2776
|
Friday, February 21, 2025, 09:18 |
David Wang | Cooling | Standard Operation | | | HALCW pump ITC:MP1 and MP2 phase current draw measurement. | HALCW pump ITC:MP1 and MP2 phase current
draw measurement result: water supplied to
both station. MP1: Black 17.0A, blue 16.9A, |
|
2777
|
Monday, February 24, 2025, 11:15 |
David Wang | Cooling | Maintenance | | | ITW/ITE water system manual valves water small leak inspection and repairing. | ITW/ITE water system manual valves
water small leak inspection and repairing
job is done. Small water drippings have been |
|
2778
|
Tuesday, February 25, 2025, 09:42 |
Travis Cave | Spent Target Vault | Standard Operation | | SHC Active Trash | SHC Active Trash | Another pail of active trash was
move to the spent target vault from the south
hot cell. 800uSv/hr, place in spot 7A see |
|
2779
|
Wednesday, February 26, 2025, 09:59 |
David Wang | South Hot-Cell | Standard Operation | | | SHC Field measurement from TH | After waste transfer, I did a SHC field
measurement from TH through top flange opening.
The general field around manipulator maintenance |
|
2780
|
Monday, March 03, 2025, 10:53 |
David Wang | ITE/ITW | Maintenance | | | ITH:MP1 has been replaced. |
No |
|
2781
|
Monday, March 03, 2025, 15:33 |
David Wang | Cooling | Maintenance | | | HALCW resin can loop two filters have been replaced. | HALCW resin can loop two filters have been
replaced. no water leak on after job check.
|
|
2782
|
Friday, March 07, 2025, 09:07 |
David Wang | ITW | Standard Operation | | | ITW water signals interlock annual check is done. | Chole and I finished ITW water signals
interlock. No issue. |
|
2783
|
Friday, March 07, 2025, 09:16 |
David Wang | Cooling | Maintenance | | | Service of 28 female Parker 1/4 quick connectors in ITW and ITE | Service of Parker 1/4 quick connectors
in ITW and ITE have been done. all
28 female connectors were serviced. o- rings |
|
2784
|
Tuesday, March 11, 2025, 08:44 |
David Wang | ITW | Standard Operation | | | ITW:TP3,TP4, TP1S TP4S have been started since March 06th. | To prevent TP bearings seize during shut
down, ITW:TP3,TP4, TP1S TP4S have been started
since March 06th. They work fine. The |
|
2785
|
Tuesday, March 18, 2025, 13:54 |
David Wang | ITE | Standard Operation | | | ITE water signals interlock annual check | ITE water signals interlock annual check
is done today. all interlocks work . No issue.
|
|
2786
|
Thursday, March 20, 2025, 13:10 |
David Wang | Conditioning Station | Standard Operation | | | TCS water system filters annual replacement has been done. | TCS water system filters annual replacement
has been done. Plant group Dan Tower finished
the job and updated the inspection tags . |
|
2787
|
Tuesday, April 01, 2025, 09:47 |
Frank Song | North Hot-Cell | Repair | | | Two NHC light bulbs replacement | 2 broken lights of NHC were replaced in
Target Hall. see pics attached. |
    |
2788
|
Friday, April 04, 2025, 09:35 |
David Wang | Crane | Development | | | spent target pail and its lifting jigs load test | Adam and I did spent target pail
and its lifting jigs load test this morning.
The load for full pail test is 263 lbs and |
|
2789
|
Friday, April 11, 2025, 13:34 |
chad fisher | North Hot-Cell | Repair | | | remote end 9342 installed | On March 27 remote end 9342 was installed
on the west position (right hand as viewed
by operator) and arm 9764 removed and moved |
|
2790
|
Friday, April 11, 2025, 13:46 |
chad fisher | North Hot-Cell | Repair | | | Remote end 9**4 repair | Tong cable on remote arm 9**4 has be relocated
onto its pulleys and tong opening adjusted
at the tong cable drum by changing the position |
|
2793
|
Thursday, April 24, 2025, 11:33 |
Travis Cave | Conditioning Station | Standard Operation | | UC#48 | Module move | TM4 with UC48 went on a long trip
from the north hot cell to the conditioning
station. |
|
2795
|
Thursday, April 24, 2025, 13:42 |
David Wang | Conditioning Station | Standard Operation | | | Refilled TCS:TK2 from 11" to 28.8 " | Refilled TCS:TK2 from 11" to 28.8
". |
|
2796
|
Friday, April 25, 2025, 14:30 |
Adam Newsome | Facilities | Standard Operation | | | Safety Walkaround complete - ISAC Hot Cells, Target Hall | A safety walkaround was completed for the
ISAC Hot Cells and Target Hall Areas.
The resulting spreadsheet can be |
|
2798
|
Friday, May 02, 2025, 10:16 |
Aaron Tam | North Hot-Cell | Maintenance | | | NHC Window Oil Fill | Findings
During April 2025 safety
walk ID: 2796 , it was noted that the |
12x |
2799
|
Monday, May 05, 2025, 09:18 |
chad fisher | North Hot-Cell | Maintenance | | | Manipulator Remote End Replacement 9352 with 9764 | Remote end 9352 replaced with end 9764
due to signs of an issue with the tong cable
(tong opening excessively large and slack |
|