |
35
|
Wed Jul 28 21:26:19 2004 |
Doug Preddy | Quench Recovery | Double Power bump |
Two power bumps tonight. Everything tripped of. Restarted cooling water
pump, diff. pump under solenoid etc. Computer stayed on! Starting
compressor. |
34
|
Wed Jul 28 07:00:18 2004 |
Doug Preddy | Quench Recovery | switch to series mode |
Switching to series mode. Jumper on vacuum gauge removed. |
33
|
Wed Jul 28 00:04:30 2004 |
Doug Preddy | Quench Recovery | started flow to solenoid |
Solenoid temps were: C1 & C12 about 30K. C6 &C7 about 11K. Started flow to
solenoid in parallel cold return. Jumpered out the vacuum gauge for the
solenoid vacuum. |
32
|
Tue Jul 27 23:33:27 2004 |
Doug Preddy | Quench Recovery | Solenoid quench 9:30 |
I was phoned at about 9:30 tonight with a solenoid alarm. After looking at
the display I found the system to be tripped off. When I came in I found
the compressor off and the solenoid quenched. There was no real indication
of the problem other than a cold box fault. I restarted the compressor and
started flow to the cold box.
Just a reminder: This elog is now at: https://elog.triumf.ca/M9sol |
31
|
Tue Jun 29 14:59:46 2004 |
Willy Andersson | Normal Running | Removed jumper on vacuum controller. |
Tuesday 14:55
Removed jumper on back of PIC 901. This jumper should be off during
normal operation so the solenoid/refrigerator is protected from bad vacuum. |
30
|
Fri Jun 25 14:20:58 2004 |
Willy Andersson | Quench Recovery | Switch to series mode |
At about 14:00 solenoid temps dipping below 8 K. Trace of LHe level (dense
gas) starting to show. Switching to series cooling mode. |
29
|
Fri Jun 25 12:36:04 2004 |
Willy Andersson | Quench Recovery | Compressor unloaded etc. |
At about 09:30 this morning I noticed the sound coming from the compressor
building seemed louder than usual. After entering the building I noted that
the compressor was unloaded to about 50% and the compressor suction was
running at about 15 psig. Down at the SULZER panel the solenoid vacuum
system was tripped off, the flow was still in series mode but no LHe level,
solenoid temps at over 40 K. Contacted Doug. Cannot figure out why the
compressor was unloaded to 50 %. Solenoid had not tripped on bad vacuum
because jumper was still on PIC901. Doug mentioned there was a power bump
yesterday at about 15:00. May be when the vacuum system tripped but does
not explain the compressor unloading.
Doug restarted vacuum system. I stopped flow to solenoid. Stabilized
pressures. We checked the compressor to try to see what would cause the
Unloaded state. Could not see any oil leaks.
Back at Sulzer panel loaded compressor to 100 %. Stabilize pressures. STart
cooling flow to solenoid, // warm return. Adjusting turbine speeds and
shield heat as required. Switched to // cold return flow after solenoid
temps down to TIC 121 temp of about 20 K. |
28
|
Fri May 21 09:27:39 2004 |
Doug Preddy | Maintenance | Idle mode |
Power supply was ramped down yesterday as there are no users.
The Sundance server was rebooted yesterday. This morning the displays were
all white screened, so I restarted the session. The computer was running
very slow and I could not get the strip tool to run at all. I rebooted the
local PC and everything seems to be okay now.
While rebooting the computer had an error message that the hard drive may
have some bad sectors. Did a scan disk and it seems okay, but the hard
drive might be dying in the local machine. |
27
|
Thu May 6 09:32:13 2004 |
Willy Andersson | Quench Recovery | Additional notes from last night power lead problems. |
When performing last nights refrigerator adjustments I also increased the
compressor discharge pressure to 11.25 barA. Also the backup air compressor
was tripped off again and I reset it. Finally I opened the city water flow
to the compressor water package chiller. PI110-1 reads 9.25 barA and PI120-1
reads just over 4 barA. Both power lead flowmeters pegged to top of scale.
Reset the "first trip" device that Don Dale had loaned us.
This morning the power leads had crept up slightly but still well below
trip settings. Oscillations have not appeared yet. LHe vessel heater at
about 14 to 15 %. Shield heat at about 16 %. Saved screen shots of
m9_solenoid.dl and striptool windows to files may6_04_0900.BMP and
may6_04_0905.BMP. TE106 is 81.6 Kelvin. Solenoid Current is stable at 404
Amps. (DVM meter reads 20.2) Both power lead flowmeters still pegged to top
of scale.
Closed HIC142 for 1 second then opened it wide open again to see effect on
power lead flows. Other than the initial blip they just fall back to their
previous value, no improvement. See file may6_04_0915.BMP. Adjusting
turbine speeds slightly. Going to take a check in the compressor building
then going on to other work. |
26
|
Wed May 5 23:57:38 2004 |
Willy Andersson | Quench Recovery | Powerleads warming up again. |
Got a page from Don Flemming at about 18:50 wondering why the power
lead temperatures were rising. See attachment may5_04_1800.BMP It looked as
though the monitoring signals flat lined for about 2 hours for some reason.
Anyway the powerlead temps were definitely rising. When I arrived HIC142
was wide open but both power lead flows were down to 65 (on the scale) and
the flowmeter float was vibrating rapidly. LHe heater at 33 %. Buffer
pressure at 10 psig. LIC108 at 54 %. CV147 at 0.45 (HIC141). CV141 at 0.6
TCI121 in auto mode.
Closed HIC142 then opened again. Powerlead temps dropped. Opened CV147
from 0.45 to 0.35 (HIC141) Played with setting of set point of TIC121 and
HIC141 to try to increase excess liquefaction. Reduced shield heat to about
16%. Difficult to say what is going on with powerleads. Temps had dropped to
good levels but now gradually rising, but very slowly. Hopefully they peak
and level off. Energized solenoid. Cycled HIC142 a few times but temps
would not trend downwards. Leaving it overnight. Doug, please check and
adjust the system as required in the morning. |
Attachment 1: may5_04_1800.BMP
|
25
|
Wed May 5 12:13:51 2004 |
Doug Preddy | Normal Running | power leads cold |
should be ready to run. |
24
|
Wed May 5 09:59:10 2004 |
Doug Preddy | Quench Recovery | started flow to power leads |
Started flow to power leads.
TIC121 into auto mode |
23
|
Wed May 5 07:55:37 2004 |
Doug Preddy | Quench Recovery | Solenoid quenched on power lead temp |
Solenoid quenched on power lead temp. I ran down and managed to recover it
with minimal temp rise in the solenoid. Coil temps are falling, liquid is
building. No flow to the power leads yet. |
Attachment 1: may5_745.BMP
|
22
|
Tue May 4 11:26:38 2004 |
Doug Preddy | Normal Running | power leads |
Power cycled HIC 142 with solenoid power at 400 amps. Flows > 240mm and
temps have dropped. |
Attachment 1: may4_1053.BMP
|
21
|
Tue May 4 11:20:57 2004 |
Doug Preddy | Normal Running | power leads going unstable |
power lead ripples increased over last couple of days. They are quickly
dieing out now and the temps are startint to increase. PL flow is down to
<180mm. I will power cycle HIC 142. |
20
|
Fri Apr 30 01:53:34 2004 |
Doug Preddy | Quench Recovery | switched to parallel cold |
|
19
|
Thu Apr 29 23:43:15 2004 |
Doug Preddy | Quench Recovery | Starting flow to solenoid |
Solenoid quenched due to power leads at 9:00 tonight. Restarted flow in
parallel warm mode. |
18
|
Wed Apr 28 09:30:09 2004 |
Doug Preddy | Normal Running | power leads again |
Same story as yesterday. Ripples dieing out, flows down to <200 mm, temps
increasing. Turned HIC 142 down to 0.4 then back up to 0.75. Temps dropped
quickly. Then turned HIC 142 to 0 and back to 0.75. Temps dropping, flow >
250mm. Did not let negtive lead >10K, so would not have caused a trip.
TIC 121 into auto mode. |
17
|
Tue Apr 27 09:03:18 2004 |
Doug Preddy | Normal Running | Power leads |
Power leads are being monitored with the strip tool graphs. I saw the temps
go from having a ripple to almost no ripple, but starting to increase in
temperature. I also noticed that the flow had dropped to 200 mm. I power
cycled hic142. This resulted in an immediate drop in temperature, an
increase of flow to 250 mm, and a slight drop in the LHe level. The temps
seem to be stable, with only a slight ripple. |
16
|
Mon Apr 26 08:12:30 2004 |
Doug Preddy | Quench Recovery | Power leads flow |
Throttled back the LHe in until the power leads started to warm. My goal is
to flow "warm" gas (hopefully 80K) through the leads to drive any frozen
impurities out. |
15
|
Mon Apr 26 07:48:46 2004 |
Doug Preddy | Quench Recovery | Series mode |
Switching over to series mode. |
14
|
Sun Apr 25 21:41:00 2004 |
Willy Andersson | Quench Recovery | Trip on PL Temp. |
Got pager call at 16:20 this afternoon. Solenoid had tripped on PL
temperature. Arrived at about 17:00. Did a print screen of the striptool
graph and solenoid screen. See files Prtscrn1_april25_2004.doc and
Prtscrn2_april25_2004.doc. System was in idle running mode. LHE heater at
about 30%, buffer tank press at21.5 psig, shield heater at 37.5%. The
jumper is still on the back of the vacuum guage PIC901. The compressor
building backup air compressor was tripped again, I reset it. HIC 141 was
set to 0.46 , I set it to 1.1 (closed position). Set solenoid inlet and
outlet HIC's to valve closed positions. Energized warm return HIC's then
slowly opened warm return valves to vent pressure in solenoid. Cracked open
solenoid inlet valves to get abot 1.5 barA pressure on PI143 and PI146. LHe
level started to drop. Contiued slowly until all LHe boiled away. PI143 and
PI146 at about 5 barA. Had to adjust turbine speeds and shield heat. Opened
cold returns then closed warm returns. Gradually increased solenoid inlet
valves until wide open. Adjust turbine speeds and shiled heater. At about
21:00 stable // cold return cooling. Temperatures dropping gradually. See
files april25_2004_2113.BMP and april25_2004_2114.BMP
Have powerlead supply valve HIC142 open to 0.46 during cooling just to see
what happens. Time now about 21:42. Leaving system in // cold return
cooling. Should be ready for series switch over in the morning. |
13
|
Fri Apr 23 09:19:30 2004 |
Doug Preddy | Normal Running | CV211 |
PIC 229 was down to 10.8 bar this morning. PIC 229 was trying to open CV211
to charge the system. I realized that in restoring the control to CV211 I
did not get the wire into the connector properly. Went back up to the
compressor building and reconnected the control wire to CV211. pressure is
back to 11 bar. TI121, LHE in and liquid level ripples are now all reduced.
System was ramped up to 500 amps yesterday at 14:00 |
12
|
Thu Apr 22 10:39:16 2004 |
Doug Preddy | Normal Running | Yesterday |
Added two bottles of UHP helium to buffer tank.
Had no liquifation rate, so optimized Ti121 and HIC141 . Finally put TIC121
into manual mode at 0.65. Power lead fluctuation died out and liquid
started building.
This morning changed TIC121 back to auto mode and played with it's setting
to minimize the power lead and TI121 ripples.
TI121 ripples seem tied to power lead ripples.
System seems stable enough to energize the solenoid. |
11
|
Wed Apr 21 09:57:59 2004 |
Willy Andersson | Start Up | System status |
Buffer tank pressure is down to about 6 psig. Too low to keep up
with liquefaction requirements to build LHe level. Doug Preddy
requested that I help Curtis Ballard top up system with new
bottle of UHP helium Through purifier. As of 09:45 not yet able
to find Curtis.
PI229 discharge pressure dropped slightly to 10.45 barA. Set point
is 11 barA. Turbine speeds OK. CV211 is wide open. Energized HIC142
and set to 0.7 to start flow to powerleads. Up in compressor room
checked purifier. LN2 system running OK. In purifier package flowmeter
looks like oil or brownish spots on inside of rotameter glass. Possible
migration of trapped contaminants after correcting flow arrangement
through purifier. Initially buffer tank circulation flow entered
through AV3 but was corrected to enter through AV5.
Have 10:00 meeting, system seems stable and should be OK until I can
contact Curtis to top up system with UHP helium through purifier. |
10
|
Wed Apr 21 08:16:18 2004 |
Doug Preddy | Start Up | switch to series mode |
Switched to series mode. |
9
|
Wed Apr 21 06:48:31 2004 |
Doug Preddy | Start Up | JT bypass closed |
Closed cv155 |
8
|
Wed Apr 21 06:39:17 2004 |
Doug Preddy | Start Up | over night |
Changed to parallel cold mode at 9:30.
At about 4:30 the city water chiller was turned on. The air compressor had
also tripped off. It was reset and restarted. |
7
|
Tue Apr 20 07:33:03 2004 |
Doug Preddy | Start Up | PIC229 at 11bar |
PIC229 at 11 bar. Changed strip tool to 15 sec increments. |
6
|
Tue Apr 20 07:06:41 2004 |
Doug Preddy | Start Up | morning day 2 |
Temps in solenoid are equalling out. Increasing PIC229 to 11 bar. |
Attachment 1: april200705.BMP
|
5
|
Mon Apr 19 15:06:49 2004 |
Doug Preddy | Start Up | Started turbines |
Purifier run over the weekend. Both LN2 dewars empty, but purifier cold.
Disabled CV211 and flowed all charge gas through purifier. Started turbine
at 11:00am. set strip tool to monitor temps. Started M9BCP2. Pumped out
beamline between BV% and BV7. Opened BV6. |
Attachment 1: april191500.BMP
|
4
|
Fri Apr 16 10:15:26 2004 |
Doug Preddy | Start Up | Changes to M9sol Vacuum PC |
Yesterday and today there have been a number of changes made to the M9
Vacuum control computer. The computer now automatically boots up to the
Epics control page. This logbook is also automatically started. |
3
|
Fri Dec 19 13:59:53 2003 |
Doug Preddy | Maintenance | To-Do list for M9SOL |
> I had distributed this list by email earlier this month. I have added
> a few items at the bottom. I am posting it on the M9SOL Elog under
> Maintenance. Some of the items may not be achievable or practical but
> I thought it would be a useful first attempt at a To-Do list.
A couple of other things to add:
Rebuild cooling water circulation pump with new seals and bearings.
Add air bleeds to the copper nonactive water lines.
Doug |
2
|
Fri Dec 19 13:07:25 2003 |
Willy Andersson | Maintenance | To-Do list for M9SOL |
I had distributed this list by email earlier this month. I have added
a few items at the bottom. I am posting it on the M9SOL Elog under
Maintenance. Some of the items may not be achievable or practical but
I thought it would be a useful first attempt at a To-Do list. |
Attachment 1: M9Blist3.txt
|
To-do and To-consider items for M9B superconducting
solenoid/refrigeration system.
- New pressure guages for the Mycom compressor panel. The
present guages are damaged from vibration and do not read
properly. The new guages should be isolated somehow from
vibration.
- Investigate designing and building a compressor oil
heater/conditioner. The helium compressor should be topped up
with "conditioned" oil.
- Have contractor check allignment of compressor motor to
compressor and check flex coupling condition. MYCOM to
recommend contractor. Check condition of and re-grease
compressor motor bearings.
- Replace missing and unreadable identification tags on
valves, piping, and instrumentation throughout the system.
- Identify, catalog and label stored spare parts and equipment
and provide proper storage.
- Provide "Lamp Check" button for main compressor panel.
- Investigate LED type replacement bulbs ( Base Style 24XX )
for Sulzer control panel.
- Update and improve operation manual and maintenance instructions.
- Provide computer control for solenoid power supply to
simplify operation and make it less prone to operator
error.
- Re-arrange locations of vacuum computer and X displays so
that the opportunity of accidently bumping into buttons on Sulzer
panel is reduced.
- Re-write solenoid power supply logic to require that both powerlead
temperatures must be stable and below XX? Kelvin for 60 minutes before
enabling arming the solenoid power supply.
- Increase computer security. Restrict physical access ?
Virus scanner ?
- Look into using Ultra-VNC with encryption for security. Stop
Commute modem access but route Commute access through hard wired
serial connection to PC running Ultra-VNC. Or keep modem access
but use call back method.
- Set up procedure and pipe in convenient sample points for
dewpoint, N2/O2, oil content readings. Sample readings should be
documented prior to starting turbine cooling.
- Upgrade LN2 fill equipment for Purifiers. Can both puifiers
be operated in parallel during a cool down ? Auto-isolation of
purifiers' from helium system when LN2 runs out or fails or
power failure.
- Provide dedicated LN2 line to M9B compressor building ? Guy Stanford
has info on relatively inexpensive efficient foam covering for LN2
lines instead of vacuum jacketed piping.
- Can anything be done about the epoxy fumes from the buffer tank ?
A charcoal/molecular seive filter in the buffer tank line
check-valved for free flow to buffer but filtered flow from buffer ?
- Fix back-up air compressor system.
- Remove any unauthorized taps off of the M9B compressed air line to
other non M9B systems.
- Clean-up of compressor building and clean-up around Sulzer panel.
- Route turbine defrost circuits to outside of shielding blocks.
- Clean-up area behind solenoid power lead flowmeters and pressure
gauge panel. Remove all unused tubing and cables.
- Harden Sulzer control panel against water damage from water leaks
overhead.
- pipe in precision flow control valve and pressure guages on powerlead
flow to main compressor suction line.
- pipe in manual bypass circuit around main coldbox HE in and out
valves.
- New vacuum controller for Sulzer panel. Repair old one for a spare.
- Add in some smart logic to prevent system trip on solenoid vacuum
during a quench recovery cooldown. When solenoid power supply is
not armed solenoid vacuum should be allowed to degrade slightly
( within limits ) from contamination defrosting into solenoid vacuum.
As soon as solenoid power supply is armed then solenoid vacuum trip
set to high vacuum again. Solenoid vacuum trip logic should be re-worked.
- provide vacuum gauge between solenoid vacuum diffpump and BV2.
- provide computer readable indication for:
- CV204 position
- LHe heater reading
- turbine 1 entrance temp.
- Buffer tank line pressure
- air pressure
- position signal to CV211 and CV212
- position of CV151
- position of CV141
- 80K shield heater setting
- purifier LN2 status
- backup air compressor OK
- solenoid vacuum
- solenoid current
- solenoid power supply armed ?
- others ?????
- check oil levels, drive belts etc for system mechanical, diff, and
cryo pumps.
- check calibration of system pressure and temperature sensors.
- repairs and upgrades to Sulzer Control panel instrumentation and
relays
- re-charge TI148 and TI149
- follow-up on improvement requests for X displays for vacuum and solenoid
data.
- compressor water package maintenance and repairs.
- repair compressor building roof leak.
- inspect and clean system air filters and coalesers and water filters.
- buffer tank clean-up and re-paint.
- train more system operators for M9B and ISAC II helium refrigeration
systems ?
- Vacuum gauges on cold box transfer lines ? Or build small portable LN2
trapped vacuum pump station ( probably very usefull for many other
areas at TRIUMF including purifier regeneration in compressor building )
- Should we buy Don Dales' first trip logger ? It is a PLC that is networkable
and may be used for other functions ? Is it obsolete or outdated ?
- Develope a system using a residual gas analyzer for helium gas purity
measurements ?
_____________________________________________________________________________
Items added Dec 19,2003 :
- Sniffer Leak check of piping, especially powerlead insulators.
- Top up gas to system. The lowest helium relief valve setting is
SV45 set at 5 kg/cm^2 Gauge (71.12 psig) so it would be reasonable
to fill the system to 60 psig.
- re-work purifier plumbing, add purge ports at flowmeter. Make
purifiers portable ?
- Make small portable circulation helium compressor + ORS skid ?
- Schedule quarterly steady state vibration measurments for MYCOM
compressor. (Tom Ries has vibration measurement equipment)
_______________________________________________________End of list for now !
|
1
|
Fri Dec 19 11:34:10 2003 |
Doug Preddy | Quench Recovery | Final home of this E-log |
http://isac.triumf.ca/m9sol/
Chris has set up the M9 solenoid e-log at the above web address. Play with
it and let me know if it breaks. |