M9sol Logbooks Solenoid Daily log
  Daily log  ELOG logo
  ID Date Author Type Category Subject
  2   Thu Jul 6 15:08:01 2006 Doug Preddy  Daily log for Thu 06 Jul 2006 03:04:41 PM PDT
	COMPRESSOR BUILDING

1	Oil cooler water inlet temp. 30	(28)	
 
2	Oil cooler water exit temp. 30	(30)	

3	Gas cooler water exit temp.	25(25)	

4	Suction gas temp.		23(23)	

5	Discharge gas temp.		82(82)	

6	Final gas temp.			22(23)	

7	Oil temp.			41(40)	

8	Suction gas press.	0.1	(0.1)	

9	Discharge press.	10.8	(10.8)	

10	Final gas press.	10.5	(10.5)	

11	Oil press.		14	(13.0)	 

12	Oil filter out press.	10.1	(10.2)	

13	Compressor current	275	(270)	

14	Oil pump current	5.1	(5.1)	

15	Hours			8585.0	(????)	

16	Warning lights		ok	(ok)	

17	Oil level		9.0	(9.0)	

18	Gas cooler water inlet temp.	(72)	

19 	Gas cooler water flow		(16)	

20	Oil cooler water flow		(135)	

21	Water pump pressure		(65)	

22	Water pump condition		(ok)	

23	Cu. non-active water flow	(165)	

24	PI9 Buffer tank pressure	(15)	

25	PI218 Low pressure		(3.0)	

26	PI229 High pressure		(145)	

27	PI296 Inlet press.		(147)	

28	Air compressor condition	(ok)	

	SULZER CONTROL PANEL

29	PI 110-1 T1 inlet press.	(9.4)	

30	PI 120-1 T2 inlet press.	(4.0)	

31	HIC 106 Turbine inlet press.	(9.9)	

32	TI 148 Mu1 supply temp.		(4.05)	

33	TI 149 Mu1 supply temp.		(4.05)	

34	HIC 143 Mu1 supply		(9.9)	

35	PI 143 Mu1 supply pressure	(10.4)	

36	HIC 151 Mu1 warm return		(0.0)	

37	HIC 104 Shield bypass		(0.55)	

38	PDI 104 Shield press. drop	(0.8)	

39	HIC 145 Mu1 JT valve		(0.0)	

40	HIC 144 Mu1 return		(9.9)	

41	SI 110 T1 speed			(4500)	

42	SI 120 T2 speed			(3200)	

43	Hic 110 T1 brake		(0.7)	

44	HIC 120 T2 brake		(0.75)	

45	HIC 146 Mu2 supply		(0.0)	

46	PI 146 Mu2 supply press.	(8.2)	

47	HIC 153 Mu2 warm return		(0.0)	

48	HIC 142 power leads supply	(0.51)	

49	HIC 147 Mu2 JT valve		(0.45)	

50	HIC 155 JT bypass		(0.0)	

51	HIC 105 shield heater		(0.56)	

52	Shield heat load %		(40)	

	COMPRESSOR DISCHARGE PRESSURE PIC 229

53	Auto/ manual			(auto)	

54	Set point (green)		(11)	

55	Reading (red)			(11)	

56	Output (upper)			(0.6)	

57	Output (lower)			(0.6)	

	COMPRESSOR SUCTION PRESSURE PIC 218

58	Auto/ manual			(auto)	

59	Set point (green)		(1.1)	

60	Reading (red)			(1.1)	

61	Output (upper)			(0.6)	

62	Output (lower)			(0.6)	

	T2 OUTLET TEMPERATURE TIC 121

63	Auto/ manual			(auto)	

64	Set point (green)		(4)	

65	Reading (red)			(4.3)	

66	Output (upper)			(0.45)	

67	Output (lower)			(0.45)	

	LIQUID HELIUM VESSEL HEATER LIC 108

68	Auto/ manual			(auto)	

69	Set point (green)		(50)	

70	Reading (red)			(52)	

71	Output (upper)			(0.55)	

72	Output (lower)			(0.6)	

73	Slide valve position		(100)	

74	Hours				(????)	

75	PI 108 Lhe vessel pressure	(1.2)	

76	Lhe vessel heater load		(15)	

77	Diffusion pump current		(2.8)	

78	PI 100 cold box inlet press.	(10.5)	

79	PI 130 cold box outlet press.	(1.05)	

80	TE 150 Mu1 supply		(1.3)	

81	TE 151 Mu1 return		(1.0)	

82	TE 152 Mu2 supply		(-3.5)	

83	TE 103 shield return		(70)	

84	TE 106 T1 inlet			(73.0)	

85	TE 107 Hx5 high press out	(2.5)	

86	TE109 Hx5 low press in		(1.3)	

87	TE 153 Mu2 return		(0.5)	

88	TE 130 low press. Outlet	(285)	

89	TE 102 Adsorber			(83.0)	

90	Vessel pressure	Head 1 	    (0.0x10-4)	

91	Backing pressure Head 2     (4.2x10-2)	

92	Solenoid vacuum	Head 3 	    (0.0x10-4)	

93	BIG1 solenoid vacuum	    (3.5x10-7)	

94	BIG2 solenoid backing	    (5.0x10-2)	

95	Turbine 1 temp.			(-20)	

96	Turbine 2 temp.			(-23)	

97	Air pressure			(95)	

98	Solenoid current		(???)	

	SOLENOID GAUGE PACKAGE

99	PAI 1				(9.5)	

100	PI 2				(7.7)	

101	PI3				(7.5)	

102	PAI 4				(6.0)	

103	PI 5				(5.5)	

104	PI6				(9.0)	

105	Power lead flow positive	(>250)	

106	Power lead flow negative	(>250)	

107	Water pressure in		(70)	

108	Water pressure out		(35)	
  1   Sat Oct 16 17:14:11 2004 Willy Andersson  Daily log for Sat 16 Oct 2004 05:13:50 PM PDT
	COMPRESSOR BUILDING

1	Oil cooler water inlet temp. 	(28)	
 
2	Oil cooler water exit temp. 	(30)	

3	Gas cooler water exit temp.	(25)	

4	Suction gas temp.		(23)	

5	Discharge gas temp.		(82)	

6	Final gas temp.			(23)	

7	Oil temp.			(40)	

8	Suction gas press.		(0.1)	

9	Discharge press.		(10.8)	

10	Final gas press.		(10.5)	

11	Oil press.			(13.0)	 

12	Oil filter out press.		(10.2)	

13	Compressor current		(270)	

14	Oil pump current		(5.1)	

15	Hours				(????)	

16	Warning lights			(ok)	

17	Oil level			(9.0)	

18	Gas cooler water inlet temp.	(72)	

19 	Gas cooler water flow		(16)	

20	Oil cooler water flow		(135)	

21	Water pump pressure		(65)	

22	Water pump condition		(ok)	

23	Cu. non-active water flow	(165)	

24	PI9 Buffer tank pressure	(15)	

25	PI218 Low pressure		(3.0)	

26	PI229 High pressure		(145)	

27	PI296 Inlet press.		(147)	

28	Air compressor condition	(ok)	

	SULZER CONTROL PANEL

29	PI 110-1 T1 inlet press.	(9.4)	

30	PI 120-1 T2 inlet press.	(4.0)	

31	HIC 106 Turbine inlet press.	(9.9)	

32	TI 148 Mu1 supply temp.		(4.05)	

33	TI 149 Mu1 supply temp.		(4.05)	

34	HIC 143 Mu1 supply		(9.9)	

35	PI 143 Mu1 supply pressure	(10.4)	

36	HIC 151 Mu1 warm return		(0.0)	

37	HIC 104 Shield bypass		(0.55)	

38	PDI 104 Shield press. drop	(0.8)	

39	HIC 145 Mu1 JT valve		(0.0)	

40	HIC 144 Mu1 return		(9.9)	

41	SI 110 T1 speed			(4500)	

42	SI 120 T2 speed			(3200)	

43	Hic 110 T1 brake		(0.7)	

44	HIC 120 T2 brake		(0.75)	

45	HIC 146 Mu2 supply		(0.0)	

46	PI 146 Mu2 supply press.	(8.2)	

47	HIC 153 Mu2 warm return		(0.0)	

48	HIC 142 power leads supply	(0.51)	

49	HIC 147 Mu2 JT valve		(0.45)	

50	HIC 155 JT bypass		(0.0)	

51	HIC 105 shield heater		(0.56)	

52	Shield heat load %		(40)	

	COMPRESSOR DISCHARGE PRESSURE PIC 229

53	Auto/ manual			(auto)	

54	Set point (green)		(11)	

55	Reading (red)			(11)	

56	Output (upper)			(0.6)	

57	Output (lower)			(0.6)	

	COMPRESSOR SUCTION PRESSURE PIC 218

58	Auto/ manual			(auto)	

59	Set point (green)		(1.1)	

60	Reading (red)			(1.1)	

61	Output (upper)			(0.6)	

62	Output (lower)			(0.6)	

	T2 OUTLET TEMPERATURE TIC 121

63	Auto/ manual			(auto)	

64	Set point (green)		(4)	

65	Reading (red)			(4.3)	

66	Output (upper)			(0.45)	

67	Output (lower)			(0.45)	

	LIQUID HELIUM VESSEL HEATER LIC 108

68	Auto/ manual			(auto)	

69	Set point (green)		(50)	

70	Reading (red)			(52)	

71	Output (upper)			(0.55)	

72	Output (lower)			(0.6)	

73	Slide valve position		(100)	

74	Hours				(????)	

75	PI 108 Lhe vessel pressure	(1.2)	

76	Lhe vessel heater load		(15)	

77	Diffusion pump current		(2.8)	

78	PI 100 cold box inlet press.	(10.5)	

79	PI 130 cold box outlet press.	(1.05)	

80	TE 150 Mu1 supply		(1.3)	

81	TE 151 Mu1 return		(1.0)	

82	TE 152 Mu2 supply		(-3.5)	

83	TE 103 shield return		(70)	

84	TE 106 T1 inlet			(73.0)	

85	TE 107 Hx5 high press out	(2.5)	

86	TE109 Hx5 low press in		(1.3)	

87	TE 153 Mu2 return		(0.5)	

88	TE 130 low press. Outlet	(285)	

89	TE 102 Adsorber			(83.0)	

90	Vessel pressure	Head 1 	    (0.0x10-4)	

91	Backing pressure Head 2     (4.2x10-2)	

92	Solenoid vacuum	Head 3 	    (0.0x10-4)	

93	BIG1 solenoid vacuum	    (3.5x10-7)	

94	BIG2 solenoid backing	    (5.0x10-2)	

95	Turbine 1 temp.			(-20)	

96	Turbine 2 temp.			(-23)	

97	Air pressure			(95)	

98	Solenoid current		(???)	

	SOLENOID GAUGE PACKAGE

99	PAI 1				(9.5)	

100	PI 2				(7.7)	

101	PI3				(7.5)	

102	PAI 4				(6.0)	

103	PI 5				(5.5)	

104	PI6				(9.0)	

105	Power lead flow positive	(>250)	

106	Power lead flow negative	(>250)	

107	Water pressure in		(70)	

108	Water pressure out		(35)	
ELOG V2.9.2-2455