Subject
*
:
> About 21:00 last night the solenoid temps had not changed much, pretty well > flat lined. I guess my reducing CV155 stalled the cooling. Called Don > Arseneau and asked him to increase CV155 to about 80% open. Temps slowly > began to fall. Asked Don to look at graph of temps later in the night and > if they fall down to a flat line to then reduce CV155 a bit to get the > temps trending further down. > > This morning CR_C1_ENT has fallen to a slightly upward trending flat line > of about 12.7 K. Probably ready for switching to series mode by whoever > gets to the system first this morning.