Logbooks Lab Maintenance Evaporator_1 Evaporator_2 Laser cutter Target Production Test-Stand RH-ISAC RH-Cyclotron RH-Meson Hall RH-Beamlines RH-ARIEL
  Test-Stand, Page 8 of 53  Not logged in ELOG logo
New entries since:Wed Dec 31 16:00:00 1969
  ID Date Author Target/No.# Source Station Module Target Oven W.O# Heat Shield W.O# Status Subject
  909   Tuesday, January 04, 2022, 13:00 Aaron Schmidt       Post water leak

 December 30th, 2021: Water poured down around Isac test stand and probes lab area in service annex extension. problem was traced to a Cracked HVAC coil on SA roof

Fault: 14601 

https://web.accel.triumf.ca/ncr/dbfault.pl?faultno=14601&usertype=unknown&username=&faultgroup=CYCLOTRON&debug=0&btn_submit=Showfault


https://elog.triumf.ca/TIS/Test-Stand/908

Noted on arrival to startup the ISAC TS some cleaning of the area was required. Optics PS & all PS quickly checked. OK / Dry. 

Use caution when HV is to be applied later. Expect conditioning / noise from the cage. 

 

  908   Tuesday, December 21, 2021, 13:34 Aaron Schmidt LP-SIS  44691-844378-6In progressSalts test HS & Holiday Shutdown

LP-SIS modified w/ 2 holes on the center block to accept a pair of Ta tubes that are run to the coil PS.

*Note modified HS plates at the ion source to accommodate the LP-SIS (Has a slightly bent ionizer tube from the drilling)

-Plan to shut down the ISAC TS on 12/23/2021 for the holidays.

Thermocouples are installed.

Ref:

https://elog.triumf.ca/TIS/Test-Stand/679

Pin configuration between top 9-pin connector on Source Tray and terminal in high voltage rack. Measured 2018-08-21 by Aaron and Anders

Grounded     X            
Source Tray Side (looking head on) 1 2 3 4 5 6 7 8 9
High Voltage Cage Side 5 4 3 2 1 9 8 7 6
Twisted pairs TP1 TP1 - TP2 TP2 TP3 TP3 TP4 TP4

 


Tuesday, December 21, 2021, 13:55: Roughing.

Tuesday, December 21, 2021, 13:57: BV1A open.


Thursday, December 23, 2021, 07:42: TP2 & TP6 off.

Thursday, December 23, 2021, 09:00: PV1 & PV2 off. RP1 & RP2 off.


Clean up?? What happened here? (Water mess?)

Tuesday, January 04, 2022, 11:13: RP1 & RP2 on.

Tuesday, January 04, 2022, 11:14: Roughing.

Tuesday, January 04, 2022, 11:17: TP2 & TP6 on.

Tuesday, January 04, 2022, 11:21: IG6 on.

Tuesday, January 04, 2022, 13:00: TP1B on.


Carla:

Swapped top and bottom connector on target side multipin to match up with wires. Added kapton tape where things were touching. TC#3 (ROI) maybe won't work, was very twisted. Not sure if I got all the twists.

Data logger Location Source tray position HV rack position
TC#1 MMO 1 pos

5 pos

     6 neg 9 neg
TC#2 MMI 4 pos 2 pos
    5 neg 1 neg
TC#3 ROI 8 pos 7 pos
    9 neg 6 neg

 


Monday, January 10, 2022, 09:53: Roughing.

Monday, January 10, 2022, 15:55: TP1B on

Monday, January 10, 2022, 16:04: TP1A on.

Monday, January 10, 2022, 16:14: TP2 Tripped. Back on within 30 seconds.

Monday, January 10, 2022, 16:14: IG1 on.


Wednesday, January 12, 2022, 09:56 : Cage has been closed up and HS water lines are open.

  907   Tuesday, November 16, 2021, 13:45 Aaron Schmidt       Pump down empty chamber

Tuesday, November 16, 2021, 13:44: Roughing. Water loop installed. Lock out tag removed.

  906   Friday, November 12, 2021, 13:01 Aaron SchmidtTa#63LP-SISITETM444691-1144378-12In progressConditioning Ta#63

Friday, November 12, 2021, 13:01: BV1B open. Roughing.

Friday, November 12, 2021, 13:05: BV1A open.

Friday, November 12, 2021, 13:34: TP1B on.

Friday, November 12, 2021, 13:42: TP1A on.

Friday, November 12, 2021, 13:50 : IG1 on. TMS:TP2 trip. Fast reset. OK. Vacuum @ 3.54e-05T. Waterline FS#5 open.

Friday, November 12, 2021, 13:53: Vacuum @ 2.12e-05T. Ok

Friday, November 12, 2021, 13:54: Power / sources on.


Monday, November 15, 2021, 09:00: Auto-ramping TGHT / TBHT to 350 / 150 @ 3 A per min. IV4 open. TMS:VCB1 not functioning. Controls group notified.

Monday, November 15, 2021, 09:40: Optics set minus TMS:VCB1 

Monday, November 15, 2021, 11:16: Auto-ramping TGHT / TBHT to 580 / 230 @ 2 A per min.

Monday, November 15, 2021, 11:34: TMS:VCB1 fixed. Optics set ok.

Monday, November 15, 2021, 11:43: BIAS / EE / EZL @ 30 / -1.5 / 13 kV.

Monday, November 15, 2021, 15:44: Mass & wire scans complete. OK. HV to 0 kV. IV4 closed.


Tuesday, November 16, 2021, 06:16: Auto-cooling TGHT / TBHT @ 2A per min.

Tuesday, November 16, 2021, 11:13: Power / sources off.

Tuesday, November 16, 2021, 11:14: IG1. Turbo pumps off.

Tuesday, November 16, 2021, 12:12: Venting.

Attachment 1: Ta#63.docx
Attachment 2: ER-580-230-30kV-m7.txt
value (Voltage offset      40.0000)
     75.0000
      1.0000
     95.0000
  29978.0220
21
21
./emit.dat
 -0.1160 -0.0705 -0.0720 -0.0665 -0.0647 -0.0714 -0.0803 -0.0665 -0.0674 -0.0714 -0.0711 -0.0635 -0.0705 -0.0665 -0.0690 -0.0772 -0.0690 -0.0217 9.9997 9.9997 0.2515
 -0.0690 -0.0644 -0.0592 -0.0662 -0.0580 -0.0604 -0.0705 -0.0592 -0.0620 -0.0650 -0.0626 -0.0537 -0.0638 -0.0589 -0.0519 -0.0146 2.8598 9.9997 1.8066 0.5316 0.0238
 -0.0500 -0.0479 -0.0446 -0.0427 -0.0522 -0.0458 -0.0439 -0.0446 -0.0565 -0.0555 -0.0443 -0.0464 -0.0540 -0.0159 4.1391 9.9997 6.1557 1.0684 0.1700 0.0089 -0.0552
 -0.0482 -0.0470 -0.0476 -0.0488 -0.0534 -0.0427 -0.0500 -0.0494 -0.0574 -0.0488 -0.0278 1.1453 9.9997 9.9997 6.5958 1.1145 0.4886 0.0500 -0.0500 -0.0323 -0.0623
 -0.0458 -0.0476 -0.0464 -0.0528 -0.0516 -0.0500 -0.0461 -0.0461 -0.0418 3.8632 9.4711 8.8336 1.4258 1.2106 0.5518 0.0836 -0.0214 -0.0427 -0.0476 -0.0433 -0.0650
 -0.0470 -0.0482 -0.0488 -0.0519 -0.0500 -0.0534 -0.0436 0.1334 7.5760 3.7332 1.4618 0.5322 0.2225 0.2005 0.0479 -0.0632 -0.0525 -0.0488 -0.0586 -0.0464 -0.0635
 -0.0476 -0.0497 -0.0458 -0.0494 -0.0491 -0.0378 1.7361 7.3523 0.9219 0.2179 0.1819 0.1324 0.0656 0.0363 -0.0317 -0.0659 -0.0449 -0.0467 -0.0458 -0.0391 -0.0537
 -0.0433 -0.0464 -0.0461 -0.0458 -0.0244 0.8417 3.5486 0.4346 0.0916 0.0552 0.0693 0.0394 -0.0171 -0.0232 -0.0424 -0.0644 -0.0449 -0.0436 -0.0439 -0.0385 -0.0513
 -0.0458 -0.0476 -0.0461 -0.0040 0.4691 4.0344 0.1456 0.0592 0.0168 0.0079 0.0122 -0.0143 -0.0534 -0.0443 -0.0443 -0.0659 -0.0443 -0.0433 -0.0552 -0.0388 -0.0525
 -0.0467 -0.0458 -0.0211 0.7001 4.1727 0.1456 0.0159 0.0079 -0.0143 -0.0299 -0.0235 -0.0378 -0.0626 -0.0427 -0.0461 -0.0650 -0.0455 -0.0436 -0.0479 -0.0375 -0.0485
 -0.0458 -0.0397 0.0229 3.0432 0.1483 0.0037 -0.0131 -0.0186 -0.0378 -0.0455 -0.0400 -0.0467 -0.0623 -0.0427 -0.0467 -0.0668 -0.0464 -0.0427 -0.0439 -0.0348 -0.0430
 -0.0443 -0.0214 3.4134 0.0745 -0.0018 -0.0223 -0.0287 -0.0342 -0.0458 -0.0494 -0.0476 -0.0525 -0.0613 -0.0433 -0.0424 -0.0708 -0.0424 -0.0418 -0.0436 -0.0369 -0.0446
 -0.0415 0.8212 0.1685 -0.0217 -0.0278 -0.0314 -0.0369 -0.0378 -0.0525 -0.0577 -0.0446 -0.0497 -0.0653 -0.0461 -0.0424 -0.0641 -0.0424 -0.0375 -0.0455 -0.0342 -0.0363
 -0.0330 1.6864 -0.0201 -0.0302 -0.0342 -0.0339 -0.0452 -0.0452 -0.0562 -0.0525 -0.0439 -0.0485 -0.0620 -0.0439 -0.0452 -0.0635 -0.0403 -0.0388 -0.0378 -0.0311 -0.0427
 -0.0195 0.0150 -0.0266 -0.0311 -0.0385 -0.0479 -0.0467 -0.0476 -0.0540 -0.0537 -0.0455 -0.0513 -0.0623 -0.0412 -0.0430 -0.0595 -0.0415 -0.0351 -0.0348 -0.0296 -0.0406
 1.9189 -0.0369 -0.0311 -0.0452 -0.0443 -0.0497 -0.0473 -0.0470 -0.0568 -0.0552 -0.0455 -0.0449 -0.0613 -0.0433 -0.0388 -0.0592 -0.0385 -0.0369 -0.0366 -0.0299 -0.0388
 0.1822 -0.0336 -0.0430 -0.0461 -0.0467 -0.0491 -0.0473 -0.0473 -0.0555 -0.0488 -0.0430 -0.0485 -0.0580 -0.0418 -0.0363 -0.0601 -0.0357 -0.0327 -0.0287 -0.0323 -0.0385
 -0.0195 -0.0385 -0.0467 -0.0461 -0.0516 -0.0461 -0.0479 -0.0461 -0.0574 -0.0540 -0.0430 -0.0424 -0.0607 -0.0400 -0.0378 -0.0568 -0.0348 -0.0314 -0.0372 -0.0330 -0.0406
 -0.0427 -0.0427 -0.0470 -0.0455 -0.0491 -0.0452 -0.0455 -0.0455 -0.0568 -0.0528 -0.0430 -0.0427 -0.0565 -0.0327 -0.0400 -0.0546 -0.0351 -0.0269 -0.0287 -0.0299 -0.0409
 -0.0385 -0.0449 -0.0443 -0.0449 -0.0497 -0.0455 -0.0446 -0.0427 -0.0540 -0.0491 -0.0427 -0.0458 -0.0574 -0.0394 -0.0360 -0.0568 -0.0323 -0.0253 -0.0336 -0.0287 -0.0388
 -0.0333 -0.0473 -0.0443 -0.0470 -0.0461 -0.0461 -0.0424 -0.0424 -0.0510 -0.0552 -0.0418 -0.0439 -0.0552 -0.0375 -0.0354 -0.0525 -0.0330 -0.0275 -0.0409 -0.0311 -0.0391
Attachment 3: ER-580-230-30kV-m23.txt
value (Voltage offset      40.0000)
     75.0000
      1.0000
     95.0000
  29992.6740
21
21
./emit.dat
 -0.1074 -0.0729 -0.0699 -0.0797 -0.0708 -0.0793 -0.0781 -0.0729 -0.0659 -0.0766 -0.0708 -0.0687 -0.0760 -0.0702 -0.0629 0.1450 0.3046 0.2570 0.0323 0.0522 -0.0122
 -0.0708 -0.0674 -0.0638 -0.0711 -0.0729 -0.0720 -0.0714 -0.0635 -0.0626 -0.0708 -0.0668 -0.0671 -0.0696 -0.0635 0.2292 0.0055 -0.0256 -0.0577 -0.0595 -0.0412 -0.0488
 -0.0711 -0.0464 -0.0485 -0.0659 -0.0681 -0.0592 -0.0623 -0.0485 -0.0623 -0.0687 -0.0482 -0.0604 -0.0647 0.2179 -0.0275 -0.0522 -0.0513 -0.0400 -0.0369 -0.0473 -0.0482
 -0.0677 -0.0504 -0.0656 -0.0519 -0.0653 -0.0580 -0.0537 -0.0500 -0.0601 -0.0699 -0.0516 -0.0546 0.1443 -0.0342 -0.0482 -0.0574 -0.0513 -0.0488 -0.0592 -0.0534 -0.0510
 -0.0732 -0.0510 -0.0504 -0.0577 -0.0647 -0.0571 -0.0540 -0.0513 -0.0629 -0.0714 -0.0504 0.1511 -0.0592 -0.0482 -0.0522 -0.0598 -0.0504 -0.0500 -0.0568 -0.0513 -0.0528
 -0.0671 -0.0531 -0.0522 -0.0623 -0.0613 -0.0620 -0.0552 -0.0525 -0.0601 -0.0699 0.1050 -0.0421 -0.0674 -0.0488 -0.0516 -0.0586 -0.0497 -0.0504 -0.0604 -0.0513 -0.0531
 -0.0687 -0.0528 -0.0571 -0.0665 -0.0644 -0.0558 -0.0577 -0.0528 -0.0604 0.0705 -0.0284 -0.0494 -0.0668 -0.0519 -0.0504 -0.0601 -0.0516 -0.0519 -0.0586 -0.0519 -0.0568
 -0.0705 -0.0507 -0.0546 -0.0610 -0.0674 -0.0577 -0.0586 -0.0504 0.0018 -0.0537 -0.0504 -0.0635 -0.0653 -0.0519 -0.0549 -0.0607 -0.0516 -0.0500 -0.0616 -0.0507 -0.0525
 -0.0693 -0.0522 -0.0528 -0.0641 -0.0674 -0.0565 -0.0531 -0.0287 -0.0009 -0.0708 -0.0467 -0.0558 -0.0659 -0.0494 -0.0516 -0.0604 -0.0510 -0.0528 -0.0601 -0.0513 -0.0525
 -0.0681 -0.0494 -0.0543 -0.0644 -0.0656 -0.0525 -0.0354 0.0375 -0.0562 -0.0705 -0.0497 -0.0598 -0.0677 -0.0497 -0.0519 -0.0589 -0.0516 -0.0528 -0.0653 -0.0543 -0.0534
 -0.0677 -0.0543 -0.0510 -0.0641 -0.0681 -0.0510 0.0162 -0.0479 -0.0604 -0.0690 -0.0504 -0.0549 -0.0711 -0.0513 -0.0494 -0.0607 -0.0494 -0.0507 -0.0598 -0.0494 -0.0543
 -0.0681 -0.0549 -0.0528 -0.0562 -0.0647 0.0327 -0.0546 -0.0507 -0.0613 -0.0674 -0.0516 -0.0577 -0.0729 -0.0519 -0.0482 -0.0586 -0.0510 -0.0507 -0.0546 -0.0485 -0.0510
 -0.0696 -0.0507 -0.0519 -0.0537 0.0079 -0.0470 -0.0595 -0.0491 -0.0598 -0.0696 -0.0519 -0.0607 -0.0693 -0.0540 -0.0513 -0.0604 -0.0507 -0.0485 -0.0583 -0.0513 -0.0516
 -0.0693 -0.0500 -0.0519 -0.0009 -0.0583 -0.0616 -0.0522 -0.0528 -0.0552 -0.0708 -0.0513 -0.0632 -0.0720 -0.0522 -0.0504 -0.0613 -0.0510 -0.0500 -0.0656 -0.0504 -0.0528
 -0.0693 -0.0473 -0.0189 -0.0574 -0.0641 -0.0528 -0.0546 -0.0519 -0.0552 -0.0723 -0.0504 -0.0577 -0.0714 -0.0510 -0.0494 -0.0586 -0.0504 -0.0510 -0.0629 -0.0513 -0.0519
 -0.0681 -0.0479 -0.0253 -0.0595 -0.0665 -0.0577 -0.0595 -0.0519 -0.0580 -0.0674 -0.0507 -0.0546 -0.0696 -0.0513 -0.0494 -0.0604 -0.0482 -0.0537 -0.0629 -0.0500 -0.0552
 -0.0668 0.0015 -0.0540 -0.0632 -0.0638 -0.0546 -0.0574 -0.0482 -0.0616 -0.0708 -0.0516 -0.0574 -0.0665 -0.0519 -0.0485 -0.0620 -0.0525 -0.0491 -0.0589 -0.0458 -0.0473
 -0.0314 -0.0510 -0.0522 -0.0519 -0.0641 -0.0543 -0.0571 -0.0513 -0.0613 -0.0690 -0.0497 -0.0586 -0.0684 -0.0507 -0.0510 -0.0568 -0.0507 -0.0452 -0.0577 -0.0467 -0.0455
 -0.0662 -0.0543 -0.0513 -0.0528 -0.0616 -0.0546 -0.0555 -0.0522 -0.0616 -0.0711 -0.0497 -0.0635 -0.0690 -0.0513 -0.0494 -0.0574 -0.0464 -0.0449 -0.0580 -0.0497 -0.0473
 -0.0726 -0.0479 -0.0546 -0.0662 -0.0635 -0.0558 -0.0519 -0.0525 -0.0632 -0.0671 -0.0510 -0.0583 -0.0717 -0.0491 -0.0467 -0.0571 -0.0400 -0.0473 -0.0571 -0.0452 -0.0446
 -0.0684 -0.0507 -0.0504 -0.0656 -0.0632 -0.0555 -0.0528 -0.0507 -0.0623 -0.0687 -0.0488 -0.0592 -0.0665 -0.0485 -0.0443 -0.0552 -0.0449 -0.0479 -0.0555 -0.0418 -0.0461
Attachment 4: ER-580-230-30kV-m131.txt
value (Voltage offset      40.0000)
     75.0000
      1.0000
     95.0000
  29978.0220
21
21
./emit.dat
 -0.1062 -0.0760 -0.0742 -0.0769 -0.0763 -0.0754 -0.0751 -0.0720 -0.0687 -0.0760 -0.0723 -0.0711 -0.0766 -0.0702 -0.0739 -0.0183 -0.0711 -0.0729 -0.0717 -0.0555 -0.0555
 -0.0690 -0.0714 -0.0714 -0.0754 -0.0711 -0.0677 -0.0674 -0.0671 -0.0641 -0.0705 -0.0671 -0.0650 -0.0723 -0.0656 -0.0049 -0.0668 -0.0677 -0.0687 -0.0653 -0.0558 -0.0568
 -0.0665 -0.0525 -0.0671 -0.0653 -0.0641 -0.0555 -0.0510 -0.0476 -0.0644 -0.0620 -0.0485 -0.0616 -0.0702 0.0089 -0.0378 -0.0696 -0.0723 -0.0443 -0.0522 -0.0510 -0.0537
 -0.0702 -0.0488 -0.0662 -0.0555 -0.0674 -0.0543 -0.0549 -0.0464 -0.0638 -0.0668 -0.0443 -0.0571 -0.0153 -0.0394 -0.0497 -0.0668 -0.0699 -0.0464 -0.0494 -0.0488 -0.0580
 -0.0681 -0.0507 -0.0558 -0.0641 -0.0699 -0.0534 -0.0607 -0.0504 -0.0653 -0.0681 -0.0519 -0.0204 -0.0595 -0.0513 -0.0522 -0.0705 -0.0711 -0.0519 -0.0519 -0.0519 -0.0552
 -0.0684 -0.0510 -0.0604 -0.0620 -0.0696 -0.0540 -0.0555 -0.0525 -0.0647 -0.0647 -0.0269 -0.0372 -0.0720 -0.0525 -0.0485 -0.0714 -0.0674 -0.0537 -0.0531 -0.0525 -0.0519
 -0.0693 -0.0513 -0.0531 -0.0623 -0.0644 -0.0562 -0.0574 -0.0516 -0.0638 -0.0485 -0.0208 -0.0558 -0.0717 -0.0485 -0.0519 -0.0723 -0.0674 -0.0513 -0.0540 -0.0537 -0.0555
 -0.0684 -0.0485 -0.0558 -0.0620 -0.0650 -0.0516 -0.0610 -0.0507 -0.0616 -0.0385 -0.0540 -0.0583 -0.0696 -0.0519 -0.0516 -0.0717 -0.0668 -0.0507 -0.0601 -0.0500 -0.0558
 -0.0711 -0.0510 -0.0583 -0.0635 -0.0653 -0.0513 -0.0613 -0.0510 -0.0403 -0.0641 -0.0510 -0.0592 -0.0696 -0.0516 -0.0491 -0.0711 -0.0702 -0.0510 -0.0562 -0.0577 -0.0540
 -0.0668 -0.0504 -0.0500 -0.0604 -0.0665 -0.0500 -0.0571 -0.0195 -0.0577 -0.0632 -0.0497 -0.0610 -0.0671 -0.0491 -0.0537 -0.0702 -0.0708 -0.0485 -0.0510 -0.0510 -0.0555
 -0.0714 -0.0522 -0.0549 -0.0616 -0.0674 -0.0504 -0.0317 -0.0302 -0.0635 -0.0677 -0.0507 -0.0531 -0.0681 -0.0504 -0.0507 -0.0702 -0.0662 -0.0507 -0.0507 -0.0543 -0.0522
 -0.0677 -0.0510 -0.0482 -0.0635 -0.0638 -0.0305 -0.0327 -0.0537 -0.0653 -0.0674 -0.0528 -0.0620 -0.0726 -0.0507 -0.0491 -0.0723 -0.0681 -0.0494 -0.0537 -0.0534 -0.0537
 -0.0665 -0.0525 -0.0510 -0.0644 -0.0513 -0.0336 -0.0586 -0.0528 -0.0638 -0.0714 -0.0528 -0.0574 -0.0696 -0.0510 -0.0507 -0.0717 -0.0702 -0.0528 -0.0528 -0.0491 -0.0568
 -0.0687 -0.0494 -0.0528 -0.0494 -0.0574 -0.0507 -0.0583 -0.0467 -0.0653 -0.0653 -0.0504 -0.0598 -0.0656 -0.0510 -0.0500 -0.0708 -0.0693 -0.0494 -0.0549 -0.0528 -0.0525
 -0.0726 -0.0488 -0.0504 -0.0537 -0.0555 -0.0504 -0.0577 -0.0488 -0.0589 -0.0677 -0.0467 -0.0589 -0.0623 -0.0522 -0.0531 -0.0720 -0.0656 -0.0488 -0.0513 -0.0485 -0.0504
 -0.0696 -0.0473 -0.0409 -0.0436 -0.0662 -0.0513 -0.0531 -0.0504 -0.0607 -0.0693 -0.0491 -0.0626 -0.0702 -0.0500 -0.0510 -0.0708 -0.0693 -0.0485 -0.0510 -0.0522 -0.0513
 -0.0668 -0.0385 -0.0201 -0.0613 -0.0668 -0.0528 -0.0555 -0.0504 -0.0647 -0.0708 -0.0510 -0.0546 -0.0699 -0.0500 -0.0507 -0.0717 -0.0705 -0.0497 -0.0528 -0.0522 -0.0494
 -0.0610 -0.0436 -0.0494 -0.0623 -0.0656 -0.0516 -0.0583 -0.0507 -0.0632 -0.0665 -0.0488 -0.0558 -0.0677 -0.0510 -0.0482 -0.0696 -0.0699 -0.0470 -0.0558 -0.0528 -0.0558
 -0.0687 -0.0342 -0.0577 -0.0595 -0.0665 -0.0479 -0.0607 -0.0507 -0.0647 -0.0653 -0.0488 -0.0592 -0.0671 -0.0507 -0.0510 -0.0687 -0.0714 -0.0476 -0.0577 -0.0537 -0.0519
 -0.0378 -0.0488 -0.0537 -0.0580 -0.0711 -0.0494 -0.0620 -0.0482 -0.0650 -0.0668 -0.0488 -0.0568 -0.0668 -0.0516 -0.0497 -0.0671 -0.0681 -0.0494 -0.0586 -0.0516 -0.0522
 -0.0662 -0.0476 -0.0525 -0.0607 -0.0656 -0.0473 -0.0613 -0.0516 -0.0638 -0.0668 -0.0516 -0.0571 -0.0684 -0.0452 -0.0485 -0.0674 -0.0687 -0.0467 -0.0540 -0.0531 -0.0522
  905   Thursday, November 04, 2021, 11:55 Fernando Maldonado      DoneOpening vacuum chamber for thesis pictures :p

Thursday, November 04, 2021, 11:54: Venting

water loop removed

Thursday, November 04, 2021, 13:39: Roughing

 

 

  904   Wednesday, October 20, 2021, 15:01 Aaron Schmidt       Pump down empty chamber

Wednesday, October 20, 2021, 15:01: Roughing.

  903   Thursday, October 14, 2021, 10:13 Aaron Schmidt LP-SISITWTM2 44378-22In progressConditioning UC#36 HS

Tube / TGHT only.

Thursday, October 14, 2021, 10:11: Roughing.

Thursday, October 14, 2021, 12:05: TP1B on. 

Thursday, October 14, 2021, 12:10: TP1A on. 

Thursday, October 14, 2021, 13:27: IG1 on.

Thursday, October 14, 2021, 16:08: Vacuum @ 3.73e-06T

Thursday, October 14, 2021, 16:10: FS#5 open. Vacuum Stable.

Thursday, October 14, 2021, 16:13: PS on. Sources on. TGHT manually tapped up to 10 A. OK. Allow vacuum to stabilize further.


Friday, October 15, 2021, 06:38: Auto-ramping TGHT to 580 A @ 2 A per min. 

Friday, October 15, 2021, 21:32: Auto-Cooling @ 1 A per min. 


Monday, October 18, 2021, 07:50: Sources, IG1, & turbo pumps off.  

Attachment 1: UC#36.docx
  902   Wednesday, October 06, 2021, 11:56 Aaron Schmidt       Pump down empty chamber

Wednesday, October 06, 2021, 11:56: Roughing.


Thursday, October 14, 2021, 09:07: Venting.

  901   Monday, October 04, 2021, 15:38 Aaron Schmidt LP-IG-LISITETM4 42132-7In progressConditioning UC#35 IG-LIS HS

Monday, October 04, 2021, 15:38: Roughing.

Monday, October 04, 2021, 16:08: TP1B on. 

Monday, October 04, 2021, 16:15: TP1 A on. 

Monday, October 04, 2021, 16:41: IG1 on.


Tuesday, October 05, 2021, 06:47: Vacuum @ 4.09e-06T.

Tuesday, October 05, 2021, 06:49: Waterlines opened. Vacuum stable.

Tuesday, October 05, 2021, 06:50: Power / sources on.

Tuesday, October 05, 2021, 06:52: Auto-ramping TGHT to 580 A @ 2 A per min.


Wednesday, October 06, 2021, 05:44: Auto-cooling @ 3 A per min. Vacuum @ 2.37e-06T.\

Wednesday, October 06, 2021, 09:37: Power / sources off.

Wednesday, October 06, 2021, 09:38: IG1 off. TSG:TP1 A & B off.

Wednesday, October 06, 2021, 11:11: Venting. Waterlines off.


Edit* Switched from ITW to ITE. on station icon - AS.

 

Attachment 1: UC#35.docx
  900   Thursday, September 23, 2021, 07:16 Aaron Schmidt       Pump down empty chamber & reboot

Thursday, September 23, 2021, 07:15: Roughing. Waterline loop installed.


Monday, September 27, 2021, 10:35: MB1 off. Turbo pumps, IG, RP, all off/closed. DI water closed/purged.

TS shutdown for planned power outage.


Friday, October 01, 2021, 06:03: Roughing pumps on.

Friday, October 01, 2021, 06:04: Roughing TS beam line side.

Friday, October 01, 2021, 06:52: TMS:TP6 & TMS:TP2 on. Venting Chamber side.

Friday, October 01, 2021, 06:57: IG6 on - Filament 2 manually set. Beam line side vacuum @ 1.5e-05T

Friday, October 01, 2021, 07:01: Vacuum @ 9.04e-06T & dropping steady (Beam line side) OK.

Friday, October 01, 2021, 07:05: Reboot ISAC TS PLC/IOC. Reset controls whiteout.

Friday, October 01, 2021, 07:10: MB1 restart ok.

  899   Tuesday, September 14, 2021, 17:12 Aaron SchmidtC#3LP-SISITWTM244691-744378-11In progressC#3 Conditioning

Tuesday, September 14, 2021, 17:00: Roughing

Tuesday, September 14, 2021, 17:37: TP1B on.

Tuesday, September 14, 2021, 17:47: TP1A on.

Tuesday, September 14, 2021, 17:55: IG1 on.


Wednesday, September 15, 2021, 06:51: Waterlines opened. Vacuum Stable @ 4.46e-06T.

Wednesday, September 15, 2021, 07:01: Power/sources/optics on - Set.

Wednesday, September 15, 2021, 07:02: IV4 opened.

 Device Temp
[C]
 Flow
[lpm]
 HS + MSP 23.8 3.99
 TBHT 24.6

3.23

 COIL + EE 23.6 5.02
 TGHT 23.8 5.66

Wednesday, September 15, 2021, 07:05: Quick system check. TGHT / TBHT @ 10 / 10 A. OK.

Wednesday, September 15, 2021, 07:06: BIAS / EE / EZL @ 1 / -0.5 / 1 kV. Not ok. BIAS short!!!* set to 1kV, zero read back. 0V & 0.230 mA.

Wednesday, September 15, 2021, 08:01: Hook was still in the cage. Removed*

Wednesday, September 15, 2021, 08:05: Quick system check. TGHT / TBHT @ 10 / 10 A. BIAS / EE / EZL @ 1 / -0.5 / 1 kV. All ok. Vacuum @ 4.02e-06T. Allow to stabilize.


Thursday, September 16, 2021, 04:38: Vacuum @ 2.13e-06T. Auto-ramping TGHT / TBHT to 350 A / 150 A @ 2 A per min. 

Thursday, September 16, 2021, 04:44: BIAS / EE / EZL @ 20 / -1.0 / 10 kV. 

Thursday, September 16, 2021, 08:58: Auto-ramping TGHT / TBHT to 580 A / 230 A @ 2 A per min.  

Thursday, September 16, 2021, 13:20: Auto-ramp halted. Vacuum @ 3.12 e-06T. TGHT / TBHT @ 410 / 210. Adjusted good vacuum / increment limit t0 5.0e-06T & 7e-06T (Back off limit). Continue auto-ramping TGHT / TBHT to 580 A / 230 A @ 2 A per min.  

Thursday, September 16, 2021, 16:30: BIAS / EE / EZL @ 30 / -1.5 / 13 kV. TGHT / TBHT @ 543+/ 230 A. TGHT still ramping on vac limit. Good wire scans so far.

Thursday, September 16, 2021, 16:36: Mass & wires scans proceeding.

Thursday, September 16, 2021, 17:16: Scans ok. TGHT @ 550 A. Vacuum @ 5.12e-06T.


Friday, September 17, 2021, 10:41: Mass & wire scans ok. BIAS / EE / EZL to 0 kV. 


Sunday, September 19, 2021, 20:33: Auto-cooling @ 1 A per min. 


Monday, September 20, 2021, 06:10: Power/sources off. IV4 off. Lock-out.

Monday, September 20, 2021, 06:13: IG1 off. Turbo pumps off.


Thursday, September 23, 2021, 05:04: Venting. 

Attachment 1: ER-550-230-30kV-m7.txt
value (Voltage offset      40.0000)
     75.0000
      1.0000
     95.0000
  29992.6740
21
21
./emit.dat
 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0012 -0.0018 -0.0015 -0.0018 -0.0012 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015
 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0012 -0.0015 0.0015 -0.0006 0.0003 0.0049 0.0009 0.0024
 -0.0015 -0.0018 -0.0012 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 0.0037 0.0110 0.0262 0.0253 0.0287 0.0281 0.0183 0.0256 0.0223
 -0.0015 -0.0012 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0012 0.0143 0.0232 0.0116 0.0018 -0.0003 0.0003 0.0000 -0.0003 0.0003 -0.0006
 -0.0015 -0.0012 -0.0015 -0.0015 -0.0021 -0.0012 -0.0012 -0.0015 -0.0003 0.0162 0.0510 0.0098 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0009 -0.0012 -0.0015 -0.0015
 -0.0018 -0.0015 -0.0015 -0.0012 -0.0012 -0.0009 -0.0009 0.0034 0.0275 0.0089 0.0000 -0.0015 -0.0018 -0.0009 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015
 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 0.0021 0.0296 0.0262 0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015
 -0.0015 -0.0012 -0.0012 0.0018 0.0177 0.0269 0.0006 -0.0009 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015
 -0.0012 -0.0009 0.0073 0.0244 0.0073 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0012 -0.0015 -0.0018 -0.0018 -0.0018 -0.0018 -0.0018 -0.0018
 0.0006 0.0198 0.0122 -0.0015 -0.0012 -0.0018 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0012 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0018 -0.0018
 0.0208 0.0018 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0012 -0.0012 -0.0018 -0.0015 -0.0021 -0.0015 -0.0015 -0.0015
 -0.0012 -0.0015 -0.0012 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015
 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0018 -0.0018 -0.0015 -0.0018 -0.0012 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018
 -0.0012 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015
 -0.0015 -0.0012 -0.0012 -0.0015 -0.0018 -0.0012 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0012 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015
 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0012 -0.0021 -0.0018 -0.0012
 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0012 -0.0018 -0.0018 -0.0015 -0.0012 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018
 -0.0012 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0018 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015
 -0.0018 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0015 -0.0018 -0.0012 -0.0018 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012
 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0012 -0.0015 -0.0018 -0.0018 -0.0018 -0.0015 -0.0021 -0.0012 -0.0015 -0.0012 -0.0015
 -0.0015 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 -0.0012 -0.0012 -0.0018 -0.0015 -0.0015 -0.0018 -0.0012 -0.0015 -0.0015
Attachment 2: ER-550-230-30kV-m26.txt
value (Voltage offset      40.0000)
     75.0000
      1.0000
     95.0000
  29978.0220
21
21
./emit.dat
 -0.0015 -0.0015 -0.0018 -0.0018 -0.0018 -0.0012 -0.0021 -0.0018 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 0.0000 0.0006 -0.0015
 -0.0015 -0.0018 -0.0012 -0.0012 -0.0018 -0.0015 -0.0018 -0.0012 -0.0012 -0.0015 -0.0018 -0.0012 -0.0015 -0.0015 -0.0018 -0.0015 -0.0012 0.0003 -0.0006 -0.0015 -0.0012
 -0.0015 -0.0012 -0.0015 -0.0015 -0.0012 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 0.0006 -0.0006 -0.0012 -0.0015 -0.0015
 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0021 -0.0018 -0.0015 -0.0018 -0.0018 -0.0018 -0.0018 -0.0012 -0.0012 -0.0018 0.0012 -0.0009 -0.0018 -0.0012 -0.0012 -0.0018
 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0012 -0.0015 -0.0015 -0.0018 -0.0015 0.0012 -0.0012 -0.0018 -0.0018 -0.0012 -0.0015 -0.0015
 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0012 0.0012 -0.0012 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015
 -0.0018 -0.0018 -0.0018 -0.0018 -0.0015 -0.0012 -0.0021 -0.0018 -0.0015 -0.0018 -0.0018 -0.0009 0.0006 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012
 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0015 -0.0018 -0.0018 -0.0012 0.0012 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0009 -0.0012 -0.0015 -0.0012
 -0.0015 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0006 0.0006 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0021
 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0012 -0.0006 -0.0006 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015
 -0.0018 -0.0018 -0.0015 -0.0012 -0.0012 -0.0015 -0.0015 -0.0003 0.0006 -0.0018 -0.0015 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0012 -0.0015 -0.0015 -0.0021 -0.0015
 -0.0015 -0.0018 -0.0015 -0.0018 -0.0018 -0.0012 0.0009 -0.0003 -0.0015 -0.0012 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015
 -0.0012 -0.0015 -0.0015 -0.0012 -0.0012 0.0006 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0018 -0.0018 -0.0015 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018
 -0.0015 -0.0015 -0.0018 -0.0015 0.0006 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0012 -0.0015 -0.0015 -0.0021 -0.0012 -0.0018 -0.0009
 -0.0015 -0.0015 -0.0015 0.0015 -0.0012 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0018 -0.0012 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015
 -0.0018 -0.0015 0.0009 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0021 -0.0012
 -0.0015 0.0003 -0.0015 -0.0015 -0.0012 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0018 -0.0018
 0.0000 -0.0012 -0.0015 -0.0021 -0.0012 -0.0015 -0.0018 -0.0018 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015
 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0021 -0.0015
 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 -0.0015
 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 -0.0015 -0.0015 -0.0015 -0.0012 -0.0018 -0.0018
Attachment 3: ER-550-230-30kV-m128.txt
value (Voltage offset      40.0000)
     75.0000
      1.0000
     95.0000
  29978.0220
21
21
./emit.dat
 -0.0015 -0.0015 -0.0018 -0.0015 -0.0021 -0.0015 -0.0015 -0.0015 -0.0021 -0.0012 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015
 -0.0015 -0.0012 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0018 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0012 -0.0012
 -0.0018 -0.0015 -0.0018 -0.0018 -0.0018 -0.0015 -0.0021 -0.0015 -0.0018 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0012 -0.0012 -0.0018 -0.0015
 -0.0018 -0.0018 -0.0015 -0.0018 -0.0012 -0.0018 -0.0018 -0.0018 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0009 -0.0015 -0.0015 -0.0018
 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0018 -0.0012 -0.0018 -0.0012 -0.0012 -0.0015 -0.0018 -0.0015 -0.0015
 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0012 -0.0015 -0.0018 -0.0018 -0.0012 -0.0009 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0012
 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 -0.0015 -0.0015 -0.0018 -0.0012 -0.0018 -0.0015 -0.0009 -0.0009 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015
 -0.0012 -0.0015 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0012 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015
 -0.0018 -0.0009 -0.0018 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 -0.0009 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0021 -0.0021 -0.0015
 -0.0018 -0.0018 -0.0012 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0018 -0.0012 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018
 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 -0.0015 -0.0012 -0.0015 -0.0012 -0.0009 -0.0015 -0.0015 -0.0012 -0.0018 -0.0018 -0.0012 -0.0015 -0.0018 -0.0012 -0.0018 -0.0015
 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0012 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0012 -0.0018 -0.0018 -0.0009 -0.0018 -0.0015
 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0018 -0.0018 -0.0012 -0.0018 -0.0015 -0.0015 -0.0018 -0.0012 -0.0015
 -0.0015 -0.0015 -0.0015 -0.0012 -0.0015 -0.0012 -0.0018 -0.0018 -0.0015 -0.0018 -0.0009 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015
 -0.0015 -0.0018 -0.0015 -0.0012 -0.0018 -0.0015 -0.0018 -0.0018 -0.0021 -0.0018 -0.0018 -0.0012 -0.0015 -0.0012 -0.0015 -0.0015 -0.0018 -0.0018 -0.0012 -0.0018 -0.0015
 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0018 -0.0018 -0.0018 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012
 -0.0015 -0.0015 -0.0018 -0.0015 -0.0012 -0.0018 -0.0012 -0.0012 -0.0012 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015
 -0.0015 -0.0012 -0.0015 -0.0012 -0.0015 -0.0018 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0012 -0.0018 -0.0018
 -0.0015 -0.0018 -0.0012 -0.0018 -0.0015 -0.0018 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0012 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018
 -0.0015 -0.0018 -0.0015 -0.0015 -0.0018 -0.0018 -0.0012 -0.0018 -0.0015 -0.0018 -0.0015 -0.0012 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0018
 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0015 -0.0018 -0.0015 -0.0015 -0.0015 -0.0015 -0.0015 -0.0018 -0.0018 -0.0015
Attachment 4: C#3.docx
Attachment 5: C#3_conditioning_-_R.docx
Attachment 6: ITW-TM2-C#3-LP-SIS_Test_Stand.docx
  898   Tuesday, September 07, 2021, 16:04 Alexander Shkuratoff      DoneReplaced flange on F/T R with blank flange

Feedthrough R had a flange installed with a HV feedthrough on it for TM3 service tray prototype HV tests. It was replaced today with the original blank flange.

  897   Tuesday, August 31, 2021, 13:55 Aaron Schmidt       Pump down chamber

Pump down chamber w/ empty HS

  896   Wednesday, August 25, 2021, 15:30 Ferran Boix Pamies       Thermocouple high voltage test

Wednesday, August 25, 2021, 15:29: Roughing.


Thursday, August 26, 2021, 04:11: IG1 switched on. Vacuum @ 8.35e-06T - AS 

Thursday, August 26, 2021, 14:04 Water on, no spike in vacuum. IG1:2.6e-6T

Thursday, August 26, 2021, 14:37 HV rack closed, BIAS EE and EZL power supplies on.

Thursday, August 26, 2021, 15:03 BIAS/EE/EZL 10000/-1000/9000

Thursday, August 26, 2021, 15:08 BIAS/EE/EZL 30000/-1500/13000 1 spark just when reached 30kV.

Thursday, August 26, 2021, 15:28 Series of sparks restarted the controling PC. Back in control BIAS/EE/EZL 48000/-2500/22000

Thursday, August 26, 2021, 15:34 BIAS/EE/EZL 50000/-2500/22000

Thursday, August 26, 2021, 15:48 BIAS/EE/EZL 55000/-2800/24000

Thursday, August 26, 2021, 15:53 Ramping down.

Monday, August 30, 2021, 10:25 turbos off.

 

  895   Monday, August 23, 2021, 10:49 Aaron Schmidt - Fernando Maldonado      Problems/SolutionsRGA replaced with a blind flange

Monday, August 23, 2021, 10:49: Aaron removed the Extorr RGA and install a blind instead.

When the new RGA arrives it will be changed.

  894   Monday, August 23, 2021, 09:55 Fernando Maldonado      Problems/SolutionsRP1 changed back

 Monday, August 23, 2021, 09:53: RP1 was swapped back to our original pump. (see e-log 889)

Derek informed that they test it overnight and performed well, and it's a bit slow but it goes down to 20 mT.

Current is at 36 mTorr and dropping.

  893   Saturday, August 07, 2021, 18:07 Fernando Maldonado      Problems/SolutionsFC0 lasrge oscillation and RMPs offset. Both started today. [Got solved by itself]

Saturday, August 07, 2021, 18:02: As mentions in previous entries, the FC0 current oscillates with no change on ion source parameters.

Hence, I came on-site to see if there was an issue with the hardware. Nothing obvious.

Last night there were some sparks that might have cause some issue.

RPMS are shifted toward negative current reading, similar to what we observed when testing TM4 sourcetray.

To rule out hardware issues I swapped the signals from FC0 to FC6 and visceversa.

When the output of FC0 goes to the FC6 controller the readout makes sense, and this behaves as expected with gas on/off.

When the output of FC6 goes to the FC0 controller there is no readout coming out. This suggest, at least to me, that some damage or error is happening on the DAQ side.

I will reboot the ioc expecting to see something.

Things sort kind of Ok but I don't trust it. FC0 reading makes a bit more sense. RPMS remains with an offset

Saturday, August 07, 2021, 20:31: The FC0 reading increase from 7.54e-11 A to 1.64e-8 A starting at 19:32. Also, the RPMS baseleves are not offset anymore, the -10 rd when using the 1 nA scale is back to 0 (normal)

  892   Thursday, August 05, 2021, 08:49 Fernando Maldonado      Problems/SolutionsCANBUS snooper set up to investigate random optics turnining off

Problem: Some devices turn off unexpectedly and sometimes without any obvious trigger. In the past, the only time this was an issue was during mass scans. Now with the automation of measurements, this is a major problem as it prevents longer parameter scans.

Thursday, August 05, 2021, 08:00: Kevin setup the CANBUS snooper by hooking it up on the magnet card loop port.

This device tracks the network so if any error happen it will be captured.

Thursday, August 05, 2021, 09:39: Test unsuccessful. No device turned off (I should be happy XD)

Thursday, August 05, 2021, 09:40: Will run the test another time

A PC was setup near the old magnet power supply (20210806_150334.jpg ). One of the software run smoothly but the other more useful one fails to connect to the usb adapter.

 


 Friday, August 06, 2021, 14:52: Fixed issue with  the usb adapter. With this, the CANBUS traffic can be store and inspected to catch any error on the communication (Annotation_2021-08-06_144737.png).

Friday, August 06, 2021, 14:53: Loggers are running. 


 Friday, August 13, 2021, 11:07: I forgot to input the feedback  from Kevin:

"33 errors out of 10,300,00 transaction seems statistically insignificant to me. "

From the devices tripped,

"Most of the tripped supplies are located on the front side of the rack, the original test stand controllers"

So maybe the issues could be

"Compatibility issues with the old and new? The newer supplies are all daisy chained, should we upgrade these to the tap boards?

 

Should the old controllers (original test stand appear to be MK supplies) be upgraded (do we have enough)?"

Attachment 1: Annotation_2021-08-06_144737.png
Annotation_2021-08-06_144737.png
Attachment 2: 20210806_150334.jpg
20210806_150334.jpg
  891   Tuesday, August 03, 2021, 11:55 Fernando Maldonado      Problems/SolutionsSwapped emmittance meter voltage cables.

After not being able to get beam through the emittance meter. I diagnosed that the plates was not biased (reason yet unknow).

I swapped the cables from the plates such that it looks like the picture below. With this, I was able to take an emittance scan with the previous parameters.

Varying the optics affect the shape and position of the emittance so I believe this is a real signal.

Keeping this configuration until I finish my measurement.

  890   Friday, July 30, 2021, 16:28 Fernando Maldonado LP-FEBIAD  41790-1044378-5DoneFEBIAD parameter scan - efficiency measurements

Restarting everything after swapping RP1 (see elog 889).


Friday, July 30, 2021, 16:14: IG1 @ 7.02e-7 T.

Friday, July 30, 2021, 16:26: IV4 open. IG1 @ 6.3e-7 T.

Friday, July 30, 2021, 16:27: Auto-ramping TGHT/TBHT to 540/270 A @ 4A/min.

Friday, July 30, 2021, 16:32: Emittance meter power supply found at 500 V. Running a scan does not weep the voltage.

Cycling the PS and running a  scan. Now the voltage is swept.

Friday, July 30, 2021, 17:43: TBHT reached set current. TGHT @ 304 A and ramping up. IG1 @  6.36e-7 T. TIS glowing so I guess it didn't break from early trip.

Friday, July 30, 2021, 18:53: IG1 @ 7 e- 7 T.

Friday, July 30, 2021, 18:53 : Auto-ramping TGHT to 580A @ 4A/min.

Friday, July 30, 2021, 19:10. TGHT reached set current. IG1 @ 7.35e-7 T.

Friday, July 30, 2021, 19:22: BIAS/EZL/EE @ 30/13/1.5 kV. 

Friday, July 30, 2021, 19:25: IG1 @ 7.55e-7 T.

Friday, July 30, 2021, 19:26 :  Auto-ramping TBHT to 280A @ 4A/min.

 Friday, July 30, 2021, 19:29: TBHT reaches set current. IG1 @ 7.72e-7 T.

Friday, July 30, 2021, 21:24: Mass scans with gas on/off shows clear only contribution from gas line. 

Friday, July 30, 2021, 21:25: Anode=200C,Coil=30A. FC0=5.14e-9 A. FC6=9.35e-10 A for 40Ar+

Parameter scans performed on nominal heater current and also with heater at similar power to older measurements.

Leaving some devices that are typically at 0 V to something like 1 to 2 volts, to avoid the red 0 readback as a test.


Saturday, July 31, 2021, 08:13: System stable overnight. TMS:VCB5 was the only device found off.

Mass scans, anode-coil scans. gas line effects.


Sunday, August 01, 2021, 08:42: On-site: Grid is fine. Gas pressure stays at |200kPa| even after several line flushes. Continuing  remotely.

Several parameter scans all at 280A. All of the look remarkably similar, so reproducibility over two day is possible.  Mass scans at three different coil-anode combinations

Emittance scans still not possible @ 1.3e-9 A on FC6, when going to 290 A will try again.

Sunday, August 01, 2021, 22:52: IG1 @ 8.43e-7 T.

Sunday, August 01, 2021, 22:53:  Auto-ramping TBHT to 290A @ 4A/min.

Monday, August 02, 2021, 01:00: IG1 @ 860e-7T. FC1=1.59e-8.


Monday, August 02, 2021, 08:59: IG1 @ 7.44e-7 T.

Mass scans performed. Emittance scans are still not possible with FC6=2.2e-9 A. Parameter scans

 Monday, August 02, 2021, 09:02:  Auto-ramping TBHT to 300 A @ 4A/min.

Emittance scans are still not possible with FC6=3.1e-9 A

 Monday, August 02, 2021, 12:48: IG1 @ 7.6e-7 T.

Monday, August 02, 2021, 12:48:  Auto-ramping TBHT to 305 A @ 2A/min.

Monday, August 02, 2021, 16:40: IG1@ 8.01 e-7 T. 

 Parameter scans. Mass scans performed. Emittance scans are still not possible with FC6=6.21e-9 A. I think there is something wrong with the parameters or with the hardware. To check with Carla on Tuesday.

 Monday, August 02, 2021, 20:44: Ran some tests with the older tune as it provides a broader beam. With this the emittance meter is able to detect the beam center at 85 mm as is common with this tune. However, the beam is not scan in angle, that is the voltage is not swept. Not sure if this has to do with a stuck power supply, or if the voltages of the plate are not biased.

 I will take one more measurement at higher current and go tomorrow to check the emittance scan status.

Monday, August 02, 2021, 20:46:  Auto-ramping TBHT to 310 A @ 1A/min. IG1 @ 8.16e-7 T.

 Parameter scans. Mass scans. 

Monday, August 02, 2021, 23:47: IG1 @ 8.07e-7 T. FC0 = 3..8e-8 A.

Monday, August 02, 2021, 23:52:  Done for the day.


Tuesday, August 03, 2021, 07:34: Things were stable overnight. IG1 @ 7.92e-7 T. 

Parameter scans, and emittance meter troubleshooting.

Grid is fine.

Tuesday, August 03, 2021, 11:55: Emittance scans seem to work now( see e-log 891

Tuesday, August 03, 2021, 12:08: Done on-site. Continuing remotely. 

Emittance scan. Mass scans.

Tuesday, August 03, 2021, 20:21: Ramping TBHT to 315 A @ 1A/min. IG1 @ 8.2e-7 T.

Parameter scan. Mass scans. Emittances scans.

Tuesday, August 03, 2021, 22:55: IG1 @8.07e-6. Done for the day. Will continue tomorrow.


Wednesday, August 04, 2021:  Parameter scan. Mass scans. Emittances scans.

Data analysis on files generated so far. Efficiency as a function of temperature-voltage look similar.

Given that previous cathode heating current did not have emittance, I will go down to measure efficiency.

Wednesday, August 04, 2021, 18:09: Cooling TBHT to 280 A @ -2A/min. 

Thursday, August 05, 2021: Morning troubleshooting CANBUS signal with no luck (this is actually something good)

Mass scans. Parameter scans, and finally emittance scans at lower temperatures.

Thursday, August 05, 2021, 20:58: IG1 @ 7.35e-7 T. 


Friday, August 06, 2021: CANBUS analyzer up-and-running.

Parameter scan. Mass scans. Emittances scans.


Saturday, August 07, 2021, 06:00:  Found all my epics windows closed. Probably a network issue as I cannot connect from any of my pc's. Submitting a ticket.

 Saturday, August 07, 2021, 08:43: Reply from Steve McDonald says there are general network issues and someone is goin on-site to investigate the "network switch stack in the ISAC2 second floor"

Saturday, August 07, 2021, 10:12 : Communications restore after fix.

Saturday, August 07, 2021, 15:06: FC0 reading oscillates a lot and sometimes drop to 0. Mass scan shows almost no peaks without gas. With gas, the FC0  behaves the sames even thought 40Ar+ signal is 1e-8A and responds to the gas open/close.

Moreover, the RPM0s have an offset current. RPM0A is not showing beam.

I will turn the HV off in case there is weird dark current going on. 

Saturday, August 07, 2021, 17:29 : On-site

ISAC test stand PC lost connection to epics due to the same issue. Initiating striptools.

Nothing visible wrong on service cap nor around the ISAC test stand, however, FC0 still oscillates a lot.

I will change the signal cables to see if one controller can read from the other faraday cup.

 Things look better now (see entry 893)

Finished mass scans

Sunday, August 08, 2021, 00:35: Ramping TBHT to 300 A @ 4 A/min. IG1 @ 6.71e-7 T. 


Sunday, August 08, 2021:  Parameter scans, mass scans, emittance scans performed.

Sunday, August 08, 2021, 23:55: Checking other species given that  with TBHT=310 A I can see m=90, which I think it might be Ta++


Monday, August 09, 2021: TBHT increased to 315 A

Parameter scans, mass scans, and emittance scans performed.

Investigating the following species: O+, (H2O)+, Ar++, (N2)+/CO+, (O2)+,Ta++,(TaO)++ on masses 16,18,20,28,32,90,98, respectively.

Both the atomic, and molecular oxygen follow different tendencies wrt other species.


Tuesday, August 10, 2021, 09:57: TBHT @ 320 A. IG1 @ 6.53e-7T. 

Tuesday, August 10, 2021, 10:01: Increasing anode limit current to 200mA. All previous tests had 150 mA and the maximum current recorded was ~110mA. 

Tuesday, August 10, 2021, 11:42: Grid is fine (confirmed by Marla) 

Tuesday, August 10, 2021: Mass 60 observed, it might be (SiO2)+ coming from the coil jacket. The parameter scan shows that the ion current is only dependent on voltage. 


Wednesday, August 11, 2021. Mass scan, and parameter scan. For the first time I am measuring only FC0 with and without gas. I'm gonna investigate the higher peaks individually, likely they are H2O,O2,O,H2, and Ar


Thursday, August 12, 2021: All day measuring different ion currents with and without gas (H2,N,O,OH,H2O,N2/CO,O2).


Friday, August 13, 2021, 09:03: Currently measuring FCO with gas. 

 Friday, August 13, 2021, 10:42: On-site. Grid is fine

Friday, August 13, 2021, 19:50:Scans completed for different species, results seem consistent but required more in-depth. FC0 scans shows higher values towards high anode voltage and high coil current but not all species shows this behavior.

Friday, August 13, 2021, 19:51: Ramping tbht to 330 @ 1 A/min. 

Friday, August 13, 2021, 20:29L IG1@8.25e-7T. 


Saturday, August 14, 2021, 22:28: Parameter scans, mass scans. Some emittance scans unsuccessful.

Anode leakage current seems to creep a bit overnight. This could be an indication of a failure onset but I'll have to see. I won't increase the current remotely until being on-site


Sunday, August 15, 2021, 10:10: Anode leakage current has increased 10 mA overnight. 

Sunday, August 15, 2021, 20:43: Emittance scans for multiple anode/coil combinations. Visually there are differences on the geometrical emittance, not so much on the 90% intensity emittance. Requires proper  emittance  analysis.


Monday, August 16, 2021, 18:58: Data analysis and short summary. Systematic emittance measurements.

Request to add more PVs to control emittance and mass scans from jupyter notebook 


Tuesday, August 17, 2021, 10:22: On site. Grid is fine. Re-initianing epics as my pc reboot it.

Tuesday, August 17, 2021, 10:23: TBHT to 335A @ 1A/min. Anode leakage current =150 mA. IG1=6.51e-7T. Increase anode current limit to 250 mA.

Tuesday, August 17, 2021, 10:29: The grid is as bright as the cathode. This is the first time the grid shines this bright. 

Tuesday, August 17, 2021, 10:53: The grid looks normal at anode=200V. By making an anode sweep I was able to observe that at around 300 V there is an onset on how bright the anode get. Passing this voltage the grid start to shine and gets a maximum brightness when reaching 500V.

This seems to suggest that the power deposited on the grid is enough to cause substantial heating if it makes it as bright as the cathode. The maximum power into the anode body (at this cathode heating current (335A))  is 500V* 200mA=100W (just like a lightbulb)

Tuesday, August 17, 2021, 12:03: Done on-site. Will continue remotely. 

Tuesday, August 17, 2021, 20:19: Anode is drawing more current. During Ar+ scan, the maximum anode current registered was ~200 mA. Now is ~250 mA 

Schottky plot shows a tiny upwards kick.

Tuesday, August 17, 2021, 22:16: Once again, at the end of the scan the current increased. This time to 320 mA

Tuesday, August 17, 2021, 22:18: I think the grid will melt tonight  with anode/coil @ 200V/30A. 


Wednesday, August 18, 2021: Well, well, well. Grid didn't melt but the  anode leakage current has increased again. At some point the anode got current limited to 350 mA and from 490 V it drop to 470V.

Wednesday, August 18, 2021, 16:57: Increasing the anode limit current to 400 A.

Wednesday, August 18, 2021, 18:01: During the scan on FC0, the anode current went up to 400 mA so I increased to 500 mA, but I had to increase to 600 mA but it was still getting current limited. Scan aborted

Maybe now I am melting the grid 

I will run an FC0 scan with gas on while I'll go on-site to check the grid and the "anomalous" ionization..

Running a mass scan while I go on-site. Anode=200. Coil=90 A.

Wednesday, August 18, 2021, 19:42: Grid is melted. From the look of it half of the visible part collapsed into a blob while the other is gone (allowing to see the far backside of the target oven.

With this knowledge I can proceed with more aggressive tests in order to test the limit if the "anomalous" regime.

Wednesday, August 18, 2021, 23:24: After a mass scan with 0 V to check surfaces ionizes species I noticed there is a signal on mass ~ 137.5 which I am not sure what it is.

It might be Ba or a molecule but is coming from the transfer line as sweeping the voltage between 0 and 2 V changes the response but above this the signal is gone and reappears with 80 V.


Thursday, August 19, 2021, 08:08: mass ~137.5 disappeared. If I increased the anode voltage to 400 V or so some appears but quickly drops.

 Thursday, August 19, 2021, 11:35: Increased anode current limit to 800 mA.

Thursday, August 19, 2021, 14:08: Scan didn't cause an increased on leakage current. Maximum registered was around 200 mA. However, the contour plot looks different to the case when the grid was complete.

Thursday, August 19, 2021, 23:36: Finishing some scans at the current settings.

Thursday, August 19, 2021, 23:36: TBHT to 280A @ -1A/min. Tomorrow I will focused on temperature scans without caring much on emittance o mass composition. 


Friday, August 20, 2021, 11:28: Scans done for,280,285. Currently running 290 A.

The coil current dependence qualitatively follows the one from ISOLDE, in which a series of minimum and maxima occur and also vary a bit with voltage.

Friday, August 20, 2021, 13:34: Accidentally set TBHT to 226 A directly from 295 A. 

Friday, August 20, 2021, 13:36: Heating TBHT to 300 A @ 4A/min. 

Friday, August 20, 2021, 14:13: TBHT is at 295 A to check things are still the same. 

Friday, August 20, 2021, 23:46: TBHT @ 310 A. 


Saturday, August 21, 2021, 06:20: Scan on-going for TBHT 315 A. 

Saturday, August 21, 2021, 13:25: TBHT to 335 A. 

Saturday, August 21, 2021, 15:02: TBHT to 340 A. 

Saturday, August 21, 2021, 18:11: The voltage got current limited during the scan for 345 A. When setting the voltage to 0V, the anode seems to be shorted. 

Saturday, August 21, 2021, 22:46: Ramping down TGHT/TBHT to 0 (@-1A/min) but the short is still present. Currently  @ TGHT/TBHT 454/162 A. 


Sunday, August 22, 2021, 13:29: This morning the heaters reach 0 A but the anode remain current limited. I will proceed to turn off the TS to check tomorrow morning the ion source. 

Sunday, August 22, 2021, 13:31: IV4 closed.

 Sunday, August 22, 2021, 13:36: Sources off.

Sunday, August 22, 2021, 13:38: IG1 off

 Sunday, August 22, 2021, 13:38: Turbos off.


Monday, August 23, 2021, 07:19: Venting 

Monday, August 23, 2021, 08:30: Confirmed a short between target/cathode to anode/heatshield

Monday, August 23, 2021, 11:29: Confirmed that the anode power supply still works :) 

ELOG V2.9.2-2455