  67   Friday, January 11, 2013, 15:48 Isaac EarleStandard OperationTarget 1TargetBL1A Tunnel Accessed

 The BL1A tunnel was accessed to drain and sample T2 cooling package water.  A puddle of water was noticed in the South TNF area around the drain by the boot-box.  No water was found in the BL1A tunnel.  Photos attached.

  66   Tuesday, January 08, 2013, 10:52 Isaac EarleMaintenanceTarget 2TargetT2-MK1 Target Maintenance

- T2-MK1 target transported from storage pit to hot cell
- Proximity sensor removed
- Target lift "T" removed, painted, relabeled
- Replaced flange o-rings: Plug (#202), Feed through port 1 (#222), Feed through port 2 (#222), Feed through port 3 (#213), Water supply tubes 1 and 2 (#208)
- Replaced all nylon Swagelok ferrules
- Leak checked water tubes: OK
- All wiring above vacuum flange replaced, secured, inspected  (D. Cameron)
- Damaged lower MS connectors replaced  (D. Cameron)
- Discovered motor wire insulation degrading  (D. Cameron)
- Motor replaced and rewired
- Motor, position micro switches, and profile monitor micro switches tested: ALL OK
- Tested profile monitor actuation: Smooth (IN: start motion @ 5psi, fully actuated @ 20psi)
- Target lift "T" installed
- Feed through port cap #2 replaced with TBP0936 (old cap was makeshift part using weird gunk sealant)
- Upper and lower parts of target photographed
- Target ladder moved to position 0
- Target ready for use.  Will be transferred to storage pit hole #4

* Approximately 50cpm found on 44-2 monitor from wet wipe used to clean blue flanges surrounding hot cell entrance on HC roof
 

  65   Tuesday, January 08, 2013, 09:27 Isaac EarleStandard OperationTarget 2TargetBL1A Air Amplifier turned off for duration of shutdown.

 The BL1A air amplifier has been shut down by closing the air supply valve on the device. The air amplifier supplies high pressure air (110psi) to the following devices: M9BB, M20BB, T1 Profile Monitor, T2 Profile Monitor, T2 Collimator, Septum Polarity Switch

  64   Monday, December 10, 2012, 15:42 Isaac EarleMaintenanceTarget 1TargetT1-MK2 Target Maintenance

- T1-MK2 target moved from storage pit to hot cell
- Removed unused proximity sensor and associated wiring (stored in tool-port boot box cabinet)
- Tested profile monitor actuation: seems stiff, but moves ok;  start travel @ 30psi, fully in position @ 50psi
- Replaced vacuum flange o-rings: Plug (#202), Feed-through port 1 (#222), Water supply tubes 1 and 2 (#208)
- Replaced all nylon ferrules for water supply tubes
- Leak checked water supply tubes: leak tight
- Replaced rusty nuts on profile monitor lift plate
- Profile monitor limit switch wiring replaced (D. Cameron)
- Heat shrink applied over motor wires (D. Cameron)
- Position micro-switch connectors replaced (D. Cameron)
- All wiring wrapped with protective coil and secured with PEEK zap-straps (D. Cameron)
- All limit and position switches tested: ok
- Profile monitor bellows straightened (noticed rotation of base seems stiff)
- T1-MK2 target moved to storage pit location #3
- T2-MK1 target moved from storage pit to hot cell for re-wiring

 

  63   Thursday, November 22, 2012, 17:22 Isaac EarleStandard OperationTarget 1Active SumpRH Lab Active Sump Released

 On Wednesday November 21 at approximately 9am the level of the Remote Handling active sump was inspected and found to be at approximately the 7000L level.  The high level alarm sounds at approximately 5800L.  The high level alarm had been silenced by somebody, and RH staff had not been notified.  It is unknown when the high level alarm was reached.  The total sump volume is 7200L (which if exceeded will cause active water to spill on the lab floor).  The sump was previously inspected about 3 weeks prior, and the level was observed to be well below the high level sensor.  The recent increase in volume was from the RCR lab in the MHESA basement.

The sump contents were sampled and approved for release by RPG.  Sump contents were released on November 22nd using the procedure written in Document #64834.

A sign was put up next to the high level alarm silence button indicating that RH staff must be contacted if the alarm is silenced.

The high level sensor was tested and found to be working properly.

  62   Tuesday, November 13, 2012, 16:26 Isaac EarleRepairTarget 1TargetManipulator Repair Complete

 Repair of the west side manipulator in the west hot cell was completed today.  Part of the repair was done by entering the hot cell using double tank suits and supplied air.  The repair was then completed on the master side of the manipulator.  The manipulator is now operating smoothly.

Two sales representatives from Central Research Labs visited TRIUMF today as they were already in Vancouver on other business.  I showed them the RH Lab manipulators and received  hourly and daily service charge estimates if repair of the east hot cell (junk cell) manipulators requires one of their experts to come in.

  61   Wednesday, October 24, 2012, 17:38 Isaac EarleRepairTarget 2TargetT1 & T2 Target Ladder Control System Status

 During the recent shutdown for the T2/M9 joint repair Graham Waters replaced the corrupted application code on the controller RAM disk.  The T1 target position control is now functioning properly.  T2 target position control is still not operational due to an electronics problem within the motor driver.   The T2 ladder position may still be moved using the portable control box.  The T2 target ladder was moved to position 3 (10cm Be) today in preparation for the upcoming running period.

  60   Wednesday, October 24, 2012, 17:34 Isaac EarleRepairTarget 1TargetT1-MK2 Target Repair Complete

The target ladder was detached, old delta seals removed, sealing surfaces cleaned using scotchbrite pad and a dremel tool, and delta seals were installed on the lower face of the upper slide plate.  The target was leak checked and found to have no significant leaks (no response from 2s helium spray at previous leak location on upper slide plate).

The profile and protect monitor electronics were checked by Bill Rawnsley and appear to be functioning normally.

The T1-MK2 target is now ready for use in the beam line.

  59   Friday, September 28, 2012, 15:19 Isaac EarleRepairTarget 1TargetT1-MK2 Delta Seal Leak

  After removal of the leaky target cassette at position 3, plugs were installed on the target ladder and a leak check was performed.  With the target pumped down to approximately 10 mTorr, and helium detector gauge baseline of 9 on the 10X scale, a response of up to 25 on the 500X scale was observed when leak checking the right side delta seal on the lower face of the upper slide plate using a standard 1s spray of helium at 3 psi.  The flange screws were tightened and the leak check repeated.  Under the same conditions there was a response of up to 60 on the 100X scale - There was still a leak, but not as severe as before.  The screws were tightened further, and the target leak checked again, with no change.

At time of installation a response of  up to 10 on the 100X scale was found at the same location.  This target was found to be water leak tight and was used in  the beam line for ~4 months.  It is possible that the seal is still water leak tight.

The seal must be replaced or a static water test performed to show that the target is water leak tight.  Seal replacement will take approximately 2-3 days. 

  58   Tuesday, September 25, 2012, 16:31 Isaac EarleRepairTarget 1TargetT1/T2 Controls

 - The target control software was modified to reference the correct pot. look-up table for the target at T1 (T1-MK1)
 - The target position buttons on the T1 & T2 panels were not working properly and Graham Waters was contacted to investigate
 - Graham power cycled the microprocessor and the TG1 crate which seemed to make things worse (the control software would not even boot up)
 - Graham was able to diagnose the problem remotely, and found a loose cable which was causing it not to boot
 - The target position issue will not be looked into further until a longer maintenance period or the 2013 shutdown
 - Target position can be controlled manually using a portable control box
 - Using the control box, the T1 ladder was moved to position zero to allow use of the profile monitor;  The ladder was then moved back to position 3
 

  57   Thursday, September 13, 2012, 18:09 Isaac EarleMaintenanceTarget 1CoolingSeptember Shutdown T1 & T2 MRO

 The following tasks were performed during the 2012 September Shutdown:

- Both targets moved to position 0 in preparation for testing of profile monitors (portable ladder control box was used for controlling ladder motors)
- T2 monitor OK; T1 monitor would not hit 'IN' limit
- The T2 branch of the amplified air system was closed, now the T1 monitor hits the 'IN' limit properly  (conclusion: a known leak in T2 section of amplified air is causing a drop in pressure of the system which prevents the T1 profile monitor from actuating properly)

- Both cooling packages were inspected and photographed (nothing abnormal observed)
- Both cooling packages drained, and water samples delivered to RPG
- Expansion tank level sensors tested at both packages: All OK
- All Hansen quick connect o-rings replaced at T1 package
- 90 micron filter on demin line replaced at T1 (caused ~0.2gpm increase of Q2 flow)
- Both packages refilled and restarted (operating normally)
- Q2 flow on both packages adjusted to ~1.45gpm

- The cause of the amplified air leak was discovered to be a cracked air dryer located in the BL1A service tunnel (photo attached)
- The air dryer was replaced which stopped the leak, resulting in a significant decrease in air amplifier cycle period and an increase in air amplifier output pressure from ~110 to 120psi

- Movement of the T1 ladder caused a spike in beam line vacuum;  After further testing it was concluded that the T1 target was leaking water
- T1-MK2 target was transferred from the beam line to the hot cell; T1-MK1 target was transferred from the storage pit to the beam line
- T1-MK1 profile and protect monitor electronics checked by Bill Rawnsley: Both OK
- Initially a leak was suspected at T1, but it was later discovered that the volume was just pumping down slowly due to water in the beam line from the T1-MK2 leak
- T1 profile monitor was not actuating properly;  It was found to be caused by a short to ground on one of the profile monitor limit switch wires.  The faulty wire was replaced by Probes Group
- T1 and T2 profile monitors tested.  Both actuating properly.
- New target ladder information sheet delivered to ops

- The leak in T1-MK2 was found to be coming from the center of the beam spot on the entry side of the position 3 target (photo attached, but not great quality).  This is a 12mm Be target, and has been running in beam position since initial start-up this spring.

  56   Friday, September 07, 2012, 16:39 Isaac EarleRepairTarget 1TargetRH Lab Crane Repaired

 The "west" button on the crane pendant was broken, and the crane would occasionally continue moving west when the button was released.  The button was replaced by a Gordon Crane technician, who also did a crane inspection.  The hoist in the target flask is also due for an inspection, but it was not possible to do it this visit.  Neil Wong will try to have it done next time a crane technician is in.

  55   Friday, September 07, 2012, 16:35 Isaac EarleRepairTarget 2TargetT2-MK1 Target Repair Completed

 - Profile monitor wiring harness checked by Bill Rawnsley using resistor pack --> OK

 - New profile monitor (0.005" gold coated molybdenum wires) installed & blip tested --> OK

 - Potentiometer checked --> OK

 - Target position and profile monitor in/out micro-switches checked --> All OK

 - Target leak checked:  very small response at top and base of left side bellows (when facing target ladder), otherwise leak tight
         (Meter on 10X scale, Baseline: 6.  Meter reached 9 at top of bellows, 11 at bottom of bellows with 1s He application.  Both recovered after ~30s)

 - Straightened twisted bellows on both sides which was causing "clicking" noises during target ladder travel
      (Note: water supply tube nylon swagelok ferrules should be replaced at next opportunity, currently no spare parts)

 - Target leak checked again - No change due to bellows adjustment

 - Static water pressure test performed, as target is likely water leak tight: Target filled with water, pressurized with air to 80psi, then valved off and left overnight.  No visible water leak from bellows.  Pressure dropped 11psi over 15 hours.  Test was repeated, but the line valved off before the target to establish a baseline.    The baseline test dropped 15psi over 16 hours.  The increased leak is likely due to the additional valve added to the system, or different amounts of air in the system compared to total system volume.  Baseline test shows that the pressure drop seen in first test appears to be due to a small leak in the test equipment, or expansion over time of the supply water hose.  Concluded that target is water leak tight.  Additionally, target assemblies have been installed in the beam line in the past with significantly higher helium leak rates, and no observed water leak, with no problems.  

 - All water pumped from target using liquid nitrogen trap

 - Target ladder moved to position zero

 - Target moved from hot cell to storage pit location #4.  Ready for use in beam line.

  54   Wednesday, August 08, 2012, 14:40 Isaac EarleRepairTarget 1TargetT1-MK1 Target Repair Complete

- Re-wired profile monitor was received from Probes Group and installed on the target

- Protect and profile monitors were 'blip' tested, both OK

- Profile monitor actuation and limit switches tested, all OK (monitor starts to travel @ 20psi, fully engaged at ~40psi)

- Elevation measurements taken for profile and protect monitors

- Target ladder moved to position 3 (12mm Be target)

- Noticed strange 'click/twang' noise when moving target ladder, found to be caused by twisted bellows on water supply tube

- Bellows was straightened, and the target was leak checked again (still leak tight)

- Noticeable wear was found on potentiometer wires.  Pot values still read accurately.  Travis C. inspected and does not think they need urgent replacement.  Will have Probes Group look at it next time the target is in the HC (they are very busy now).

- T1-MK1 target transported from HC to storage pit location #3  (ready for use in beam line)

- T2-MK1 target transported from storage pit to HC (max field: 97,000 μSv/hr @ 0.5m)

  53   Friday, July 27, 2012, 14:48 Isaac EarleRepairTarget 1TargetT1-MK1 Target Repair Update

- T1MK1 target transferred from storage pit to hot cell (max field: 4700 μSv/hr @ 0.5m)

- Protect monitor with incorrect wiring removed (20μSv/hr on contact, 60cpm contamination on 44-2 meter)

- Scott Kellog fixed the wiring and returned the protect monitor (correct wiring schematic is TDE0301E, previously used incorrect schematic D10649)

- Installed new protect monitor on target

- Profile monitor was found to have broken wires and will be replaced with new more robust design (0.005" thick gold coated molybdenum wires)

- Bill Rawnsley confirmed that protect and profile monitor wiring harnesses are wired correctly using resistor packs

- Bill was double-checking the wiring of the new profile monitor before installation and found that it had been wired incorrectly.  Scott K. will fix the wiring and return the monitor mid next week for installation.

- Leak check was performed on the target and confirmed that all seals and target cassettes are leak tight

 

  52   Monday, July 23, 2012, 16:01 Isaac EarleDevelopmentTarget 1TargetTarget Flask Seismic Restraint Clamps Installed

 Installation of the seismic restraint clamps has been completed for the MK1 and MK2 target flasks in the Remote Handling lab (photos attached).  Two clamps on the MK1 flask required 3/8" shims due to warpage of the flask baseplate (see photo IMG_0429).

Dragan Mitrovic has been notified so that he can inspect the installation and close the work request.

  51   Tuesday, July 17, 2012, 15:30 Isaac EarleDevelopmentTarget 1CoolingT1 & T2 Expansion Tank Level Warnings Added

 Mike Mouat and Juan Pon have modified the control system so that the control room will receive a message when the warning or trip level sensors for the T1 & T2 expansion tanks read "NOT OK".  The message also displays the current water height in the tank.  This will help with earlier detection of water leaks from the cooling package or from the target ladder in the vacuum volume when the vacuum interlock has been defeated.

All sensors were checked by depressing the level sensor float and the correct warnings came up on the message reader.

  50   Wednesday, July 11, 2012, 17:51 Isaac EarleRepairTarget 1TargetT1 Target Swap

 BL1A was started yesterday and brought up to 10μA.  A problem was noticed with the T1 protect monitor (the right and bottom plates were not showing any response when the beam was swept across the monitor).  The protect monitor is new and was installed on the target assembly in February 2012, so this is the first time it has seen beam.  A 'blip' test was performed on the monitor in the hot cell and once again from the mezzanine after the target had been installed in the beam line.  Both tests showed that the monitor was performing normally, so an internal wiring mistake on the monitor was initially suspected and it was decided that the T1-MK1 target should be swapped with the T1-MK2 target.

Today the T1 monolith was uncovered, the T1-MK1 target was moved to the storage pit, and the T1-MK2 target was moved from the hot cell to the beam line.  The T1 volume pumped down normally after installation and a 'blip' test performed from the mezzanine showed that the protect monitor on the new target was functioning normally.  The potentiometer look-up tables were switched to the appropriate target (initially Graham Waters had difficulty with the control software, but was able to solve the problem by accessing the program remotely).  The T1 target is now ready for BL1A start-up.

This afternoon Bill Rawnsley discovered that there were two different protect monitor designs, one with a different internal wiring configuration than what has been used in the past.  If the protect monitor on the T1-MK1 target is the design with the different configuration, this could explain the symptoms observed yesterday.  If we had known this earlier, it may have been possible to solve the problem by installing a simple wire adapter at the mezzanine to switch the wires in the connector to the same configuration as the original design and the target swap would not have been necessary (saving time, dose, and the potential for damaging equipment due to handling).  This will be investigated further to determine if it is really the case.

 

 

 

 

 

 

 

 

 

  49   Monday, July 09, 2012, 17:17 Isaac EarleStandard OperationTarget 1TargetBL1A Start-Up Prep

 - T1 & T2 targets switched to "remote" control
 - Both target ladders were moved to Position 3 (12mm Be)
 - T2 Q1 flow interlock defeat was removed (only required when target ladder is in position zero)
 - The targets are now ready for BL1A start-up (up to 10μA this evening)
 

  48   Friday, July 06, 2012, 16:03 Isaac EarleRepairTarget 1TargetT1-MK2 Target Repair Complete

 Target elevation measurements and beam spot plots were completed on the T1-MK2 target and the target is now fully repaired and ready for use.  It will be returned to the storage pit when cranes are available.

A copy of the elevations measurements and beam spot plots is attached.