Message ID: 22     Entry time: Wednesday, June 10, 2015, 14:57
Author: Isaac Earle 
Category: 100KW Beam Dump 
Type: Development 
Subject: BD Water System Leak Test 

A leak test was performed on the beam dump water system on June 9 in the afternoon.

- Pipe segments tested: The entire HAW system except for the expansion tank, air separator and HAW pump
- Test medium: air
- Test pressure and duration: 60 minutes at 50psi with no loss in pressure
- Swagelok joints and VCR joints around the beam dump which had been opened since last test were sprayed with Snoop: no bubbles