  187   Thu Apr 19 15:18:25 2007 Doug PreddyStart Uppreparing to start the refrigerator
Starting the vacuum systems in the coldbox and solenoid.
  188   Fri Apr 20 12:15:12 2007 Doug PreddyStart Upremote PLC switch
I could not control the vacuum devices using EPICS. The buttons could be 
pushed, but nothing would respond. The PLC was in local mode. Thumbwheel 
to 100, push On/Open button to put it into remote mode.
  189   Mon Apr 23 16:31:02 2007 Doug PreddyStart UpStarted compressor
Startewd compressor and purifer today.
  190   Tue Apr 24 10:21:49 2007 Doug PreddyStart UpStarted flow to turbines
Started flow to turbines at about 10:00 in parallel warm mode.
  217   Fri Sep 14 12:44:52 2007 Doug PreddyStart Upstarted compressor
running purifier over weekend
  220   Mon Sep 24 15:08:41 2007 Doug PreddyStart UpStarted cool down this morning
The vacuum in the cold box was good on Friday 0.0 X 10-4. Let it pump over 
the weekend. Added two bottles of UHP helium to system Friday.

Started the turbines this morning. Cooling in paralell warm return. 

Solenoid vacuum is 3.9 x 10-6
  221   Tue Sep 25 07:34:04 2007 Doug PreddyStart UpPIC229 to 11 bar
adjusted turbine speeds and HIC104 to maintain their values.
  222   Wed Sep 26 08:52:46 2007 Doug PreddyStart Upswitched to parallel cold return
  223   Thu Sep 27 07:41:15 2007 Doug PreddyStart UpSolenoid cold
Solenoid cold and in series mode. 50% liquid level. Starting flow to 
powerleads.
  243   Tue Apr 1 15:17:06 2008 Doug PreddyStart UpStarting up vacuum systems
Monday afternoon there was no control of the vacuum system. The controls were working, but no output to devices. The "output" breaker in the PLC box was found to be tripped. Reseting it allowed control to the vacuum systems. I started the regeneration of BCP2 this morning, but hte output breaker tripped again. reset it and continued to pump. Started to pump out the solenoid also. Removed jumper on the BDP2 temperature read-back, bypassed BV2, and BCG2. This allows pumping through the diffussion pump. Cold box has been pumping for a few weeks. It's at 2.0 x 10-3
  245   Wed Apr 16 15:15:44 2008 Doug PreddyStart Uprefrigerator started
Turned on compressor last Tuesday. Ran purifier until today. Final value 0.15ppm. Started cool down yesterday. Switched into parallel cold return this morning, but PIC 229 would not allow the compressor to charge. The compressor tripped due to bad solenoid vacuum (solenoid was warming up). The controller now seems to be working okay. Restarted in parallel warm mode at ~12:00
  246   Wed Apr 16 16:51:16 2008 Doug PreddyStart Upswitched to parallel cold return
  247   Thu Apr 17 13:52:25 2008 Doug PreddyStart Upswitched to series mode at 9:30 this morning
switched to series mode at 9:30 this morning. Added two bottles of helium gas. Started flow to power leads.
  274   Wed Mar 24 08:30:33 2010 Doug PreddyStart UpStart up

Compressor started yesterday afternoon. Pumping out solenoid overnight. Cold box vacuum good. circulating helium to solenoid in Parallel warm mode, CV142 open. Purifier running.

  275   Mon Mar 29 09:25:52 2010 Kevin TrithardtStart UpStarted cool down this morning
  276   Thu Apr 1 11:57:55 2010 Doug PreddyStart Upstarted flow to power leads

Solenoid cold. Buffer tank pressure ~3psi, so Kevin will add a bottle of helium. Started flow to power leads at 11:45

  278   Fri Apr 9 16:07:28 2010 Doug PreddyStart Upflow to power leads started
  49   Mon Sep 13 10:55:25 2004 Doug PreddyShut DownQuench and shutdown
The solenoid quenched on powerlead temps this morning at 10:00. It is 
warming up and the power leads are >200K.Isolating and purging the coldbox 
is not very useful now, so I am shutting the system down.
  50   Mon Sep 13 13:56:06 2004 Doug PreddyShut Downcompressor off
compressor off
  116   Thu Dec 22 15:10:44 2005 Doug PreddyShut Downshut down system
shuttting down the system. isolated cold box by closing v135. preparing to 
pump out cold box.