Logbooks Lab Maintenance Evaporator_1 Evaporator_2 Laser cutter Target Production Test-Stand RH-ISAC RH-Cyclotron RH-Meson Hall RH-Beamlines RH-ARIEL
  Lab Maintenance, Page 4 of 4  Not logged in ELOG logo
New entries since:Wed Dec 31 16:00:00 1969
ID Date Author Status Test Subject
  4   Wednesday, April 13, 2011, 13:54 John Wong  Cloth booties now avaiable for hotlab

Wed Apr 13 13:53:46 2011

I've setup a box of cloth booties for entering the hotlab.  They are
washable so please use them.  I also have some paper booties there if you
like using them, but it can be costly to keep stocking them up, plus the
fee to throw them away.

As per RPG, before you exit the hotlab please check yourself.  If the
cloth booties are clean of radiation, please put the them back to the box.
 I'll ask to get them wash every now and then.

  3   Tuesday, April 12, 2011, 12:07 John Wong  All Fumehood pumps in hot and cold labs tripped off due to MCC-X powered down

John Wong wrote:

All the fumehood pumps in the ISAC-I hot and cold labs got tripped off when the MCC-X was powered down (See ISAC WP#2011-03-30-5). No reaction process is done inside the  fumehoods, so the pumps are ok to be left off for now until the MCC-X work is done.

 

On 3/31/2011 2:01 PM, Jonathan Aoki wrote:
> Razvan and I took a closer look.  We found that power to the fumehoods
> likely was not lost (they are fed from a different panel), but that EF14
> and EF15 would have tripped off.  These two fans serve the room 06 and 07
> fumehoods.
>
> This is an oversight on my part and I apologize for any inconvenience --
> EF14 and 15 are clearly stated on P-370's directory.  I hope that no
> damage was done.
>
> I will leave it to your discretion, but this (in my opinion) is worthy of
> an NCR.  I've updated my planned power outage notes.  This should not
> happen again.
>
> Jon
>
>
>> Thank Jon.
>>
>> Pierre
>>
>> Le 2011-03-31 à 13:37, "Jonathan Aoki"<jonaoki@triumf.ca>  a écrit :
>>
>>> Razvan&  Franco,
>>>
>>> Yesterday, during the MCC-X power down there was one unexpected event --
>>> the fumehoods in Marik's cold/hot labs tripped off.
>>>
>>> According to the documentation that I have, the following panels were to
>>> be affected:
>>> P-370
>>> P-378
>>> P-384
>>> P-396
>>> P-418
>>>
>>> I have print-outs of all of the circuit directories and I don't see any
>>> mention of the fumehood fans.
>>>
>>> Can you please trace the fans' electrical feed and let me know so that I
>>> can update our directories?
>>>
>>> Thanks,
>>> Jon
>>>
>>
>
  2   Tuesday, April 12, 2011, 12:03 John Wong  Hot Lab Glove Box Regeneration

Tue Apr 12 12:00:52 2011:  The hot lab glove box regeneration was started yesterday (April 11, 2011).  "Before regeneration, the O2 level was 97 ppm, The H2O level was 47 ppm. After restarting circulation through the dry train, the levels immediately started dropping. At 11:30 today, the O2 was @ 1.76 ppm, the H2O @ 11.2 ppm." (Marik). 

 

  1   Wednesday, March 30, 2011, 16:47 John Wong  All Fumehood pumps in hot and cold labs tripped off due to MCC-X powered down

All the fumehood pumps in the ISAC-I hot and cold labs got tripped off when the MCC-X was powered down (See ISAC WP#2011-03-30-5). No reaction process is done inside the  fumehoods, so the pumps are ok to be left off for now until the MCC-X work is done.

ELOG V2.9.2-2455