Last night at about 7:00 there was a large power bump that shut the compressor and water pump off. I came in this morning and am restarting the system.
started flow to solenoid in parallel cold return.
Saturday November 12 the solenoid power supply ramped itself down to zero. It would not ramp up unless the ramp rate was set to 30 minutes. At this setting the power supply ramped up to the required current. It seems to ramp slower than the 30 minute rate. Klaus also looked at the problem. His suggestion is to exercise/clean the switches and pots.
The solenoid tripped on power lead temps at about 9:15. I am recovering it from it's all around mode into parallel cold return.
shuttting down the system. isolated cold box by closing v135. preparing to pump out cold box.
Solenoid and cold box were pumped out last Tuesday. Cold box roughing pump initially would not start. had to retighten all wires on the contactor in the Sulzer control panel (RP900). Started compressor on Friday. ran purifier over the weekend. Started flow in parallel warm return. Started flow to turbines. Replacing dead monitor on other control computer.
switched to parallel cold return
CV155 closed. Temps about 15K
Changed to series mode. Liquid level building.
Started flow to power leads. Liquid level 15%
Solenoid is cold, liquid level is 35%, power leads cold and seem stable. Added one bottle helium to buffer tank. Pressure is 7 psi..
power leads warming. closed HIC 142, then re-opened. temps falling
No indicator lights etc as to why the compressor tripped. The only light was a cold box fault. I had to shut off the main breaker before the compressor would come back on. Started cooling in parallel cold return.
LI108 indicates high on EPICS screen (150%) Controller shows ~64%
I would have made an entry when it died, but-----
Tuesday night. June 27, 2006, the solenoid quenched for no apparent reason. It was restarted Wednesday morning. The vacuum in the solenoid went away (up to 8 Torr). This was found to be a result of a leaking isolation valve between the solenoid and T2. T2 was vented, which caused the solenoid to slowly vet. When T2 was pumped out again, the solenoid vacuum recovered. This caused a delay in recovering the solenoid. As of Friday morning 7:15 the solenoid power supply was ramped up.
power lead warming/ripples caused quench at 18:45 today. Compressor stayed on, but flow to solenoid stopped. I started flow to solenoid at 22:40.
test
Solenoid Quenched on C1 temp. It went above 5K. Shut off compressor. Restarting system @ 12:15