Logbooks Lab Maintenance Evaporator_1 Evaporator_2 Laser cutter Target Production Test-Stand RH-ISAC RH-Cyclotron RH-Meson Hall RH-Beamlines RH-ARIEL
  Lab Maintenance, Page 2 of 4  Not logged in ELOG logo
ID Date Authordown Status Test Subject
  34   Wednesday, August 05, 2020, 19:50 Darwin Ortiz RosalesFixed1Hot Lab Glove Box Regeneration

Wednesday, August 05, 2020, 19:34

On Friday July 31 a regeneration of the glovebox was started.

Initial 02 = 130 ppm

Initial H20= 1.9 ppm

The Argon gas level was 1200 psi

The regeneration was finished on August 01, 2020. 

The 02 level (not accurate as stated in the manual) was p 137 ppm.

The H20 level was 8.9 ppm and not considered accurate as the system needs time to reach equilibrium.

 

The final 02 level was 7.0 ppm and recorded on August 05, 2020.  The final moisture levels were recorded to be 1.9 ppm.

The regeneration was successful and it was concluded that the catalyst is active enough so that it does not need to be replaced.


 Thursday, August 06, 2020, 15:47

02 = 6.75 ppm

H20 = 1.9 ppm

 

 

  47   Tuesday, June 20, 2023, 15:11 Darwin Ortiz RosalesFixed Inspection ISAC 1 B1 L06 Glovebox

On Monday June 19th, the Glove box was inspected.  Gas lines, solenoids, pump, argon usage, state of gloves and gas levels were checked. 

The only note is that we have one pair of spare gloves for the glove box and we don't have a spare for the Evap1 glove box.  We will try to order spare for the Evap1 glove box.

  49   Tuesday, August 01, 2023, 12:31 Darwin Ortiz Rosales  Evap1 and Evap2 Inspection and Maintenance

Evap1:  Cleaned and checked seals.  Oil level could not be clearly determined, but are consulting with pump group to check.

Evap2: Cleaned and checked seals. 

  52   Friday, January 19, 2024, 10:18 Darwin Ortiz RosalesFixed Inspection of Glovebox inside B1 L06 (hotlab)

Friday, January 19, 2024, 10:10

This is a belated entry.  The inspection was performed on December 19, 2023.  A leak on one of the lines from the regulator (regeneration gas) was fixed. No other issues were found. 

All lines, pump, blower, were found in working condition. 

A regeneration can proceed.

 

  53   Friday, January 19, 2024, 10:20 Darwin Ortiz RosalesFixed Glovebox regeneration (B1 L06, Hotlab)

Friday, January 19, 2024, 10:19

This is a belated entry.  The regeneration was performed successfully on December 20th, 2023. 

  55   Tuesday, March 12, 2024, 15:21 Darwin Ortiz RosalesFixed Glovebox regeneration and O2 sensor replacement(B1 L06, Hotlab)

Tuesday, March 12, 2024, 15:21

Hotlab ISAC1 B1

I performed a regeneration of the glovebox catalyst.  I also swapped the O2 sensor as the old one had outlived its useful life.  The glovebox will be reestablishing equilibrium for a day or two.  Please do not panic if you see high moisture or O2 values, all is good.   Thanks,

 

 

Darwin

  58   Thursday, June 20, 2024, 13:33 Darwin Ortiz RosalesFixed Glovebox inspection ISAC1 B1 L06

 Thursday, June 20, 2024, 13:28

All lines, pump, blower, were found in working condition. From a previous issue with corrosion of lines connecting pumps, it is recommended that we check the ability of the pump to achieve full vacuum during inspections.  Currently full vacuum was observed while checking.  

The nipple connecting the argon gas tank to the regulator needs replacing.  Aaron will order it.  

  60   Thursday, August 01, 2024, 15:01 Darwin Ortiz Rosales  EVAP1 and EVAP2 Inspection and Maintenance

Thursday, August 01, 2024, 14:56

EVAP1:  Checked seal and no visible deterioration was observed.  Oil level in roughing pump was good.  Circulated argon to observe functionality of the gloves and to check appropriate gas flow. 

EVAP2:  Visually inspected the connections at the back of the evaporator.  A loose connection had been observed on the previous day but fixed.  Roughing pump running well and system operational.  The door seal could not be checked but it is working properly as evidenced by the fact that the evaporator was in use. No major maintenance required at this moment.

  61   Thursday, August 01, 2024, 15:03 Darwin Ortiz Rosales   

Ultrasonicator in Cold Lab:  The ultrasonicator cooling lines and their operation was checked.  The functionality of the probe and operation software was checked.  Visual inspection of probes and water receptacle showed good operational condition. 

  62   Tuesday, October 15, 2024, 09:21 Darwin Ortiz RosalesFixed Hotlab glovebox catalyst regeneration

Tuesday, October 15, 2024, 09:22

The glovebox catalyst was regenerated.  No issues.  Removed TCE and PVB from inside the glovebox.  These were vestiges from the previous UCx production process.

  66   Tuesday, February 18, 2025, 12:11 Darwin Ortiz RosalesCompleted1Evap1 Gloves swap

Tuesday, February 18, 2025, 12:06

On Friday February 15th, Aaron and I changed the evaporator 1 gloves. 

1. Each glove was rolled up and taped with duct tape into a little ball (to expel air).  T

2, The clamp ring and the o-ring was loosened up and placed to the side after swiping.

3. A large, clear plastic bag was taped around the each glove before taking it off.  The area around the port was swiped and no counts were found.  

4. The old gloves were placed inside the plastic bag and disposed into the contaminated waste yellow drum inside.

5. Proceeded to install new glove. 

6.  Have other spares available in the  cold lab.

  68   Thursday, May 29, 2025, 13:41 Darwin Ortiz RosalesFixed Evaporator 2 TP switch

Thursday, May 29, 2025, 09:34

Yesterday Edi and Derek from Vacuum group installed TP.  They recommended two things:

1) Clean the BV1 as it has some oil from previous roughing pump. 

2) Consider using inert gas in TP purge line.  This helps protect the bearings from particulates being exhausted through the pump.

 

The old TP showed many signs of particulates and condensed material on the blades and inside surfaces.

  40   Thursday, January 20, 2022, 13:38 Carla Babcock  Testing of spare FUG bias supply

Tomislav and John Chow tested the spare bias supply located in the rack of the electrical services room. This is a FUG HCN 1400 M-60000, serial 11590-01-01, PO TR131986 but when it was installed online we found it could not go above about 40kV. It was replaced but not tested until now. Tomislav says:

"We started testing the FuG this morning, in manual mode it is possible to reach 60 kV, 59.75 according to the display and with the load we have 1.6 mA. From the DC HV point of view, at least in manual mode no problem.

When we looked at the HV through a 1000:1 voltage divider in the oscilloscope there is a situation, the coupling in graphs 4 and 5, attached, is AC, and it was taken at 55 kV. The 200 mV scale represents 200 V because of the divider. There is a strong noise of 200 Vpp at 55 kV, it can be interpreted as ripple of 0.36%, we usually ask in FuGs 10-5 or 0.001%. Also there are random peaks of 1 V in the divider (1000V in the output) that indicate a possible failure of the PWM circuit that generates the high voltage.

Because of issues like these Friedhelm replaced the old ITW power supply, these instabilities caused problems in the experiments, so I am not sure if it is necessary to continue testing this PS. We can only do a remote test that I do not expect to give different results from what we have now, maybe we will find an issue and it does not go beyond 40 kV, and we can check long term stability, the DC value should remain very constant for at least 8 hrs."

  10   Thursday, September 08, 2011, 15:41 Anders MjosFixed1Evaporator#1 glovebox repairing

John Wong wrote:

The evaporator#1 glovebox is leaking from the gloves, around the ports, and the base (possible more places).  It is evident that there were holes on the gloves.  When the glovebox is purged with Ar gas, one can feel that the gas is blown out from the base.  

Solutions:

New gloves are ordered from RENCO Co. (PO#TR189708). 

New seals & glove port rings have been implemented. 

More need to be done...  

 

 

 See Evaporator_1 log entry

  11   Thursday, February 23, 2012, 13:38 Anders MjosFixed Water leak in chemistry / cold lab

 Please see attached file for notes on the water leak from the cold lab fume hood Tuesday Feb 21.

Attachment 1: Notes_on_water_leak_ISAC_I.docx
  13   Friday, March 15, 2013, 13:55 Anders Mjos  Non active water off for a short time (10 - 15 min)

ISAC operations called to check that equipment in the labs were OK for the non active water to be off for a short time. I gave the OK after having checked that both evaporators are off. The system will be bled for air.

  30   Wednesday, April 08, 2020, 11:40 Anders Mjos  Lab check in

Checked in on the labs and other equipment yesterday. Everything looks ok, including the glove box Ar supply. Recorded O2 and H2O values in the log book.

  31   Friday, April 24, 2020, 16:27 Anders Mjos  Lab check in

Anders Mjos wrote:

Checked in on the labs and other equipment yesterday. Everything looks ok, including the glove box Ar supply. Recorded O2 and H2O values in the log book.

 Checked in on labs again on Wednesday April 22nd. See attached for glove box details

Attachment 1: 20200422_154045506_iOS.jpg
20200422_154045506_iOS.jpg
  15   Thursday, March 16, 2017, 09:32 Aaron SchmidtFixed D.H.W water pipe replacement
Fri 03/03/2017 17:00 - A water leak was noticed on the D.H.W line. Hot water to the Cold lab was shut down. Wed 15/03/17 11:00 – 14:45. The insulation was removed. A pin hole leak was found in the D.H.W waterline. Soldering/replacement of new copper pipe was required. The smoke alarm in the Cold Lab was disabled during the work period. The corroded copper pipe section was replaced. An insulating tape was added where the pipe rests on another metal joint; however the pipe is not fully insulated yet. The Main Control Room was called for the smoke alarm to be re-activated. Noteworthy comments: -Plastic sheets were placed around the work area to protect the lab from dust/water/solder. -The hot water quality is still poor coming from the pipe. The water needs to be run continuously for a few minutes before it develops clarity. Hot water is used to effectively activate the Oxide remover when cleaning copper parts in the lab. Just note to make sure the any parts cleaned in the lab are adequately rinsed with D.I water when cleaning. -The pipe removed was quite corroded. Likely other pipe in the area is in similar condition. Something to be mindful of. -The water coming through the emergency eyewash station & shower is still a near scalding 50-55 degrees C. This still requires attention. -Some of the insulation on a nearby pipe and above the D.H.W pipe was burned during this work but is otherwise fine. The attachment contains the same information but with included pictures.
Attachment 1: DHW_pipe_replacement.docx
  16   Wednesday, April 05, 2017, 08:22 Aaron SchmidtFixed D.H.W.R Leak
When: 04/04/17 Between 09:00 & 11:30 Where: ISAC 1 – Cold Lab Who: Ron Murray & Aaron Schmidt A pin hole leak was found in the previously repaired D.H.W.R waterline. Soldering of new copper pipe was done. The fire alarm 051-046 in the ISAC Cold Lab was disabled. We removed a copper pipe section out into the hallway and stopped around 6 ft past the door to the ISAC cold lab. We did find a second smaller leak outside past the door. Background: -Fri 03/03/2017 15:00 - The emergency shower was tested. The water was too dirty & hot for proper use and a leak was detected. Water @ 55 degrees C. -Fri 03/03/2017 17:00 - A water leak was noticed on the D.H.W.R line. Hot water to the Cold lab was shut down. -15/03/17 Between 11:00 & 14:45 – The corroded copper pipe section was replaced, however a small leak turned up further up the copper pipe the next day. Summary: The corroded copper pipe section was replaced beyond the ISAC Cold lab door; however the pipe is not fully insulated yet. The Main Control Room was called for the smoke alarm to be re-activated. Noteworthy comments: -The new pipe may require insulation. -The water quality was poor coming from the pipe. The water was run continuously for around 20 minutes before it developed clarity. -There were other pieces of pipe wrapped in amongst the copper pipe. One piece appeared to be steel, but was quite corroded -Some of the insulation was quite rotted and crumbled to dust during handling. In the event of any other leak repairs, a respirator is highly recommended. -The pipe removed was quite corroded both in the ID and OD. Likely other pipe in the area is in similar condition. Something to be mindful of as further leaks may occur over time.
ELOG V2.9.2-2455