Service bridge, Outrigger #1, and Outrigger #2 have had the controls system migrated to PLC controls. The 5069-AENTR control unit is located at the centrepost and will be mounted there after wiring is cleaned up. Preliminary testing consisted of operators simulating a shutdown task was performed today and was a success. Minor adjustments to the encoder logic will be made before the commissioning test. The follow tests were done:
PLC box:
Check Relays toggling over correctly.
OR1:
Radial In/Out & HMI Feedback Accurate
Vertical Up/Down & HMI Feedback Accurate
Shoulder Home/Out & HMI Feedback Accurate
Elbow Home/Out & HMI Feedback Accurate
Pan CW/CCW & HMI Feedback Accurate
Tilt Up/Down & HMI Feedback Accurate
Cameras Zoom/Focus
4 movements at once
Random camera restart noted (could be tied to grounding issue. will further investigate)
OR2:
Radial In/Out & HMI Feedback Accurate (Encoder Swap direction)
Vertical Up/Down & HMI Feedback Accurate
Shoulder Home/Out & HMI Feedback Accurate
Elbow Home/Out & HMI Feedback Accurate
Pan CW/CCW & HMI Feedback Accurate
Tilt Up/Down & HMI Feedback Accurate
Cameras Zoom/Focus
4 movements at once
Bridge:
Orbital Motor & Encoder HMI Feedback (Orbital Motor controls using Outrigger CP only active when ORs not selected) (set range to 0 to 360 same direction)
Centerpost Camera PTZF
Light
Speed Control
Vid Trolley:
Test operating video trolley with bridge controls and outriggers
Top/Bot LED
Implement radial speed control using pot
|