M9sol Logbooks Solenoid Daily log
  Solenoid logbook, Page 2 of 15  ELOG logo
Entry  Wed Jun 14 10:35:30 2006, Willy Andersson, Quench Recovery, Switched to series cooling. 
Had system in //return cooling overnight with small flow to keep power 
leads cool. Switched to series mode about 30 minutes ago. Building LHe 
level.
Entry  Wed Jun 14 16:27:01 2006, Willy Andersson, Quench Recovery, Energized solenoid 
Powerleads appear stable.
Entry  Thu Jul 20 11:01:09 2006, Willy Andersson, Quench Recovery, Opened up warm return valves CV151 and CV153 
Mu2 pressure was just about at trip point due to trapped volume of helium 
warming. So opened up warm returns to bleed off pressure and prevent it 
from rising.
Entry  Thu Jul 20 13:21:57 2006, Willy Andersson, Quench Recovery, started // warm return flow. 
TIC121 was down to 27K
warm return valves were wide open
opened supply valves CV143 and CV146.
Entry  Thu Jul 20 13:27:21 2006, Willy Andersson, Quench Recovery, cold return mode continues... 
cr_c1 and cr_12 are both at about 45K and heading slowly down, so the 
gamble of going to // cold return worked. Maximum opening of CV155 is 
limited by CV204 goes fully closed and suction pressure begins to rise 
Entry  Thu Jul 20 13:34:26 2006, Willy Andersson, Quench Recovery, cold return mode continues... 
Even though cr_c1 and cr_c12 have begun to tick down, cr_c7 and cr_c6 are 
actually ticking up. This is probably a wave of warming propagating through 
the solenoid. As long as the two inlets are falling in temperature then 
Entry  Fri Jul 21 17:18:19 2006, Willy Andersson, Quench Recovery, Opened HIC142 fully open 
Power leads have flatlined but still building LHe level.
Entry  Wed Aug 9 06:44:58 2006, Willy Andersson, Quench Recovery, // cold mode cooling continues. 
After restarting flow to the solenoid yesterday in // cold return mode 
TIC121 just refused to go lower than about 29K even when we closed CV155 
all the way. Tried various things, switching to // warm return, changing 
Entry  Wed Aug 9 06:59:43 2006, Willy Andersson, Quench Recovery, more // cold return stuff 
About 21:00 last night the solenoid temps had not changed much, pretty well 
flat lined. I guess my reducing CV155 stalled the cooling. Called Don 
Arseneau and asked him to increase CV155 to about 80% open. Temps slowly 
Entry  Thu Aug 10 16:33:11 2006, Willy Andersson, Quench Recovery, Flow to solenoid tripped on powerlead temperature. 
Power lead temps were drifting up, tried to tweak TIC121 and HIC141 to 
unstall powerlead flow. Got quench. Restarted series flow, building LHe 
level.
Entry  Thu Aug 10 20:26:09 2006, Willy Andersson, Quench Recovery, solenoid energized 
Powerleads seem stable.
Entry  Tue Aug 15 15:39:27 2006, Willy Andersson, Quench Recovery, switched to parallel cold return 
Return flow temps from solenoid about 40K, TIC121 at about 40K so switching 
to //cold return.
Starting with slightly reduced flow through cold returns, CV145 and CV147 
Entry  Thu Aug 17 19:45:27 2006, Willy Andersson, Quench Recovery, switch to series cooling 
Temps of flow returning from solenoid flat lined at about 10K.
Gradually closed CV155.
Then switched to series cooling.
Entry  Wed Oct 4 18:10:18 2006, Willy Andersson, Start Up, Quick check on system 
System in good // warm return mode, temps coming down nicely. BCP2 cryopump 
does not look too healthy, temperature is just over 20K, very close to low 
set point.
Entry  Thu Oct 12 11:53:04 2006, Willy Andersson, Quench Recovery, Compressor trip, 09:50 this morning. 
Main compressor tripped, refrigerator shutdown. Checked with experimentors 
and main control room, no indications of power bump etc.
Entry  Thu Oct 12 19:54:10 2006, Willy Andersson, Quench Recovery, Energized solenoid. 
Switched to series mode about 6 hours ago. Cooling continued including 
power leads until LHe level at about 50% and powerleads appeared stable.
Entry  Thu Oct 26 04:27:31 2006, Willy Andersson, Quench Recovery, Powerlead overtemp 
02:30 this morning got page from operations.
Looked at system online, appears that there was a powerlead overtemp
that caused the quench. Compressor still running. After arriving to 
Entry  Thu Oct 26 04:34:15 2006, Willy Andersson, Quench Recovery, Still in // cold return mode. 
Leaving system cooling in // cold return mode, cooldown rates still good. 
Had flow on to powerleads since re-starting cooling flow to solenoid.
Either I (when I return to work later this morning) or Doug will do the 
Entry  Wed Nov 15 17:05:49 2006, Willy Andersson, Quench Recovery, powerleads cold, energizing solenoid 
Powerlead temperatures have bottomed out, energizing solenoid to 300 
amps, ramp rate 60.
Entry  Sat Oct 9 22:50:26 2004, Other, , power leads warmed 
At 10:30 PM Saturday, Donald Arseneau sees power leads at
25K, having gone up for the previous 10 hours.  (I didn't
see it earlier because striptool wasn't scrolling).  Cycled
ELOG V2.9.2-2455