Message ID: 308     Entry time: Thursday, January 12, 2023, 10:36
Author: Adam Newsome 
Category: Maintenance 
Type: Target 1 
Specific: Water Leak 
Subject: T1 and T2 - Cooling Package Water Leaks - Ball Valves 

Upon uncovering the T1 and T2 areas to prepare for regular cooling package maintenance, it was discovered that multiple ball valves were leaking. Primarily the Swagelok SS-45S12 parts, but some SS-45S8 parts have failed as well. There were small puddles of water underneath many of the valves. It appears that the leak is due to a compromised seal. It is suspected that these parts failed from radiation exposure. They have PTFE packing material which is highly susceptible to decomposition under irradiation, and as far as we can tell they have not really been repaired/replaced (aside from a written note on one saying the seal was changed in 1997).

It is recommended to add the regular repair/replacement of these valves to the annual shutdown MRO checklist.

Once replaced, this e-log will be updated to document which ones were replaced.