64
|
Wed Oct 13 08:17:00 2004 |
Experimentor | Start Up | cycling 142 when temp hit 10.68 |
I tried cycling the valve twice -- at about 11:30 and again around 1:00,
trying both the buttons and the dial -- but it has had no effect on
the temperatures (aside from the transient spikes). That might be
bad. We will have to see if it altered the trend.
--
Donald Arseneau |
|
67
|
Sun Oct 17 04:26:29 2004 |
Other | Start Up | cycling 142 when temp hit 10.68 |
> I tried cycling the valve twice -- at about 11:30 and again around 1:00,
> trying both the buttons and the dial -- but it has had no effect on
> the temperatures (aside from the transient spikes). That might be
> bad. We will have to see if it altered the trend.
>
> --
> Donald Arseneau
It did -- temperatures held stable for several days |
|
212
|
Tue Jul 31 07:53:57 2007 |
Kevin Trithardt | Normal Running | cycled power leads |
got a page for the power lead temp
came down and cycled the power leads.. did not seem to make a difference..
Kevin |
|
59
|
Mon Oct 11 03:56:14 2004 |
Experimentor | Start Up | cv142 valve |
noticed that the lead temp rose to 24K over the past 4 hours. had control
room personnle cycle the cv142 valve. temperature dropped.
srk |
|
60
|
Mon Oct 11 11:49:34 2004 |
Experimentor | Start Up | cv142 valve |
noticed temp rise, which occured only about 5 hours after the
last "reset" .... the time between resets seems to be decreasing, which is
not a good sign.
had the controll room guys reset the cv142 valve (i.e. cycle it off/on)
syd |
|
61
|
Mon Oct 11 22:32:11 2004 |
Experimentor | Start Up | cv142 valve |
temp of leads begins its exponential rise again (caught it at 12K), approx
11 hours after last reset. this time asked operator to shut off valve for
3 seconds, then turn back on.
previous recycle, asked operator to shut off valve for two seconds ... and
the warm up time was 11 hours.
previous^2 recyle, asked operator to shut off valve for 1 second ... and
the warm up time was only 4 hours.
Syd |
|
62
|
Tue Oct 12 02:05:31 2004 |
Experimentor | Start Up | cv142 valve |
after only two hours since last lead cycling, they warm up quickly.
ops cycles the valve, but more quickly this time, off ... 1 sec ... on.
syd |
|
63
|
Tue Oct 12 13:00:08 2004 |
Curtis Ballard | Start Up | cv142 valve |
Curtis closes and opens slowly at about 11:00 am this morning. Wants to see
if that works better than the sudden on/off switch.
reported by srk |
|
170
|
Sun Oct 15 07:09:41 2006 |
Other | Normal Running | cryopump bcp2 trip |
Donald Arseneau reporting
Not really solenoid realated, but FYI...
The cryopump bcp2 stopped working and the vacuum valves tripped.
When I came in, the CP was over 200K and the pressure (bcg4) read
over 200 torr, with the CP nominally on. I switched it off and
continued warming; pumped it out; and am now re-cooling. It seems
to be normal so far.
-D |
|
98
|
Thu Jun 2 09:16:40 2005 |
Doug Preddy | Quench Recovery | continuing to cool |
See screen grab |
| Attachment 1: 02-06-05-7.32.49 AM.jpg
|
 |
|
50
|
Mon Sep 13 13:56:06 2004 |
Doug Preddy | Shut Down | compressor off |
compressor off |
|
141
|
Thu Jul 20 13:27:21 2006 |
Willy Andersson | Quench Recovery | cold return mode continues... |
cr_c1 and cr_12 are both at about 45K and heading slowly down, so the
gamble of going to // cold return worked. Maximum opening of CV155 is
limited by CV204 goes fully closed and suction pressure begins to rise
above set point. Adjust cv155 to keep cv204 just at the closed point. Keep
tweaking cv155 and turbine speeds as things get cooler. |
|
142
|
Thu Jul 20 13:34:26 2006 |
Willy Andersson | Quench Recovery | cold return mode continues... |
Even though cr_c1 and cr_c12 have begun to tick down, cr_c7 and cr_c6 are
actually ticking up. This is probably a wave of warming propagating through
the solenoid. As long as the two inlets are falling in temperature then
things are going in the right direction. Once the warm wave travels through
the outlets will begin to cool as well. |
|
218
|
Tue Sep 18 18:48:11 2007 |
Curtis Ballard | Maintenance | cold box leak check |
The leak check of the cold box diff pump fittings. Found a leak at the
base of the diff pump on the tee that is apparently used to fill the pump
with oil. The fitting was removed and a plug was removed that resembled a
dip stick (approx 1" long). Tbe dip stick was charred black as if it had
been hot. The seal between the dip stick and the tee was not an O-ring.
It looked like a high temperature glue? For leak checking purposes, an O-
ring was fitted to the dip stick and reinserted in situ. Only the top
portion of the tee was removed. The lower cap was slathered in vacuum
grease. Pumping back down was slow. After two hours the vacuum was down
to 2 torr. At 6:30 pm, the vacuum was 200 mtorr, so I turned on the
filament and tried again to leak check. I was able to get the throttle
valve open a little wider than previously, but we still had a big leak. I
checked at the tee and got a strong response, but I also checked at the
diff pump connections and also got a response, albeit much less. We may
have to blank off the entire diff pump to isolate the cold box so that we
can leak check the system. Dimo said he will be able to help tomorrow.
For now, I will leave the roughing pump on the cold box and isolte the
leak detector. See you tomorrow.
P.S. I left a voice mail re: welding at TITAN 8:30 am/blankets/work
permits/extractor. cb |
|
252
|
Fri Jul 25 21:48:15 2008 |
Doug Preddy | Quench Recovery | another quench |
| System was stable and solenoid ramped up at 4:00 today. At about 7:30 it tripped off again. I came in and restarted the compressor and am now cooling in parallel cold return mode. Solenoid is at ~30K. I talked to Kevin and he will get the power leads on tomorrow morning. Once they are stable the power supply can be ramped up.
I phoned Curtis, but there was no answer (he may be on holidays??) |
|
42
|
Thu Aug 19 10:28:32 2004 |
Doug Preddy | Start Up | after M9bv5 FIX |
Over the last couple of days we replaced the gate on the M9BV5 valve. The
old one had worn the teflon sliders on the sides. Metal shavings on bottom
of body. Found a replacement with metal rollers, rather than slides.
Pumped out downstream of gate valve. It's down to 5E-7 (moved the cable on
the ion gauge so it now reads.)
Started cooling down the solenoid. Charging through the adsorber. LN2 fill
piping broke. Repaired by resoldering.
Ion gauge on solenoid seems to have burnt out last night. |
|
53
|
Tue Oct 5 07:18:16 2004 |
Doug Preddy | Start Up | adjust compressor discharge pressure |
adjusted compressor discharge pressure to 11 Bar |
|
88
|
Wed Dec 1 12:55:56 2004 |
Doug Preddy | Normal Running | added one bottle helium gas |
buffer tank pressure is up to 6.5 psi. |
|
201
|
Tue Jun 12 12:48:25 2007 |
Doug Preddy | Maintenance | added one bottle UHP helium to system |
|
|
12
|
Thu Apr 22 10:39:16 2004 |
Doug Preddy | Normal Running | Yesterday |
Added two bottles of UHP helium to buffer tank.
Had no liquifation rate, so optimized Ti121 and HIC141 . Finally put TIC121
into manual mode at 0.65. Power lead fluctuation died out and liquid
started building.
This morning changed TIC121 back to auto mode and played with it's setting
to minimize the power lead and TI121 ripples.
TI121 ripples seem tied to power lead ripples.
System seems stable enough to energize the solenoid. |