 On January 15th, when attempting to move the T2 target from the beam line to the hot cell, the latch mechanism on the flask did not actuate and the target could not be lifted from the beam line.  

On January 16th the flask was placed on blocks (IMG_0818) (while remaining attached to the crane) in the RH hot cell lab for inspection.  The cause of the problem was found to be a damaged and disconnected military style connector (IMG_0824).  Damaged wiring was also found (IMG_0836).

On January 21st the connector and faulty wiring was replaced by Travis Cave, which fixed the problem (IMG_0838).  The new location of the connector is less exposed and should prevent it from getting damaged if the target swings within the flask.  Travis and Don Jackson also used the opportunity to check some wires on the flask that previously were not documented properly.  The flask was returned to its storage position in the lab and is ready for use.

Attachment 1: IMG_0818.JPG  145 kB  | Show | Hide all
Attachment 2: IMG_0824.JPG  129 kB  | Show | Hide all
Attachment 3: IMG_0836.JPG  84 kB  | Show | Hide all
Attachment 4: IMG_0838.JPG  136 kB  | Hide | Hide all
IMG_0838.JPG
ELOG V2.9.2-2455