M9sol Logbooks Solenoid Daily log
  Solenoid logbook, Page 6 of 15  ELOG logo
Entry  Wed Nov 28 15:07:08 2007, Kevin Trithardt, Other, power lead regeneration 
Power leads cold again, power supply ramping up.
Entry  Tue Oct 31 03:52:29 2006, Doug Preddy, Quench Recovery, power lead quench at 2:30 this morning 
Compressor still on. Starting flow to solenoid
Entry  Thu Oct 26 14:14:57 2006, Doug Preddy, Quench Recovery, power lead quench 
solenoid tripped on power lead temp. I was here and caught it. System 
cooling.
Entry  Fri Nov 23 08:35:37 2007, Doug Preddy, Normal Running, power lead problems 
About 10 hours ago the power lead temperatures started to fluctuate and 
climb.
I cycled CV142 and the Temps have dropped and stablized.
Entry  Mon Nov 26 09:45:43 2007, Doug Preddy, Normal Running, power lead problems 
Power lead temperatures were rippling yesterday afternoon. I asked one of 
the operators to cycle CV142.
The temperatures were rippling again this morning, so I cycled CV142.
Entry  Fri Oct 29 14:25:23 2004, Doug Preddy, Normal Running, power lead flows dropping 
Flow is down to <190 mm. temps are starting to climb. Cycled HIC142
Entry  Mon Nov 1 07:17:44 2004, Doug Preddy, Normal Running, power lead flow gone bad 
power temps as follows:
LHE_IN 23
PL_POS 36
PL_NEG 31
Flow <90mm 
cycled HIC 142 off and on in 1/2 hour.
Entry  Wed Oct 24 12:04:06 2007, Doug Preddy, Maintenance, power lead and cryopump regeneration 
Regenerating M9B:CP2 as temperature was up to almost 20k.
Shut off flow to power leads to allow them to warm up. The positive and 
negative temps were beginning to creep up.
Regeneraing the adsorber.
Entry  Thu Jul 24 16:28:50 2008, Doug Preddy, Quench Recovery, power bump 
There was a power bump at ~15:00 today. All mseon hall cooling water went off. Compressor tripped. Main magnet went off. Restarted compressor after water pumps came back on. Started flow to the cold box. Compressor outlet pressure went >12 Bar and tripped of the compressor. Restarted again and am now cooling in parallel cold return. Solenoid ~25K.
Entry  Wed Oct 6 07:57:01 2004, Doug Preddy, Start Up, parallel cold return 
Switched to parallel cold return at 4:00 yesterday afternoon.
6:30 this morning started closing cv155 as temps had bottomed out at 24K.
Entry  Wed Apr 21 06:39:17 2004, Doug Preddy, Start Up, over night 
Changed to parallel cold mode at 9:30.
At about 4:30 the city water chiller was turned on. The air compressor had 
also tripped off. It was reset and restarted.
Entry  Fri Jan 26 15:10:37 2007, Doug Preddy, Maintenance, new control computer installed 
I have installed a new control computer at the M9 solenoid control panel
Entry  Tue Apr 20 07:06:41 2004, Doug Preddy, Start Up, morning day 2 april200705.BMP
Temps in solenoid are equalling out. Increasing PIC229 to 11 bar. 
Entry  Sun Dec 5 11:15:24 2004, Doug Preddy, Normal Running, more ripples 
I loked at the power lead temps this morning. LHe_in 10.4-12.0  PL-Neg 8.0-
9.0  PL-Pos 9.8-10.4. Flows down to 160mm. Called Ops and got Danica to 
cycle CV142. Ripples and flow improved on the second try.
Entry  Wed Aug 9 06:59:43 2006, Willy Andersson, Quench Recovery, more // cold return stuff 
About 21:00 last night the solenoid temps had not changed much, pretty well 
flat lined. I guess my reducing CV155 stalled the cooling. Called Don 
Arseneau and asked him to increase CV155 to about 80% open. Temps slowly 
began to fall. Asked Don to look at graph of temps later in the night and 
if they fall down to a flat line to then reduce CV155 a bit to get the 
temps trending further down.

This morning CR_C1_ENT has fallen to a slightly upward trending flat line 
of about 12.7 K. Probably ready for switching to series mode by whoever 
gets to the system first this morning.
Entry  Sat Jul 22 06:34:14 2006, Experimentor, Quench Recovery, looking good 
Donald Arseneau reporting.

It is looking pretty good, so I came back in with the intent of energizing 
the magnet.  Doug should be up now or soon, so I'll wait a little for you 
to see this.  If you do, call the m9 counting room 222-7379.  After waiting 
a while, I will just forge ahead.
Entry  Sat Oct 16 17:18:50 2004, Other, , lame 
 
Entry  Wed Apr 16 15:12:01 2008, Doug Preddy, Normal Running, graphs to load 
There are three strip tools saved: coils powerlead startup
Entry  Fri Oct 5 13:25:41 2007, Doug Preddy, Quench Recovery, funny graph  Capture.jpg
There was a fluctuation of the positive lead temp with no flow going to 
the power leads.
Entry  Fri Apr 9 16:07:28 2010, Doug Preddy, Start Up, flow to power leads started 
 